firstalert.com
ARCHITECTURAL A N D ENGINEERING SPEC
INSTALLATION OFALA R M
The smoke alarm shall be a First Alert Model SA320 and shall provide at a minimum the
following features and functions:
1. Two smoke sensing chambers - photoelectric and ionization.
2. Powered by two AAalkaline batteries andhave a solid state piezo horn ratedat
85dB at 10ft. and shall be capable of self restoring.
3. A visual power-onindicator to confirm unit is receiving power.
4. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm
condition hassubsided. Low battery latch: to visually identify whichunit isin low
battery condition. Two Silence Features: Alarm Silence to temporarily silence
nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8hours.
5. Two Locking features - tamper resistant locking pinsthat lock battery drawer
and/or alarm to mounting bracket.
6. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and
relative humidity between 10% and95%.
7. The unit shall contain mounting hardware and shall be listed for wallor ceiling
mounting.
8. The unit shall have a gasketless base for easy installationand be capable of
keeping alarm secure over a wide rotationrange to allow for true alarm
alignment.
9. The unit shallat a minimum meet the requirements of UL217, CSFM,
NFPA 72and the ICC.
SHIPPING SPECS:
TECHNICAL SPE C S
Individual Carton Dimensions 2.5"L x 7.0"W x 8.5"H
.sbl37.0thgieW
483700450920CPU
Master Carton Dimensions 7.2"L x 5.4"W x 8.7"H
Master Pack 2
.sbl.761thgieW
200 29054 00738 8:5fo2I
Pallet Information
Cases per Layer 44
Number of Layers: 5
Cases per Pallet: 220
Units per pallet: 440
.sbl395:thgieW
©2011 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901Liberty Street Road
Aurora, IL 60504-8122
All rightsreserved
First Alert is a registered trademark of the First Alert Trust
BRK isa registered trademark of BRK Brands, Inc.
CM3044
CAT.
SA320CN-2
BATTERY DRAWER LOCK
Remove Pin from
Mounting Bracket
Close Door. Insert Pin in Holes
through alarm and BatteryDrawer
5.0"
TOP VIEW SIDE VIEW
MOUNTING
BRACKET
2.0"
THE PARTS OF THIS SMOKE ALARM
BOTTOM OF ALARM
1. Mounting bracket
2. Mounting Slots
3. Battery Drawer - Install
2 AA batteries here
4. Turn this way to
remove from bracket
5. Turn this way to
attach tobracket
TOP OF ALARM
1. Test/Silence button
2. Slide-open
battery drawer
3. Power/Alarm light
Alarm Dimensions: 5.0” dia x 2.0”H
Weight: 8.6 oz
Operating Voltage: Two 1.5V AA alkaline batteries
Temperature Range: 40°F (4°C) to 100°F (38°C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates smoke condition, causing the unit
to alarm. Pressand hold test/silence button
Alarm Reset: Automatic when smoke clears
Smoke Sensors: Photoelectric and Ionization
Indicator Lights/Sounds:
DCPower: Intermittent GreenLED
Local Alarm: Red LED flashes rapidly
Alarm Latch: LED flashes red 2 sec on, 2 sec off after local alarm stops
Low Battery Latch: LED flashes green 2 sec on, 2 sec off
Listing: Listed to UL217 Standard