Turtle Tough TT-HFC User manual

TURTLE
TOUGH
®
TURTLE
TOUGH
®
turtletoughsensors.com
MANUAL
DSS HANDHELD FIELD COMMUNICATOR
Conducvity
CON

TURTLE
TOUGH
®
Product name DSS HandHeld Field Communicator - Conducvity
Code TT-HFC
Mechanical
Housing ABS
Handheld
IP Class Housing IP40
Connector Quick connect plug
Temperature Usage -15 to +50 °C (Storage -35 to +75 °C)
Weight 130 grams with baery (4.6 ounces) 100 grams without baery (3.5 ounces)
Dimensions D 26 x W 60 x H 120 mm (1.0” X 2.4” X 4.7”)
Electrical
Supply 9V baery (Alkaline or Lithium)
~45 mA with DSS sensor “On”
~6 hrs Alkaline or ~12 hrs Lithium
Auto shutdown aer 25 seconds * without communicaon
Smart Digital DSS Modbus RTU Conducvity (EC) Sensors
Baud rate 9600 or 19,200 kbps (selectable)
CE mark EN61326A
* Number of seconds unl auto shutdown starts from when sensor is disconnected from HFC
DSS Handheld Field Communicator
for Conducvity DSS Sensors
The Handheld Field Communicator calibrates and
congures DSS Smart Digital RS485 Modbus RTU
sensors at any locaon. All values stored in non-
volale sensor EEPROM for hot-swap portability
when installed back into eld service.
Specicaons
CON

TURTLE
TOUGH
®
Programming and Navigation
The Handheld Field communicator (HFC) has 3-digit display and 16 LEDs to show readings and analyc data
as well as to calibrate and congure sensor. Programming done by 4 key front panel. ‘Mode’ key used to toggle
and navigate to each LED. ‘Up’ or ‘Down’ buons scroll available opons and adjust values. ‘Mode’ key is used to
make selecons and save entries. ‘View’ key provides addional informaon for the given LED mode (see table for
details on use of ‘View’). Once baud rate and node of connected sensor are entered all parameters are automacally
loaded for zero conguraon plug and play use in the eld.
3-digit display
Use ‘Up’ or ‘Down’ buons
to scroll available opons
and adjust values.
Press ‘View’ for addional
informaon for the given
LED mode
Use ‘Mode’ key to make
selecons & save entries.

TURTLE
TOUGH
®
Intelligent DSS Handheld Field Communicator for Calibraon, Conguraon,
Spot Measurement and Troubleshoong of Smart Digital RS485 Modbus RTU
Conducvity DSS Sensors
LED LABEL Parameter Descripon and Method to Access Range Default
Sensor Type Measurement type
Load opons for connected sensor
‘View’ key shows soware revision
‘Up’ key shows cell constant
‘Mode’ key used to exit and save
any changes and move onto
‘Reading’
pH or ORP or DO or ISE or CON
‘Down’ shows range mode: Standard (Std) /
High (Hi) or else Ultralow (UL)
‘Up’ key then used to iniate toggling
between Std & Hi Range Modes
Per Type
Reading***** Process Parameter ****
Display current calibrated value
0.01-9.99 μS/cm (value is ashing)
10.0-99.9 μS/cm (value is ashing)
100-999 μS/cm (value is ashing)
1.00-9.99 mS/cm (1,000–9,990 μS/cm)
10.0-99.9 mS/cm (10,000–99,900 μS/cm)
100-999 mS/cm (100,000–999,000 μS/
cm)
1.00-4.00 S/cm (Reading LED ashing)
Per
Measured
Soluon
Absolute mS Process Parameter Display the absolute conducvity
value from connector EC sensor
Same as Reading LED mode (see above)
Max raw conducvity is 4,000 mS/cm
Per Sensor
& Media
Cal Temp. Oset calibraon of
temperature in °C **
Adjust temp reading up & down
‘View’ key shows temperature oset ±25.0 °C * from raw value 0.0
Oset Calibraon
Zero Dry in Air **
Denes the oset for dry in air
‘View’ shows current zero oset 0.00 to 2.00 % of the output Per Sensor
Cal Slope Denes Gain **
Denes gain on nominal cell
constant for all measured ranges
‘View’ shows current gain
0.300 to 1.700 mes nominal cell constant
yields eecve apparent calibrated cell
constant in eld use
Per Sensor
Dampener Smoothing dampener
& output delay ***
Sets number of seconds to be used
for dampener for process value(s) 1, 2, 3, 4, 5, 8, 10, 15, 20 or 30 Seconds
10 -
Dampen
1 - Delay
Step Change ‘Up’ & ‘Down’ buon
Sensivity seng
% increment for each me the
‘Up’ or ‘Down’ buon is depressed
Choices: 0.05, 0.10, 0.20, 0.5, 1.0 or 2.0
‘View’ selects TDS for Std/Hi Mode: ‘nA’
(NaCl), ‘PoT’ (KCl) or 442
0.05
Special
Set ATC Coecient
Display Computed EC
Unit 1 (Reg 30005)
Display Computed EC
Unit 2 (Reg 30006)
Set temp compensaon coecient
‘View’ shows PSU for for Std/Hi
MegaOhms (MΩ) for Sensor Type 7
HOLD ‘View’ shows TDS for Std/Hi
UPW MegaOhms (MΩ) for Ultralow
Units are % per °C (Limits are 0.00-9.99)
Salinity range is 0.000 to 50.000 PSU
Resisvity range is 0.000 to 20.000 MΩ
TDS shown in ppt. Convert ppt to ppm
mulply by 1,000 (2.34 ppt is 2,340 ppm)
Per Sensor
Default is
2.00%
Baudrate Baudrate for Com Toggle between 9600 or 19,200 kbps 9600 or 19,200 kbps Per System
Node Address for Com Choose a valid address on network From 001 to 247 Per Sensor
Item/Serial
Number
Sensor Item Number
and Serial Number
Item # denes model; ‘View’ shows
Serial # (unique traceable idener)
Item # from 0-65,535 (>999 is toggled)
Serial # per YY.M-AA.DDD Scheme Per Sensor
Days in Use Total me DSS sensor
is energized
Increments me in use to track
sensor lifeme and predicve
maintenance
0-65,535 in units of days (>999 is toggled)
Within ±2% accuracy for any me in use
Per Sensor
Field Use
Max/Min °C Displays max & Min
Temp in eld use
The max temp in eld use is shown;
Push ‘View’ buon for min temp -40 to +210 °C * Per Sensor
Field Use
* Negave values are always shown as ashing.

TURTLE
TOUGH
®
Color notes
Parameters in light green are dened by factory at dispatch me or determined from eld use.
Parameters in grey can be adjusted as desired.
Parameters in dark green are obtained from wet calibraons done with DSS sensor in the eld.
Scaling Display Notes
When reading is less than 1.00 mS/cm the value will ash indicang that the units are in μS/cm instead of mS/cm.
When reading is greater than 999 mS/cm, ‘Reading LED’ will ash and units will switch to S/cm ( i.e. 1.34 Siemens/
cm is equivalent to 1,340 mS/cm ).
** Holding the ‘View’ key for 3 to 5 seconds in this LED mode shows the ‘Days in Use’ SINCE this calibraon was performed
** Holding BOTH the ‘View’ AND ‘Up’ keys for 3 to 5 seconds in this LED mode will reset all calibraon values back to default
*** Holding the ‘View’ key for 3 to 5 seconds allows for the delay from boot value to be shown as well as adjusted
**** Holding both ‘Up’ & ‘Mode’ keys shows soware rev or both ‘Down’ & ‘Mode’ keys shows build date in Reading LED mode
***** User Adjustable Timeout Feature: Press ‘Down’ + ‘View’ in ‘Reading’ mode to set minutes before automac shuto occurs
• The “Modbus Com” LED is illuminated briey each me that a communicaon packet is sent or received.
• The “Baery Low” LED will at rst ash as warning and then illuminate connuously when the 9V baery
should be replaced.
oMUST Change 9V baery when LED is illuminated to ensure valid readings and calibraons
Smart Digital DSS Conductivity Sensor Features and Basic Usage
The smart digital DSS conducvity sensors with integral Modbus RTU communicaons allows for simple and fully
portable installaon scheme. Sensor may be calibrated anywhere (lab, shop or eld) and interfaced with any data
acquision or control system in the eld via the RS-485 Modbus RTU communicaons. The temperature oset
and process value oset calibraons can be done with sensor le in service to agree with a reference value for an
external measurement device (please see calibraon instrucons). Waterproof and corrosion-resistant NEMA 6P
quick connect plugs comes standard for easy seamless hot-swap of sensors from service for cleaning, recalibraon
and other maintenance tasks as may be required as well as eventual replacement of sensor in me.

TURTLE
TOUGH
®
Setup of DSS RS-485 Modbus RTU Sensor to Handheld Field Communicator
1. Press the ‘Mode’ buon to turn on HFC. The HFC will aempt to communicate with the last used baudrate
and node address. If either no sensor is connected or available at the last used baudrate and node address
then three dashes “---” are shown on display. If no buons is pressed for 25 seconds the HFC will automacally
turn itself o to conserve baery life.
a) If previous baudrate & node are valid HFC will automacally load all relevant LED opons and address-
able parameters for that sensor type.
2. Pressing ‘Mode’ buon navigates to ‘Node’ LED mode. Use ‘Up’ & ‘Down’ keys to scroll to node of the con-
nected sensor. Node informaon is typically found on label of sensor. If this informaon is not available, the
DSS Windows soware can be used scan the sensor in queson to determine the current node address.
The baudrate and node address of the DSS sensors can only be changed by the Windows soware. When
the desired node address is reached press the ‘Mode’ key enter the value.
a) Default nodes: pH is 1, ORP is 2, Wide-Range ORP is 3, DO is 4, ISE is 5, Conducvity is 6. If mulple
sensors of same type are used on one Modbus RTU network then node address for each same type sensor
must dier from default to ensure a unique and valid node address.
3. If baudrate needs to be adjusted (9600 or 19,200 kbps) then the HFC automacally navigates to this LED
mode next.
4. HFC returns to reading mode aer selecng node & baudrate. If selecons are valid then process reading is
shown else three dashes “---” are shown.
5. Press ‘Mode’ buon aer reading LED to toggle to sensor type LED which shows type of sensor that is
connected.
• Inial node of ‘0’ will be shown (press ‘Mode’ when node address is ‘0’ to exit scan mode).
Select starng address for scan with ‘Up’ or ‘Down’ keys. Node address scrolled in increments of 10.
For example, pressing ‘Up’ key gives address of 1à10à20à30… and so forth while pressing ‘Down’ key
gives addresses of à240à230à220… and so forth.
• Press ‘Mode’ to begin scan. Scanning is always performed in an ascending fashion. Scan will stop when sensor
is found. Sensor type for node address found displayed ashing with node address.
• Press ‘Mode’ to select this node and you will enter ‘Reading’ mode.
• Press ‘View’ to connue scanning. If no sensors found when address 247 is reached, then ‘Err’ is displayed.
Press ‘Mode’ to resume scan and repeat these procedures.
** Select the current node for the aached sensor.
If the current node is not known use the node scanning feature to determine it. When in the ‘Baud Rate’ LED
mode, hold the ‘View’ key for at least 3 seconds to iniate the node changing mode. The current node of the
sensor will be shown and the ‘Sensor Type’ and ‘Node’ LED will ash.
If the ‘Mode’ key is pressed immediately aer entering this node changing mode, then no change to the address
will be made since the address displayed will equal the current node address. Use ‘Up’ and ‘Down’ keys to adjust
the nodeto the modied address if desired. Press ‘Mode’ key to enter the new node address selected with ‘Up’ &
‘Down keys.
Notes on adjustable smoothing dampener and output delay
• Dampener LED when DSS-CON sensor is connected allows for display and modicaon of the variable that
is used to set the number of seconds used for the smoothing dampener and delay from boot to send the
output values.
• For intermient operaon, it is recommended to set this dampener and output delay variable to a low number
in order to minimize power consumpon while from baery power sources and maximize sampling me of
process output.

TURTLE
TOUGH
®
Sensor Serial Number, Item Number and Total Time in Field Service
Systemac tracking achieved with factory stamped sensor serial and item number. The internal clock on the
DSS sensor board is incremented when energized to monitor the total number of days in acve eld service.
If the sensor is disconnected the incremenng of the me in service will stop. When the sensor is energized
the incremenng of me in service will once again resume. The number of days in service is always the actual
real-me total usage. The total days in use is shown in days and equally accurate for connuous or intermient
service such that the me in service is accurate even if the sensor is taken in and out of use for cleaning and
re-calibraon and/or swapped between dierent installaons.
Important note before performing calibraons
The me averaging dampener is always on even when performing calibraons. It can be desirable to adjust
dampener to a short value when performing calibraons to make the calibraon process quicker and then reset
the dampener back to a higher value before reinstalling the sensor back into connuous use in eld service
(be sure to remember this last step!)
Temperature Calibraon Instrucons
The temperature is calibrated by pushing the ‘Up’ or ‘Down’ buons when in the temperature display (°C) mode. *
Calibraon of DSS Conducvity Sensors with Handheld Field Communicator
1. Use the ‘Mode’ buon to toggle to ‘Oset’ LED to perform the zero dry in air calibraon. The sensor should
be completely dry and clean before starng this calibraon. Pressing ‘Up’ or ‘Down key will iniate an auto-
calibraon.
2. Use the ‘Mode’ buon to toggle to the ‘Slope’ LED and use ‘Up’ and ‘Down’ keys unl the display reads the de-
sired value in conducvity units. If the number is not ashing and the LED is not ashing the units will be mS/cm.
a. If the number displayed is ashing the units are then μS/cm (divide by 1,000 to get mS/cm units)
b. If the ‘Slope’ LED is ashing, then the units are Siemens/cm (mulply by 1,000 to get mS/cm units)
3. Calibraon values stored inside DSS smart digital conducvity sensor in EEPROM so sensor can be powered
down without loss of calibraon meaning a true plug and play seamless hot-swap measurement system in
the eld.
4. Results of slope calibraons with conducvity sensor can be viewed by pressing the ‘View’ key in ‘Slope’
calibraon LED mode which returns the current gain on the nominal cell used to compute the displayed
conducvity values.

TURTLE
TOUGH
®
Display Features Available Using The ‘View’ Key
• In ‘Node’ mode press ‘View’ key to invoke the node scanning feature (see Instrucons for node scanning and
changing node - page 6).*
• In ‘Baud Rate’ mode press ‘View’ key for 3 to 5 seconds to invoke node changing mode (see Instrucons for
node scanning and changing node - page 6).*
• In ‘Sensor Type’ LED mode, the soware revision for the connected sensor is shown when the ‘View’ key
is pressed.
• In ‘Sensor Type’ LED mode, when ‘Up’ key is pressed then the nominal cell constant of sensor is indicated:
oRange of cell constant is anywhere between K = 0.01/cm up to K= 20.0/cm
• In ‘Sensor Type’ LED mode, when ‘Down’ key is pressed then the currently operang range mode is
displayed.
oPress ‘Up’ key while range mode is displayed to iniate toggling between standard and high range
modes. For the ultralow style sensors only one range mode exists. Press ‘Mode’ to save and exit tog-
gling range modes.
• In ‘Reading’ and ‘Slope’ LED mode the displayed units are mS/cm unless one of the two condions below exists:
oWhen reading is ashing then the units are μS/cm (divide by 1,000 to get mS/cm units)
oWhen the ‘Reading’ or ‘Slope’ LED is ashing then units are Siemens/cm (mulply by 1,000 to get mS/cm)
• In ‘Cal Temp.’ LED mode, the oset in °C * for current temp calibraon is shown when the ‘View’ key is
pressed.
• In ‘Cal Oset’ LED mode, the oset for the dry in air zero calibraon is shown when the ‘View’ key is pressed.
• In ‘Cal Slope’ LED mode, the current gain for the connected DSS conducvity sensor is shown. The limits for
the gain on the nominal cell constant of the given sensor is from 0.300 to 1.700.
oThe calibrated apparent eecve cell constant for the sensor in eld use is obtained by mulplying the
nominal cell constant mes the gain shown as the result of the slope calibraon.
oOutput scaling & limits dened solely based upon the nominal cell constant and range mode in use.
oDays since this calibraon performed shown by holding ‘View’ in the ‘Cal’ mode for 3 to 5 seconds.
If BOTH ‘View’ & ‘Up’ pressed for 3 to 5 seconds in any ‘Cal’ mode will reset all calibraons back to
factory default.
• In ‘Step Change’ LED ‘View’ key displays and toggles TDS units (NaCl, 442, KCl) for std/hi range mode type
sensors.
• In ‘Special’ LED ‘View’ shows salinity in PSU for Std/Hi ranges & resisvity in MegaOhm (MΩ) for ultralow
range.
• In ‘Special’ LED if ‘View’ is pressed for 3 to 5 seconds then total dissolved solids (TDS) in ppt units is shown
for Standard/High ranges and MegaOhm (MΩ) using ultrapure water (UPW) ATC is shown for ultralow range
sensors.
oTo convert from ppt units to the ppm units mulply by 1,000 (i.e. when 3.78 is display this means 3,780 ppm)

TURTLE
TOUGH
®
READ-ONLY Data Core Process Value Descripon READ-ONLY Data Analyc Sensor Value Descripon
Calibrated & Temperature
Compensated Process
Values for DSS-CON(-L)
Conducvity sent as 0 to 50,000
steps for all cell constants & range
modes. To compute conducvity
value sent is mulplied by cell
constant integer (nominal cell * 100)
& range mode scaling factor which
is then nally divided by 50,000 to
yield μS/cm units.
Connected Sensor
Type
1 - DSS-pH
2 - DSS-ORP Standard Range
3 - DSS-ORP Wide Range
4 - DSS-DO (Dissolved Oxygen)
5 - DSS-ISE (Ion Selecve)
6 - DSS-CON (EC Standard/High)
7 - DSS-CON-L (EC Ultralow)
Raw Process Values
Temperature Process Values
Scaling for raw conducvity values
is the same as temperature com-
pensated conducvity values for the
given sensor.
Calibrated temp with the range
-40.0 to +210.0 °C sent as 0 to
2,5000
Sensor Serial Number
Sensor Diagnoscs
Unique Serial Number Designaon:
YY.M-AA.DDD **
Sensor Item Number
Soware Revision
Max Temp in Use
Min Temp in Use
Days in Field Use
Computed units for
DSS-CON(-L)
Computed units of salinity/resisvity
sent as 0-50,000 correspond to
0-50.000 PSU/MΩ
Computed units of total dissolved
solids (TDS) NaCl, 442 or KCl sent
as 0 to 50,000 correspond to 0
to 100,000 ppm. On handheld
communicator the units of ppt are
displayed instead of ppm (1ppt =
1,000ppm
Calibraon Values
Temperature Oset
Days since Temp Oset Cal
Process Oset (Zero Dry in Air)
Days since Process Oset (Zero) Cal
Slope Low Cal
Days since Slope Low Cal
Slope High Cal
Days since Slope High Cal
** Serial format YY is last digits of year; M is month with A=Oct, B= Nov & C=Dec; AA is leer(s) from A to nY (as permissible); DDD is value from 0 to 255
READ/WRITE Type Adjustable Calibraon Descripon READ/WRITE Type Adjustable Parameter Descripon
Oset Adjust Temperature
Calibrated Temperature Value
The temperature to which reading
is adjusted is sent as 0 to 2,500
corresponding to -40.0 to +210.0
°C
Reset Calibraons
Temp. Comp.
Coecient
Will reset all user adjustable sensor
calibraons back to factory default values
Adjustable from 0.00 to 9.99 % per °C as
appropriate for measured sample
Oset to create true zero
for dry in air condion
Dampener
Delay from Boot
Time averaging of process value
Time unl process values are sent from boot
1, 2, 3, 4, 5, 8, 10, 15, 20 or 30 Seconds
Adjust Sensor Slope
Gain on Nomial Cell Constant
Sent as 300 to 1,700 corresponding
to 0.300 to 1.700 mulplier to
nominal cell constant of the sensor
Step Change
Increment value for stepwise calibraon
on the handheld communicator:
0.05, 0.10, 0.20, 0.5, 1.0 or 2.0 % per °C
* Negave values shown as ashing.
.
Note 1: All Modbus devices on network must use the same baudrate and have a unique node address. Handheld Communicator (HFC) is
Modbus master while all DSS sensors are Modbus slaves. To interface HFC with DSS sensor, either removed it from the network, or else bypass
with a bridge box with switch scheme. Access any given DSS sensor on the Modbus network with HFC is possible if the exisng Modbus master
is disconnected or powered down. If node of DSS sensor is not known, use Widows Soware or HFC search feature to nd it. Please see DSS
installaon guide and DSS controller manual for addional recommendaons & details about commissioning, calibraon and troubleshoong.
Access to READ values in Core Process Value Column gained through Modbus funcon code (04).
Note 3: Access to READ parameters in the Analyc Sensor Value Column, Adjustable Calibraon Column & Adjustable Parameters Column
gained through Modbus funcon code (03).
Note 4: Access to WRITE parameters in the Analyc Sensor Value Column, Adjustable Calibraon Column & Adjustable Parameters Column
gained through Modbus funcon code (16).

TURTLE
TOUGH
®
Conducvity Cell Constant and Available Range Modes
for Smart DSS Sensors with RS-485
STANDARD RANGE MODE * - in microSiemens/cm
Cell Constant (K)
CCCC
0.01 200 0.004 2 200 100 66.67
0.02 400 0.008 4 400 200 133.33
0.05 1,000 0.02 10 1,000 500 333.33
0.10 2,000 0.04 20 2,000 1,000 666.67
0.20 4,000 0.08 40 4,000 2,000 1,333.33
0.50 10,000 0.2 100 10,000 5,000 33,33.33
1.00 20,000 0.4 200 20,000 10,000 66,66.67
2.00 40,000 0.8 400 40,000 20,000 13,333.33
3.00 60,000 1.2 600 60,000 30,000 20,000.00
5.00 100,000 2 1,000 100,000 50,000 33,333.33
10.00 200,000 4 2,000 200,000 100,000 66,666.67
20.00 400,000 8 4,000 400,000 200,000 133,333.33
HIGH RANGE MODE * - in microSiemens/cm
Cell Constant (K)
CCCC
0.01 2,000 0.04 20 1000 666.67 500
0.02 4,000 0.08 40 2,000 1,333.33 1,000
0.05 10,000 0.2 100 5,000 3,333.33 2,500
0.10 20,000 0.4 200 10,000 6,666.67 5,000
0.20 40,000 0.8 400 20,000 13,333.33 10,000
0.50 100,000 21,000 50,000 33,333.33 25,000
1.00 200,000 42,000 100,000 66,666.67 50,000
2.00 400,000 84,000 200,000 133,333.33 100,000
3.00 600,000 12 6,000 300,000 200,000.00 150,000
5.00 1,000,000 20 10,000 500,000 3333,33.33 250,000
10.00 2,000,000 40 20,000 1,000,000 666,666.67 500,000
20.00 4,000,000 80 40,000 2,000,000 1,333,333.33 1,000,000
* Sensor can toggle between standard/high range mode range mode while in use. Standard/high range mode sensor is one conguraon and associated
sensor board hardware. Ultralow range mode sensor is a dierent conguraon and associated sensor board. While you can toggle between standard and
high range modes you cannot toggle between the standard/high and ultralow modes since these are two dierent sensor boards. Two slope calibraons are
stored in dual mode standard/high sensors; slope low is used for the standard mode and slope high for the high mode. Slope calibraons are automacally
assigned based upon range mode in use for sensor at me when calibraon is performed. The ultralow range mode only uses the single low slope (slope high
is unused).

TURTLE
TOUGH
®
ULTRA-LOW RANGE MODE * - in microSiemens/cm
Cell Constant (K)
CCCC
0.01 2 0.00004 0.02 2 1 0.667
0.02 40.00008 0.04 4 2 1.333
0.05 10 0.0002 0.1 10 53.333
0.10 20 0.0004 0.2 20 10 6.667
0.20 40 0.0008 0.4 40 20 13.333
0.50 100 0.002 1.0 100 50 33.333
1.00 200 0.004 2.0 200 100 66.667
2.00 400 0.008 4.0 400 200 133.33
Total dissolved solids (TDS) units are computed from measured conducvity.
The curves that dene relaonship between the measured conducvity
and user selectable total dissolved solid (TDS) units of NaCl, KCl or
442 are preprogrammed into sensor with full range of 0 to 100,000
ppm. The actual usable range may be limited by the choice of cell
constant and range mode in which the sensor is operated.
Other types of total dissolved solids (TDS) for other electrolytes
or electrolyte mixtures can be programmed into the sensor on a
special order basis (minimum order requirements apply for such
special programming requests). Inquire to the factory if you have need
for such special TDS units for your smart digital DSS Modbus RTU
conducvity sensors.
Salinity computed from the measured conducvity. Curves that
dene the relaonship between measured conducvity and the
computed salinity in PSU are preprogrammed into the sensor with a
full range of 0.000 to 50.000 PSU.
The actual supported range may be limited by cell constant and
range mode used). Contact the factory to determine the most suitable
sensor model and cell constant conguraon for your desired salinity
range of interest.
Conducvity Cell Constant and Available Range Modes
for Smart DSS Sensors with RS-485

TURTLE
TOUGH
®
The conducvity of pure water varies signicantly with temperature
in a well dened but non-linear fashion as detailed in the graph to le.
This behavior is preprogrammed into the DSS-CON-L Modbus RTU
conducvity sensors for the automac temperature compensaon
feature to make it suitable for ultrapure water (UPW) type applicaons.
Although the recommended cell constant for performing conducvity
measurement in UPW is K=0.01/cm for best resoluon and lower bounds
of measurement there may be situaons where this K=0.01/cm cell
constant cannot be used for the planned installaon locaon because
of limitaons such as piping arrangement and low-ow. The higher cell
constants of K=0.05/cm or K=0.10/cm can be used instead in such cases
albeit they require the sample to be at a higher temperature to ensure
best results. Table below details recommended minimum temperature
for various cell constants for use in UPW. The minimum temperature for
UPW measurement for each cell is determined based upon the lowest
absolute conducvity value for which the cell constant is recommended
& temperature at which this conducvity occurs for UPW. Resisvity
are computed units are the inverse of the measured conducvity value.
Ultralow Range Conducvity Sensors for Ultrapure Water (UPW)
ULTRA-LOW RANGE MODE
Cell Constant (K) Raw Max Input
@ 25°C Resoluon Lowest Recommended
Absolute Measurement Minimum Temp °C * Absolute MegaOhm (MΩ)
@ Min Recommended °C *
0.01 2 0.00004 0.02 8 50
0.05 10 0.0002 0.1 40 10
0.10 20 0.0004 0.2 55 5
* Minimum recommended temperature is conducvity of UPW which is 1% of ultralow range mode for the given cell and the associated MegaOhm units.
Measurements can be performed below the recommended minimum temperature with an associated higher uncertainty for those situaons.
For ultralow range conducvity sensors the 5th read input register
(30005) sends the computed resisvity MegaOhm (MΩ) using
the user dened linear automac temperature compensaon
(ATC) while the 6th read input register (30006) sends computed
resisvity MegaOhm (MΩ) using the special non-linear ultrapure
water style automac temperature compensaon. The resisvity
values sent as 0 to 50,000 steps corresponding to 0.000-50.000
MegaOhm (MΩ) for both the 5th (30005) & 6th (30006) read
input registers. Theorecal temperature compensated resisvity
value can never go above 18.18 MegaOhm (MΩ) for uncon-
taminated pure water since this is the ideal value at 25 degrees
celsius.
Temperature compenated conducvity and resisvity are refer-
enced back to the 25 °C condion for all ATC. Ultrapure water
with no contaminants has a value of 0.055 μS/cm conducvity
or 18.18 MΩ in resisvity. The most common units for mea-
surement of pure water is resisvity (MΩ) MegaOhm due to high
resoluon and convenient scaling in the very low conducvity
levels. Temperature compensated conducvity and computed
resisvity values sent for the ultralow range mode smart digital
DSS-CON-L style Modbus RTU conducvity sensors as well as
the raw conducvity.
Graph above shows relaonship between the resisvity of pure water
at various temperatures. Computed resisvity MegaOhm (MΩ) units
are the inverse of measured conducvity and so are the mirror image
of the conducvity at various temperatures for ultrapure water (UPW).
The graph above shows absolute raw resisvity at various temperatures.
Resisvity values sent include ATC referencing reading to 25 °C state.
Table of contents