APPLICATION
The Model AFS-460–137 is a general pur-
pose airow proving switch designed for 24
VAC HVAC and Energy Management ap-
plications where a manual reset switch with
DPDT contacts is desirable. It may be used
to sense positive, negative, or differential
air pressure.
GENERAL DESCRIPTION &
OPERATION
The plated housing contains a diaphragm, a
calibration spring, a snap-acting switch with
manual reset button, and a dpdt relay.
The sample connections located on each
side of the diaphragm accept .25" OD tub-
ing via the integral compression ferrule and
nut.
An enclosure cover guards against acci-
dental contact with the live switch terminal
screws and the set point adjusting screw.
The enclosure cover will accept a 0.5" con-
duit connection. The manual reset button is
located on the top surface of the enclosure
cover.
MOUNTING (SEE FIGURE 1)
Select a mounting location which is free
from vibration. The AFS-460–137 must be
mounted with the diaphragm in any vertical
plane in order to obtain the lowest specied
operating set point. Avoid mounting with the
(Figure 2)
sample line connections in the "up" position.
Surface mount via the two 3/16" diameter
holes in the integral mounting bracket. The
mounting holes are 3-7/8" apart.
AIR SAMPLING
CONNECTION
(SEE FIGURE 2)
The AFS-460–137 is designed to accept
rm-wall sample lines of ¼" OD tubing by
means of ferrule and nut compression con-
nections. An optional ¼" adapter, suitable
for slip-on exible tubing is available. For
sample lines of up to 10 feet, ¼" OD tubing
is acceptable. For lines up to 20 feet, use ¼"
ID tubing. For lines up to 60 feet, use ½" ID
tubing. Locate the sampling probe a mini-
mum of 1.5 duct diameters downstream from
the air source. Install the sampling probe as
close to the center of the airstream as pos-
sible. Refer to Figure 2 to identify the high
pressure inlet (H), and the low pressure inlet
(L). Select one of the ve application options
listed below, and connect the sample lines
as recommended.
POSITIVE PRESSURE ONLY: Connect
the sample line to inlet H; inlet L remains
open to the atmosphere.
NEGATIVE PRESSURE ONLY: Connect
the sample line to inlet L; inlet H remains
open to the atmosphere.
TWO NEGATIVE SAMPLES: Connect the
higher negative sample to inlet L. Connect
the lower negative sample to inlet H.
TWO POSITIVE SAMPLES: Connect the
higher positive sample to inlet H. Connect
the lower positive sample to inlet L.
ONE POSITIVE AND ONE NEGATIVE
SAMPLE: Connect the positive sample
to inlet H. Connect the negative sample
to inlet L.
Model
AFS–460–137
Manual Reset DPDT Air Pressure Sensing Switch for 24 VAC Applications
SPECIFICATIONS
Model AFS–460–137
Air Pressure Sensing Switch with
Manual Reset Feature,
DPDT Contact Arrangement,
for 24 VAC Applications.
Sample Media:
Air or combustion by-products that
will not degrade silicone.
Mounting Position (in order
to meet lowest operating
specications): Diaphragm in any
vertical plane.
Field Adjustable Range:
0.40 ± .06"w.c. to 12.0"w.c.
Maximum Pressure:
0.5 psi (0.03 bar)
Operating Temperature Range:
-40 to 180F (-40 to 82C)
Electrical Rating:
0.5 VA @ 24 V AC, 50/60 Hz.
Contacts:
DPDT, 2 form-C
rated 8 amps @ 250 V AC.
Electrical Connections:
Screw terminals.
Sample Line Connections:
Ferrule and nut compression type
connectors will accept .25" OD rigid
tubing.
Shipping Weight: 1.2 lbs.
Agency Approvals: pending
ELECTRICAL CONNECTIONS
(SEE FIGURE 3)
Before pressure is applied to the diaphragm,
the snap switch contacts will be in the nor-
mally closed (NC) position. As differential
pressure rises above the eld adjustable set
point, the snap switch opens, de-energizing
the coil on the slave relay, which activates
the DPDT contacts. An LED indicates that
the snap switch exceeds differential set
point. It remains lit until the manual reset
push button is depressed.
FIELD ADJUSTMENT
The AFS-460–137 Manual Reset Air Switch
has an adjustment range of 0.40 to 12.0"
w.c., ±.06" w.c. To adjust the set point:
Turn the adjusting screw counterclockwise
until motion has stopped. Next, turn the ad-
justing screw 4 complete turns in a clockwise
direction to engage the spring. From this
point, the next ten turns will be used for the
actual calibration. Each full turn represents
approximately 1.16" w.c.
Please note: To properly calibrate an Air
Switch, a digital manometer or other mea-
suring device should be used to conrm the
actual set point.
(Figure 3) Shown in "on shelf" condition:
no power and no differential pressure
applied.

Other UNICONTROL Electronic Switch manuals

UNICONTROL Electronic Cleveland Controls RSS-498-013 User manual

UNICONTROL Electronic

UNICONTROL Electronic Cleveland Controls RSS-498-013 User manual

UNICONTROL Electronic Cleveland Controls RSS-495-011 User manual

UNICONTROL Electronic

UNICONTROL Electronic Cleveland Controls RSS-495-011 User manual

UNICONTROL Electronic Cleveland Controls RSS-498-013 User manual

UNICONTROL Electronic

UNICONTROL Electronic Cleveland Controls RSS-498-013 User manual

Popular Switch manuals by other brands

Lantech IES-2008B-DNV user manual

Lantech

Lantech IES-2008B-DNV user manual

EchoLab MVS3 Operator's manual

EchoLab

EchoLab MVS3 Operator's manual

Sony MK7807V1 Guide book

Sony

Sony MK7807V1 Guide book

COS S10 user manual

COS

COS S10 user manual

Hubbell Circuit-Lock installation instructions

Hubbell

Hubbell Circuit-Lock installation instructions

Huawei Quidway S9300 Configuration guide

Huawei

Huawei Quidway S9300 Configuration guide

HP ProCurve 5300xl Specification sheet

HP

HP ProCurve 5300xl Specification sheet

Extron electronics System 5cr Plus Specifications

Extron electronics

Extron electronics System 5cr Plus Specifications

Tektronix WVR4000 Service manual

Tektronix

Tektronix WVR4000 Service manual

Power integrations LinkSwitch-4 LNK4*15D Series Application note

Power integrations

Power integrations LinkSwitch-4 LNK4*15D Series Application note

S&C CS-1A manual

S&C

S&C CS-1A manual

Equinox Systems ESP-2 MI installation guide

Equinox Systems

Equinox Systems ESP-2 MI installation guide

StarTech.com SV201 instruction manual

StarTech.com

StarTech.com SV201 instruction manual

Black Box LIE402A user manual

Black Box

Black Box LIE402A user manual

ELCART 42/12622-00 user manual

ELCART

ELCART 42/12622-00 user manual

United Electric Controls 117 Series Installation and maintenance instructions

United Electric Controls

United Electric Controls 117 Series Installation and maintenance instructions

StorageWorks DWZZH user guide

StorageWorks

StorageWorks DWZZH user guide

SWiiD SwiidInter Installation and user guide

SWiiD

SWiiD SwiidInter Installation and user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.