This quick guide does not subsitute the Mounting and
Operating Instructions EB 5724-8 EN supplied with the device.
Read the safety instructions and warnings in the Mounting and
Operating Instructions.
Description
The TROVIS5724-x Electric Actuators with Process Controllers
are a combination of an electric actuator and an integrated
digital controller with two PID control modules. 14 ready-to-
use congurations (system code numbers) allow a wide variety
of control tasks to be implemented for heating and cooling
applications (see table below).
Device versions
TROVIS 5724-8: Electric actuator with process controller,
without fail-safe action
TROVIS 5725-8: Electric actuator with process controller,
with fail-safe action
Device version
Connecting
lead
Pt 1000
sensors Control line
[A] 1) Two-wire 2 None
[B] 2) Three-wire 2 None
[C] 3) Two-wire 2 Four-wire
[D] 4) Three-wire 2 Four-wire
1) Suitable for system code numbers 20, 60
2) Suitable for system code numbers 1, 10, 21, 30, 50, 70, 80
3) Suitable for system code numbers 65, 66
4) Suitable for system code numbers 35, 55, 95
Mounting position
The electric control valve can be mounted in the pipeline in
any desired position. However, the actuator must not be
installed in a suspended position.
Start-up
1. Realign the scale for travel indication when a three-way
mixing valve is used.
No action needs to be taken when a globe valve or a
three-way diverting valve is used.
2. Install the valve in the pipeline.
3. Mount the actuator on the valve.
4. Install the ready-wired sensors.
5. Connect the actuator to the power supply (230V, 50Hz)
and start initialization.
6. Congure the actuator over the TROVIS-VIEW software.
Detailed information on TROVIS-VIEW can be found in
the menu [? > Operating Instructions TROVIS-VIEW].
The electric actuator with process controller is ready for
use and can be operated on site.
Readings and operation
The readings and operation depend on how the device has
been congured. Check the applicable parameter settings to
obtain an overview of the activated readings and possible
functions.
The reading on the display depends on A3.1 parameter.
Actual value of controller [1]
A3.1 - 1
Actual value of controller [2]
A3.1 - 2
Press to display following reading (depending on A2.1
parameter).
Measured value AI1 A3.1 - 1
Measured value AI1 after function generation A3.1 - 2
Measured value AI2 A3.1 - 3
Measured value AI2 after function generation A3.1 - 4
Measured value AI3 A3.1 - 5
Measured value AI3 after function generation A3.1 - 6
Measured value AI4 A3.1 - 7
Measured value AI4 after function generation A3.1 - 8
Actual value before comparator of controller [1] A3.1 - 9
Set point before comparator of controller [1] A3.1 - 10
Set point deviation of controller [1] A3.1 - 11
Actual value before comparator of controller [2] A3.1 - 12
Set point before comparator of controller [2] A3.1 - 13
Set point deviation of controller [2] A3.1 - 14
Set point before program controller A3.1 - 15
Press to display following reading (depending on A2.1
parameter).
Set point of controller [1],
change set point with and A2.1 - 1
Set point of controller [2],
then change set point with and A2.1 - 2
Set point of controller [1] A2.1 - 3
Set point of controller [2] A2.1 - 4
Set point before comparator of controller [1] A2.1 - 5
Set point before comparator of controller [2] A2.1 - 6
Press and to perform operating functions depending on
A1.1 parameter.
For cooling applications, A1.1-1 is set by default, for heating
applications A1.1-2.
Start control sequence
Stop control sequence A1.1 - 1
Set point reading
Start set point change,
then change set point with and
A1.1 - 2
Activate external set point
Activate internal set point A1.1 - 3
Start/halt program controller
Cancel program controller A1.1 - 4
TROVIS 5724-8 and TROVIS 5725-8 Electric Actuators with Process Controllers
System code number 0 1 10 30 35 50 55 70 95 20 21 60 65 66 80
Setting
Heating
Adjustable as required
••••••••
Cooling ••••••
Fixed set point/follow-up control
•••• •••
Diff. temperature •
Mean value • •
Override control •• •••
Cascade control • •
Return ow temp. limitation • • •
Outdoor temp. based control • •
Digital input • •
Switching output ••••••• • •
Recommended version – B B B D B D B D A B A C C B
Edition October 2015 Quick Guide KA 5724-8 EN