Trox Technik RM-O-3-D User manual

I n s t al l at i on an d op erat i n g m an u al
D u ct s m ok e det ect or
R M - O - 3 - D
to prov id e the control input signal f or f ire d ampers and smok e
protection d ampers
G eneral build ing inspectorate licence
Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)
Z-78.6-125

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)2
Subj ect to change / All rights reserv ed © TROX G mbH
C on t en t s
TR O X G m b H
Heinrich-Trox -Platz
47504 Neuk irchen-Vluyn, G ermany
Phone +49 (0) 2845 2020
F ax +49 (0) 2845 202265
E-mail trox @ trox .d e
w w w .trox technik .com
1G en eral i n f orm at i on 3
Other applicable d ocumentation __________ 3
Symbols used in this manual _____________ 3
Symbols used on the RM-O-3-D d uct smok e
detector_____________________________ 3
2 S af et y an d correct u s e 4
G eneral inf ormation regard ing saf ety _______ 4
Stand ard s and guid elines________________ 4
Repair and replacement parts ____________ 4
Env ironmental protection ________________ 4
Correct use ___________________________ 4
I ncorrect use __________________________ 4
Resid ual risk s _________________________ 4
3Produ ct des cri p t i on 5
F unctional d escription __________________ 5
Parts of RM-O-3-D _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5
Operating status LEDs __________________ 6
4Tech n i cal dat a 7
5Tran s p ort , s t orage, an d p ack agi n g 7
Deliv ery check ________________________ 7
Transport on site _______________________ 7
Storage ______________________________ 7
Pack aging ____________________________ 7
6I n s t al l at i on 8
I nstallation in f ire d amper F K -EU __________ 8
I nstallation in a d uct or an ex tension piece_ _ _ 9
7E l ect ri cal i n s t al l at i on 10
Supply v oltage 230 V AC _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 10
Supply v oltage 24 V DC _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 10
Connecting a f ire d amper or smok e protection
d amper _____________________________ 10
Connecting a f an _____________________ 10
Connecting a contamination ind icator _____ 10
Connecting an ex ternal reset push button _ _ 10
8C om m i s s i on i n g/ f u n ct i on al t es t 11
9M ai n t en an ce 12
Maintenance _________________________ 12
I nspection ___________________________ 12
Repair ______________________________ 12
10 C l ean i n g 12
Remov ing the sensor head ______________ 12
F itting the sensor head _________________ 12

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018) 3
1 G en eral i n f orm at i on
This operating manual d escribes the f ollow ing v ari-
ants of the d uct smok e d etector:
• RM-O-3-D f or 24 V DC supply
• RM-O-3-D f or 230 V AC supply
To ensure correct f unctioning of the RM-O-3-D
d uct smok e d etector it is essential to read the pro-
v id ed operating manual bef ore starting any w ork ,
and to comply w ith it. This manual must be giv en to
the system ow ner w hen hand ing ov er the system.
The system ow ner must includ e the manual w ith
the system d ocumentation.
The manuf acturer d oes not accept any liability f or
any malf unction or d amage resulting f rom
non-compliance w ith this manual or non-compli-
ance w ith relev ant statutory regulations.
This operating manual is intend ed f or specialist
consultants, d ev elopers, and ow ners of the v entila-
tion systems in w hich the d uct smok e d etector is to
be installed . This manual is also intend ed f or peo-
ple cond ucting the f ollow ing w ork :
•Transport and storage
•I nstallation
•Electrical connection
•Commissioning
•Maintenance
•Cleaning
O t h er ap p l i cab l e docu m en t at i on
The general build ing inspectorate licence no.
Z-78.6-125 also applies. Dow nload : w w w .trox tech-
nik .com
S y m b ol s u s ed i n t h i s m an u al
D an ger!
Designates d anger to lif e and limb d ue to
electrical v oltage.
N ot e
Designates important notes or
inf ormation.
S y m b ol s u s ed on t h e R M - O - 3 - D du ct
s m ok e det ect or
D an ger!
Danger of electric shock f rom liv e compo-
nents w hen you open the casing!
•Only sk illed q ualif ied electricians should
open the casing.
•Sw itch of f the pow er supply bef ore w ork -
ing on any electrical eq uipment.

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)4
2 S af et y an d correct u s e
G en eral i n f orm at i on regardi n g s af et y
Only specialist personnel are allow ed to perf orm
the d escribed w ork on the d uct smok e d etector.
Only sk illed q ualif ied electricians are allow ed to
w ork on the electrical system.
The installation location must be easily accessible
and hav e suf f icient clearance f or electrical connec-
tion and maintenance of the d uct smok e d etector
S t an dards an d gu i del i n es
Compliance w ith the f ollow ing regulations and
guid elines is req uired f or any j ob perf ormed on the
d uct smok e d etector:
• Eq uipment and Prod uct Saf ety Law s
•I nd ustrial Health and Saf ety Regulation
•Build ing regulations
• Accid ent Prev ention Regulations (BG V A1, BG V
A3)
•Maintenance stand ard s DI N 31051 and
EN 13306
•DI N 14675
•Any ad d itional related f ire protection stand ard s
and regulations
R ep ai r an d rep l acem en t p art s
The RM-O-3-D d uct smok e d etector is a saf ety
related prod uct that has been especially d ev el-
oped f or the f ire protection in v entilation systems.
To maintain the f unction, use only original TROX
replacement parts.
E n v i ron m en t al p rot ect i on
To protect the env ironment k eep the f ollow ing in
mind :
• Dispose of pack aging in an env ironmentally
sound manner.
• Af ter f inal d ecommissioning, hav e the d uct
smok e d etector d isposed of by an authorised
company.
•Dispose of electronic components accord ing to
the local electronic w aste regulations.
C orrect u s e
The RM-O-3-D d uct smok e d etector is used to sig-
nal to and release f ire d ampers and smok e
protection d ampers to prev ent f ire and smok e f rom
spread ing through d ucting.
The d uct smok e d etector can also be used to
sw itch of f f ans in a v entilation system.
F ire d ampers or smok e protection d ampers must
be f itted w ith an electric spring return actuator, an
electromagnet or a solenoid v alv e.
The d uct smok e d etector must only be used in
compliance w ith general build ing inspectorate li-
cence Z-78.6-125. The installation d etails and the
technical d ata in this manual also apply.
I n correct u s e
The f ollow ing applications are not allow ed :
• U se in ex tract air systems in commercial k itchens
(k itchen ex tract air in general)
•U se in potentially ex plosiv e atmospheres
•U se outd oors w ithout suf f icient protection
against the ef f ects of w eather
• U se in v entilation systems in w hich high lev els of
d ust and pollution, ex treme humid ity, or chemical
contamination impair the f unction of the prod uct.
•I nstallation in a w ay that prev ents inspection,
cleaning or testing.
Mod if ying the d uct smok e d etector or using re-
placement parts that hav e not been approv ed by
TROX is not permitted .
R es i du al ri s k s
TROX prod ucts are subj ect to strict q uality controls
d uring manuf acturing. I n ad d ition, a f unctional test
is perf ormed bef ore shipping.
Damage can, how ev er, occur d uring transport or
installation and impair the f unction of a prod uct.
I n any case, the proper f unction of the d uct smok e
d etector must be check ed d uring commissioning
and ensured through regular maintenance w hile in
use.

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018) 5
3 Produ ct des cri p t i on
F u n ct i on al des cri p t i on
To prev ent smok e f rom spread ing in build ings, it is
ex tremely important that it is d etected at an early
stage.
The RM-O-3-D d uct smok e d etector is used to sig-
nal to and release f ire d ampers and smok e
protection d ampers. The d uct smok e d etector op-
erates on the principle of light scattering and
d etects the smok e regard less of its temperature so
that f ire d ampers can be closed bef ore the release
temperature is reached .
The d uct smok e d etector can also be used to
sw itch of f f ans in a v entilation system.
F ire d ampers and smok e protection d ampers close
because the pow er supply is cut of f w hen smok e is
d etected .
The d uct smok e d etector is suitable f or f ire d amp-
ers and smok e protection d ampers that are f itted
w ith one of the f ollow ing:
• Electric spring return actuator (pow er of f to close)
•Pneumatic actuator (pressure of f to close)
•Electromagnet
①
②
③
④
⑤
⑥
⑦
⑤
④
③
②
①
⑦
⑥
Part s of R M - O - 3 - D

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)6
1 1 PageHeaderToc3 Produ k t b es ch rei b u n g
O p erat i n g s t at u s L E D s
L E D O p erat i n g s t at u s D am p er b l ade
p os i t i on
R ed Y el l ow G reen
A l arm rel ay S i gn al rel ay
Read y
Supply v oltage OK
3412
No v oltage
3412
Supply v oltage OK
Electrical error
No d uct smok e d etector
– A l arm - i m m edi at e rel eas e –
3412
Contamination
70% .... 90%
3412
Contamination
> 90%
– A l arm - i m m edi at e rel eas e –
3412
Test/Reset
– I n s p ect i on –
3412
Smoke d etected
– A l arm - i m m edi at e rel eas e –
3412
LED on
LED of f
LED blink ing
1) Contamination
> 90% – Alarm
2) I f there is an alarm because smoke has been d etected
(smok e incid ent or maintenance), you can only reset the
d uct smok e d etector w ith the reset button af ter the d uct
smoke d etector is f ree f rom smoke again.

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018) 7
4 Tech n i cal dat a
R M - O - 3 - D
E M C i m m u n i t y t o
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
S u p p l y v ol t age
230 V AC + 10 / – 15%
50/60 Hz
or
24 V DC ± 6%
Pow er rat i n g
3 VA
M i cro f u s e
T 100 L 250 V
Prot ect i on l ev el
I P 42
A m b i en t t em p erat u re
0 ° C … + 60 ° C
A i rf l ow v el oci t y :
1 m/s ... 20 m/s
A ccep t ab l e h u m i di t y
cond ensation
A l arm t h res h ol d f or
i n creas ed
con t am i n at i on
> 70%
S y s t em m on i t ori n g
• > 90% contaminated
• No d uct smok e
d etector
•Data transmission to
d uct smok e d etector
has f ailed
A l arm rel ay con t act
( rel eas e,
con t am i n at i on )
250 V 2 A
W ei gh t
0 . 7 k g
5 Tran s p ort , s t orage an d
p ack agi n g
D el i v ery ch eck
Check d eliv ered items immed iately af ter arriv al f or
transport d amage and completeness. I n case of
any d amage or an incomplete shipment, contact
the shipping company and your supplier immed i-
ately.
A complete shipment includ es:
•Duct smok e d etector RM-O-3-D
•Operating and installation manual
Tran s p ort on s i t e
I f possible, tak e the prod uct in its transport pack ag-
ing up to the installation location.
S t orage
F or temporary storage please note:
•Remov e the plastic w rapping
•Protect the prod uct f rom d ust and contamination.
• Store the prod uct in a d ry place and aw ay f rom
d irect sunlight.
• Do not ex pose the prod uct (not ev en w ith its
pack aging) to the ef f ects of w eather.
• Do not store the prod uct below -40 ° C or abov e
50 ° C.
Pack agi n g
Properly d ispose of pack aging material.

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)8
1 1 PageHeaderToc6 I n s t al l at i on
I n s t al l at i on i n f i re dam p er F K - E U
The RM-O-3-D d uct smok e d etector can be in-
stalled into the inspection access of F K -EU f ire
d ampers. F or the ex act position see the illustration
on the right.
I f F K -EU is used as an air transf er d amper accord -
ing to general build ing inspectorate licence
Z-6.50-2031:
I nstall the RM-O-3-D d uct smok e d etector in the
upper inspection access of the f ire d amper.
Proceed as f ollow s:
1. ③
②
④
panel is used f or centering).
2. Remov e the inspection access panel by turning
and lif ting it.
3. ①
⑤
ad apter.
4. Connect the f ire d amper electrically to the d uct
smok e d etector, siehe „ Elek trische I nstallation“
auf Seite 10.
N ot e:
Old er F K -K 90 and F K -EU f ire d ampers may hav e
an inspection access panel mad e of metal.
I n this case you can remov e the inspection access
panel and install the d uct smok e d etector w ith
w ashers and w ing nuts in the f ire d amper (no
ad apter req uired ).
①
②
d amper
③
G alv anised : A00000043410
Stainless steel: A00000043411
④
⑤
①
③
④②
⑤
I n s t al l at i on i n F K - E U
H 200 – 320 H 200 – 800
I n s t al l at i on l ocat i on b as ed on h ei gh t
H

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018) 9
2 1 PageHeaderToc6 E i n b au
I n s t al l at i on i n t o a du ct or an ex t en s i on
p i ece
Proceed as f ollow s to install the RM-O-3-D d uct
smok e d etector:
N ot e
The sensor head has to be permanently in
the airf low as otherw ise its f unction w ill be
impaired . Conseq uently:
•1.5 × H minimum d istance betw een d uct
smok e d etector and any bend , control
unit or other obstacle.
• Place the d uct smok e d etector in the up-
per third of the d uct (not near a corner).
1. Decid e upon an installation location and af f ix
①
2. Create an opening f or the sensor head of the
d uct smok e d etector.
3. Drill holes f or the self -tapping screw s.
4. ②
③
5. Connect the f ire d amper electrically to the d uct
smok e d etector, siehe „ Elek trische I nstallation“
auf Seite 10.
①
②
③
D u ct i n s t al l at i on
① ② ③
Rauchauslöseeinrichtung
Auslösung / relase
Verschmutzung / pollution
Betrieb / operation
Test / Reset
Typ RM-O-3-D
A
A
Ø100
Ø140
Ø180
Ø160
~ 40~ 95
Ø7
23
Ø13
D i m en s i on s

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)10
1 1 PageHeaderToc7 E l ect ri cal i n s t al l at i on
L1 1234 12NL1 N PE PE
L1 L2 L3
–+ S1 S2 S3 S4 S5 S6
5–250 V
AC / DC
N(
–) L(+)
PE N L
230 V AC
①
②
③
⑤
④
⑥
⑦
NL
23 0 V A C s u p p l y v ol t age
D an ger!
Danger of electric shock ! Do not touch any
liv e components! Electrical eq uipment
carries a d angerous electrical v oltage.
•Only sk illed q ualif ied electricians are al-
low ed to w ork on the electrical system.
•Sw itch of f the pow er supply bef ore w ork -
ing on any electrical eq uipment.
B e s u re t o com p l y w i t h t h e gu i del i n es of y ou r
n at i on al as s oci at i on f or el ect ri cal an d el ec-
t ron i c t ech n ol ogy as w el l as w i t h t h e
regu l at i on s of t h e l ocal p ow er u t i l i t y f or an y
w i ri n g j ob .
Be sure to comply w ith any applicable national or
local regulations, in particular the guid eline regard -
ing f ire protection req uirements on v entilation
systems.
S u p p l y v ol t age 23 0 V A C
Terminal strip L1, terminal L1 / N / PE
Mak e the connection accord ing to the w iring ex am-
ple (see f igure).
S u p p l y v ol t age 24 V D C
Terminal strip L4, terminal + / –
Mak e the connection accord ing to the w iring ex am-
ple on Seite 11.
Connection of a 24 V DC v oltage source req uires
as only that PCB w ill release a d amper if there are
-
et by others.
C on n ect i n g a f i re dam p er or s m ok e
p rot ect i on dam p er
Terminal strip L2, terminal 3 / 4
Y ou can connect sev eral f ire d ampers or smok e
protection d ampers in parallel as long as the ac-
ceptable sw itch rating (see Seite 7) is not
ex ceed ed .
C on n ect i n g a f an
Terminal strip L2, terminal 3 / 4
Y ou can also hav e the d uct smok e d etector sw itch
of the f an as long as the acceptable sw itch rating
(see Seite 7) is not ex ceed ed . Higher sw itch
ratings req uire aux iliary relays.
C on n ect i n g a con t am i n at i on i n di cat or
Terminal strip L2, terminals 1 –2
I t is possible to connect relays or ind icator lights
and to signal to the f ire alarm system as long as the
acceptable sw itch rating (see Seite 7) is not
ex ceed ed .
C on n ect i n g an ex t ern al res et p u s h b u t t on
Terminal strip L3, terminals 1 and 2

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018) 11
2 1 PageHeaderToc7 E l ek t ri s ch e I n s t al l at i on 8 F u n ct i on al t es t /
com m i s s i on i n g
A f unctional test should be carried out bef ore com-
missioning, then ev ery 12 months and af ter any
mod if ication, e.g. repair.
W i t h ou t s m ok e
Press the test/reset push button on the d uct smok e
d etector or in the engineering room (option).
The v oltage supply to the smok e d etector w hich is
attached to the f ire d amper or smok e protection
d amper is interrupted , and the d amper closes as a
conseq uence.
Once the push button has been released , the
d amper OPENS, either by means of a spring return
actuator or a pneumatic actuator.
N ot e
F ire d ampers w hose release mechanism
includ es electromagnets can be opened
manually.
W i t h s m ok e
Spray test gas into the d uct through the opening
right nex t to the d uct smok e d etector
I f the threshold v alue is ex ceed ed , the v oltage sup-
ply to the d uct smok e d etector w hich is attached to
the f ire d amper or smok e protection d amper is in-
terrupted , and the d amper closes as a
conseq uence.
To reopen the d amper af ter the sensor head has
become f ree of smok e, press the test/reset push
button on the d uct smok e d etector.
Once the push button has been released , the
d amper OPENS, either by means of a spring return
actuator or a pneumatic actuator.
N ot e
F ire d ampers w hose release mechanism
includ es electromagnets can be opened
manually.
All operating, w arning and alarm f unctions are d e-
scribed on page 4.
24 V D C s u p p l y v ol t age
L1 1234 12NL1 N PE PE
L1 L2 L3
–+ S1 S2 S3 S4 S5 S6
5–250 V
AC / DC
+–+–
24 V DC
L4
N(
–) L(+)
–+
①
②
③
⑤
④
⑥
⑦
①
②
③
④ -
lease mechanism
⑤
⑥
⑦

Operating manual RM-O-3-D / Technical leaf let no. M375DD8 (05/2018)12
9 M ai n t en an ce
D an ger!
Danger of electric shock ! Do not touch any
liv e components! Electrical eq uipment
carries a d angerous electrical v oltage.
• Do not open the casing f or cleaning.
• Do not use any liq uid s near the d uct
smok e d etector.
I f the contamination is > 70% (yellow LED is illumi-
nated ) the d uct smok e d etector should be cleaned .
• Clean it w ith compressed air that is f ree f rom oil
or w ater.
Should this not suf f ice, the sensor head has to be
replaced (ord er no. M536HC7).
•Remov e contamination f rom the mesh f ilter on
the air inlets.
R em ov i n g t h e s en s or h ead
• ①
d uct.
• ②
released .
• ③
F i t t i n g t h e s en s or h ead
• ② ③
• Turn the sensor head on the base to engage it
w ith the base.
• Turn the sensor head clock w ise until it click s into
place (you should hear this).
N ot e
A f unctional test is req uired w hen the sen-
sor head has been replaced .
①
②
③
D an ger!
Danger of electric shock ! Do not touch any
liv e components! Electrical eq uipment
carries a d angerous electrical v oltage.
•Only sk illed q ualif ied electricians are al-
low ed to w ork on the electrical system.
•Sw itch of f the pow er supply bef ore w ork -
ing on any electrical eq uipment.
Regular care and maintenance ensure operational
read iness, f unctional reliability and long serv ice lif e
of the d uct smok e d etector.
Maintenance must comply w ith EN 13306 and DI N
31051.
The system ow ner is responsible f or maintenance.
The system ow ner is responsible f or creating a
maintenance plan, f or d ef ining the maintenance
goals, and f or the f unctional reliability of the eq uip-
ment.
M ai n t en an ce
The sensor head has to be replaced af ter 8 years
All the other parts of the RM-O-3-D d uct smok e
d etector are not subj ect to w ear and hence mainte-
nance-f ree.
I n s p ect i on
Duct smok e d etectors must be inspected bef ore
commissioning and af ter any mod if ication.
Af ter that, the f unctional reliability of the d uct
smok e d etector has to be ex amined w ith a test gas
or smok e at least ev ery 12 months. Local req uire-
ments and build ing regulations must be complied
w ith.
The test of ev ery d uct smok e d etector must be d oc-
umented and ev aluated . I f the req uirements are not
f ully met, suitable remed ial action must be tak en.
R ep ai r
F or saf ety reasons, repair w ork must only be car-
ried out by ex pert q ualif ied personnel or the
manuf acturer. Only original replacement parts are
to be used . A f unctional test is req uired af ter any
repair, see " F unctional test/
commissioning" on page 11.
10 C l ean i n g