Model No. : UT-1405
CLEAN ROOM INDICATOR
(TEMP. & INDICATOR)ROOM PRESSURE PΔ
INSTRUCTION MANUAL
M
26.5
0.0

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
I
WARNING
Electrical Consideration / Precautions
The controller is considered “rack and panel mounted equipment” per EN 61010-1, Safety Requirements for
electrical equipment for Measurement, Control and Laboratory Use, Part 1: General Requirements. Conformity
with 2/23/EEC Low Voltage Directive, requires the user to provide adequate protection against a shock hazard.
The user shall install this controller in an enclosure that prevents OPERATOR access to the rear terminals.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN DEATH OR SERIOUS INJURY.
Shielded twisted pair cable is required for all Analog Input & Output, Process Variables,
RTD, Thermocouple, DC volts-mV, low level signal, mA, Alarm Outputs, and Computer
communication interface circuits.
CAUTION
FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY RESULT IN PRODUCT DAMAGE.
Power Supply / Wiring Requirements
Applying 240V AC to a controller rated for 12-24VDC will severely damage the controller
and is a fire and smoke hazard.
This controller is suitable for connection to 230 15% VAC, 50 Hz or 12 / 24 VDC, power mains.+
It is the user responsibility to provide the following
230 15% VAC - a switch, fuse (1/2A, 250V) or a circuit breaker.+
12 / 24 VDC – a switch, fuse (1A, 125A) or a circuit breaker.
The above items should be installed together with UT-1405 for the products electrical protection.
The switch, Fuse or circuit-breaker should be located close to the controller, within easy reach
operator. The switch or Circuit-breaker should be marked as the disconnecting device for the
controller. applying power to Multiple instruments, make sure that sufficient current is supplied,
Otherwise, the instruments may not start up normally due to the voltage drop caused by the in-
rush current.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS MAY RESULT IN PRODUCT DAMAGE.
Disposal action of Instruments follows as per country and regional law and rules & regulation also same in
international. Company might be follows as per rules.
DISPOSAL ACTION
PRE CAUTIONS, WARNING AND DISPOSAL ACTION
Line voltage Wiring

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
1
CONTENTS
2. NSTALLATIONI
2.1 MOUNTING
2.2 EXTERNAL DIMENSION
2.3 TECHNICAL SPECIFICATIONS
2.4 WIRING DIAGRAM
3. PROGRAMMING
3.1 OPERATION INTERFACE
3.2 MODE ACCESS FLOW CHART
4.1 CONFIGURATION MODE
4. OPERATIONAL MODES
4.2 SETUP MODE
4.3 CALIBRATION MODE
4.4 CHANGE PASSWORD MODE
4.5 ERROR MESSAGE.
5. COMMUNICATION [MODBUS RTU] PROTOCOL
5.1 INTRODUCTION
5.2 MODBUS CONFIGURATION BASIC SETTINGS
5.3 REGISTER ADDRESSES FOR MODBUS / RTU PROTOCOL
1. OVERVIEW
1.1 INTRODUCTION
2
2
2
2
2
3
5
6
6
7
8
8
10
11
12
12
13
13
13
13
14
5.4 MODBUS SYSTEM SCHEMATIC.
...................................................................................................
........... ..............................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...........................................................................................
.............................................................................
....................................................................
...................................................................................
...........................................................................
............................................................................................
.................................................................................
.....................................................................
......................................................................................
...............................................
.........................................................................................
.............................................
. ..................................
....... ..............................................................

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
2
1. Introduction1
Function
Mount Anywhere
Two different configuration levels provide easy access to parameters. A4 digit security code perverts una-
uthorized changes. Parameters can also be hidden to user to prevent improper configuration of the unit
The UT-1405 product group is Process control instruments that must be panel mounted. The wiring terminals
-must be provided. the UT-1405 is environmentally hardened and, if suitably handled, can be mounted virtua
-lly anywhere in plant or factory; in a panel or enclosure wall mounted or Flameproof enclosure or even on
the process machinery. it can withstand ambient temperature up to 50°C
Easy to Configure
1. OVERVIEW
2.1 Mounting 2.2 External Dimension
2. INSTALLATION
CAUTION
The product can be mounted on tilted or horizontal
panel using the mounting clamps supplied. Proper
space must be available at the back of the panel for
installation and maintenance activity.
Installation Mounting Precautions
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY
RESULT IN INSTRUMENT DAMAGE
All dimensions are in mm
The instrument accept inputs from standard T + RH sensor or internal sensor. The instrument
display the temperature ( C) in the range of 0 to 100 C and Humidity in the range of 0.0 to 100.0%
ºº
RH and press. diff. in 0 to 100 pascal on 3 digit segment Red LEDs with High and Low alarm LED
outputs and are set able using programming modes.
The UNITECH “CLEAN ROOM INDICATOR [T+DP] : UT-1405" is specially designed to display Temperature, Humidity a
Room Pressure Difference in one unit.
Model No. : UT-1405
Indicator Size : 145[H]X175[W]X25[D]
Mounting Box Size : 135[H]X162[W]X15[D]
Cutout Size : 135[H]X138[W]
DIMENSIONS :

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
3
Flame Proof
High scale / Low scale Full range as per input selection
Other
Mounting Bricks and modules wall flush panel mounting
MOC Full S S 316 plate and box , back side wall mounting M S covers.
Power Consumption 24 VDC @ 4 Watt Maximum
Input
Indication DP
Accuracy
DP
0.25 % on FS
2.5 % for 10 to 90 % RH rest of 3 %
3 Nos (Temp. + RH + DP)
Nos Of Input
Integral Or Remote (external)
Temperatures Input
DP Input
24V/5V DC @ 30mA max, Isolated from Input & Output
Transmitter Power Supply
Status indication LEDs for Relay status & Communication
Prog. parameters
Modbus RTU RS- 485/RS- 232 Communication
Baud rate, Parity, Node address, Stop bit
Protocols & method
Max. Connections
Communication Up to 128 Units
Programmable
Parameters
Setpoint / Hysteresis
Alarm Logic
Full range as per input selection
F.S. high & low alarm
Gas Group I IIA IIB as per IS 2148/1981
TECHNICAL SPECIFICATIONS
2.3 Technical Specifications
Integral Or Remote (external)
Range
Temperatures
Channel-1 : 3 digit Seven segments 0.56" RED display.
Humidity
Read/Write Read : Process Value, Decimal Point. Write : Hi Low set point.
Operating Ambient Temp. : 0~50˚C, Humidity : Below 90% Non condensing
Endose Certificate Enclosure is certifies by C.M.R.I. dhanbad
Display Glass Clear glass thognet type A as per is 2206
Degree Protection Ip65 as per IS 2147
Material Of Construction
Aluminium Alloy
Cable Entry 2 X 3/4 “ ET
DP
Display Resolution 0.1 for Temp. & Rh for DP mmWc : 0.1 / PA : 1 / Hpa : 0.01
Temperature
-10 to 10 mm / -25 to 25 mm / -100 to 100 mm / -200 to 200 mm ......
Humidity Channel-2 : 3 digit Seven segments 0.56" RED display.
Channel-3 : 3 digit Seven segments 0.56" RED display.
0 to 99.9% with decimal point.
0 to 60.0% with decimal point.
Humidity Input
Integral Or Remote (external)
Temperature
Humidity
1 % on FS in all unit
Response Time : 8 Sec.
Response Time : 4 Sec.
Response Time : 1 Sec.

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
4
2. Technical4 Features
FEATURES
FDA 21 CFR Part 11 - GAMP - 4 compatible
Microcontroller based indicator wit hinbuilt Temperature & DP measurement in single enclosure.
Incorporates highly stable built-in or DP sensor. (with different unit like mmWc / pa / kpa / mmhg).
3 digit, 0.56" bright LED display for displaying DP.
Process parameter HI and LOW LEDs. Status indicator for one channel.
User selectable set limits for process value violation.
Inbuilt buzzer to audible process value violation.
Password protection for calibration and programming mode.
Software based Calibration.
MODBUS RTU multi drop RS-485 serial communication for PLC, SCADA, etc.
Programmable device address, baud rate, (max no. of device is 1-256).
Remote programmable from master device.
User programmable offset correction.
*
*
*
*
*
*
*
*
*
*
*
*
*
Compact, All stainless steel of FLP enclosure with 35 mm depth for installation in prefab panels.
Brick and modular wall mounting and flush mounting.
*
*
*
*
FDA21 CFR part 11 compliance data logging software available.
Ex. Flameproof model available for Hazardous applications.

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
5
CAUTION
WIRING CONSIDERATION
Shielded twisted pair wire is used for all analog I/P, Process sensors RTD,
Thermo-couple, mV-mA DC, Volt DC, Linear input and Communication.
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
CAUTION
LINE VOLTAGE
This product is suitable for connection 110/230VAC, 50Hz or 12/24 VDC main power
supply. It is user responsibility to provide proper protection for the products electrical
protection .
when applying power to various instruments, make sure sufficient current is supplied.
otherwise the instruments may not start up due to the Voltage drop.
2.4 Wiring Diagram
AILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULTF
IN INSTRUMENT DAMAGE
Sensor 4 Wire Sensor with wire code:
POWER SUPPLY : 24VDC Supply Voltage.
2.4.1 Terminal Connection
YELLOW
SENSOR RS-485 24VDC
BLACK
GREEN
RED
COMM.+
COMM.-
VDC +
VDC -
YELLOW
SENSOR
BLACK
GREEN
RED
RS-485
COMM.+
COMM.-
24VDC
VDC +
VDC -
COMMUNICATION : RS-485 nterface TerminalI

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
6
3. PROGRAMMING
314
Low
High
115
Low
High
ºC
P
M
1
2
3
4
5
6
7
8
9
10
COM
FRONT VIEW
1. 7 segment Display 4 Digit 7 segment dedicated to display the present value. In Programing
mode it shows Parameter and its value.
2LOW. When LED is On It indicates the status of, Low Value.
6. Sensor
KEYS
6. MODE KEY MODE or Function key allows to access the programming group or
parameters. press this key to return to the normal view.
NORMAL VIEWS
7. ENTER KEY ENTER Key allows enter into the Parameter, moving from one parameter
to another or saving a new value of parameter or a status of parameter.
Press to change set point-2 in normal view.
8. UP KEY UP Key allows increasing the value of a digit selected or changing the
status of parameter in programming mode. Press to change set point-1 in
normal view
9. PASS KEY PASS Key allows pass the digit of a value from right to left of a selected
parameter in programming mode. In some Parameter it also change or
decrease the value.
3 HIGH. When LED is On It indicates the status of, High Value.
Internal T + RH Sensor (If Applicable)
4COM.When LED is It indicates the status ofBlink, Communication.
10 ACK. BUZZER. Acknowledgement of Buzzer ring at Low & High Values of C, %RH and P
Δº

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
7
3.2 Mode Access Flow Chart.
*
*
*
Default Password will be 0000
Protected Parameter Password will be 1111
NOTE :
These are the whole parameter list. Parameters
can be very as per Type Requirement by User.or
*To come out from Programming Mode to
Normal mode Press key in any step.
MODE
8888
Normal Mode [PV]
Mode Selection
Configuration Setup
Mode Mode
Change
Password Mode
Calibration
Mode
WARNING
INJURY
Programming parameter should be accessed only by Personnel who are
technically competent to do so. Local regulations regarding electrical &
safety must be observed.
FAILURE TO COMPLY WITH THESE INSTRUCTION COULD BE RESULT IN SERIOUS INJURY OR DEATH
Press key to enter into the
Programming mode from
Normal mode
pas
MOD
-
CH6
000
oLd
pas
---
PAS
new
-
no
FCt
SEt
MM
p-u
n1t
01
Add
nod
rAt
bud
05
rH
dmp
-
dmp
-
05
Prs
96
MOD
Con
F1G
000
Ent
pas
Lo
AL1
tMp
tmp
-
HI
AL2
Prs
HI
AL2
Lo
AL1
Prs
non
1tY
PAr
Password Protected
oFF
tm-
000
oFF
Pr-
000
-
MOD
set
000
Ent
pas
200
sp1
tmp
tmp
sp2
Prs
sp2
sp1
Prs
400
020
050
UP
-
-
Password Protected
1br
MOD
-
CAL
000
Ent
pas
---
Lo
Prs
prs
H1
---
Password Protected
Press key Press key Press key Press key
YES
RH-
ENB
MnF
Ct7
Ct1
MxF
445
518

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
8
‘Configuration Mode’ will shown by pressing key, will be display and then by pressing or keyMode
4.1 Configuration Mode
4. OPERATIONAL MODES
Range / Values
Parameter
CONFIGURATION MODE
Password for Config. Mode Parameters
Display
Scroll the digit by key, Increase by key.
Range : Values between to000 999
Default Input : Lo
Temperature Alarm-1 Type
To Activate Buzzer on this Value
Change the type Up by key, Down by key.
Values :
Default Value : 0000
Temperature Alarm-2 Type
To Activate Buzzer on this Value
Values :
Default Value : Hi
Pressure Diff. Alarm-1 Type
To Activate Buzzer on this Value
Unit :
Default Value :
Change the value by key, or by key.
Lo
Pressure Diff. Alarm-2 Type
To Activate Buzzer on this Value Values :
Default Value :
Change the value by key, or by key.
Hi
non
1tY
PAr
Lo
AL1
prs
HI
AL2
prs
01
Add
nod
rAt
bud
96
000
Ent
pas
Lo
AL1
tmp
-
HI
AL2
tmp
-
Baud Rate
Baud Rate for Communication
Change the value by key, or by key.
Parity
Parity for Communication
Change the value by key, or by key.
Node Address
Device Address for Communication
Values between:
Default Value :
99
to
00
Change the value by key, or by key.
0001
Change the type Up by key, Down by key.
: Baud Rate 4800
4800
: Baud Rate 9600
9600
: Baud Rate 19200
19.2k
Values :
Default Value : 9600
:EvenParity
EvEn
:OddParity
Odd
: None Parity
none
Values :
Default Value : none
: Active in Low
Lo
: Active in Very Low
vLo
: Active in Very High
vH1
: Active in High
H1
: Disabled
dsb
: Active in Low
Lo
: Active in Very Low
vLo
: Active in Very High
vH1
: Active in High
H1
: Disabled
dsb
: Active in Very Low
: Active in Low
Lo
vLo
: Active in Very High
vH1
: Active in High
H1
: Disabled
dsb
: Active in Low
Lo
: Active in Very Low
vLo
: Active in Very High
vH1
: Active in High
H1
: Disabled
dsb
Change value by key, or by key.
Pressure Damping
Note : Factory Set Value
Default Value : 05
05
PRS
dmp
-
Value :s between 00 to 10
Change value by key, or by key.
Temperature Gain
Note : Factory Set Value
Default Value : 03
03
TMP
Gen
-
Value :s between 00 to 10

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
9
Continue Configuration Mode
WARNING
PERSONAL INJURY :
Configuration should be performed only by personnel who are technically competent to do
so. Local Regulations regarding electrical & safety must be observed.
FAILURE TO COMPLY WITH THESE INSTRUCTIONS COULD RESULT IN DEATH OR SERIOUS INJURY.
Range / Values
Parameter
Display
Change value by key, or by key.
Pressure Offset Factory Set Value
Note : Factory Set Value
Default Value : 15
Change value by key, or by key.
Pressure Gain Factory Set Value
Note : Factory Set Value
Default Value : 08
Change value by key, or by key.
Factory Setting
Note : Factory Set Value
Default Value : No
Pressure difference unit selection
Default Value :
Unit in for pressure difference display value
Increase value by key, decrease by key.
15
Prs
Off
-
08
PRS
Gen
-
no
FCt
SEt
MM
p-u
n1t
mmw
pa
: mmWC
: Pascal
mmw
Value :s between 00 to 62
Value :s between 00 to 14

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
10
‘Setup Mode’ Mode will shown by pressing key, after Mode display.Conf
4.2 Setup Mode
Range / Values
Parameter
SETUP MODE
Password for Setup Mode Parameters
Display
Scroll the digit by key, Increase by key.
Range : Values between to0000 9999
Default Value : 0000
Temperature Alarm 1 Set Point
Set point for buzzer activation
Scroll the digit by key, Increase by key.
Range : Values between to00.0 .99 9
Default Value : 2.00
Scroll the digit by key, Increase by key.
Range : Values between to00.0 .99 9
Default Value : 40.0
Temperature Alarm 2 Set Point
Scroll the digit by key, Increase by key.
Range : Values between to00.0 .99 9
Pressure Diff Alarm 1 Set Point
Scroll the digit by key, Increase by key.
Range : Values between to00.0 .99 9
Default Value : 05.0
Pressure Diff Alarm 2 Set Point
(According to Decimal point)
(According to Decimal point)
(According to Decimal point)
(According to Decimal point)
Default Value : 445
Factory Set Value
Default Value : 02.0
400
sp2
tmp
-
020
sp1
prs
050
sp2
prs
oFF
Mnf
000
-
000
Ent
pas
200
sp1
tmp
-
Set point for buzzer activation
Set point for buzzer activation
Set point for buzzer activation
Default Value : 518
Factory Set Value
oFF
Mxf
000
000
pr-
off
-
Scroll the digit by key, Increase by key.
Range : Values between to00.0 .99 9
Default Value : 00 0.
Pressure Offset
Offset to pressure value (According to Decimal point)
Scroll the digit by key, Increase by key.
Range : Values between to00.0 00.0
Default Value : 00 0.
Temperature Offset
Offset to temperature value (According to Decimal point)
oFF
tMp
000

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
11
‘Calibration Mode’ Mode will shown by pressing key, after Mode display.Setp
4.3 Calibration Mode
Range / Values
Parameter
CALIBRATION MODE
Password for Calibration Mode Parameters
Display
Scroll the digit by key, Increase by key.
Range : Values between to000 999
Default Value : 0000
Pressure Low alibrationC
Calibration Zero
NOTE : AfterZeroCal.press keyfornextPara.
Apply Low signal [as per input] & press key.
Range :
Default Value : ----
According to Input Type
Pressure High Calibration
Calibration Span
NOTE : After Span Cal. press key for next para.
Apply High signal [as per input] & press key.
Note : After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Note : After Calibration random value
appeared in display, as per input.
Refer below Table for Cal. values range.
Range :
Default Value : ----
According to Input Type
Pressure Range
Change to Pressure Range
100
pr-
RNG
Range : Values between to00 0 99 9..
Default Value : 1.00
Scroll the digit by key, Increase by key.
000
Ent
pas
---
Lo
Prs
---
H1
prs

@
+91 7046223333 , 9427301436
www.utplindia.in
www
UT-1405
CLEAN ROOM INDICATOR [T+DP]
12
‘Change Password Mode’ Mode will shown by pressing key, after Mode display.CAL
Open the Input Connection
Sensor Break or Sensor disconnected.
Sign Description Solution
In case the following error messages appear in the display of controller,
please refer to the Error message table below, or call technical support.
OPN Check the Input sensor wiring
Replace the sensor.
Check the Input sensor wiring
Check the Input type.
Adjust the Range
Excess of PV over the Span value
Check the Input sensor wiring
Check the Input type.
Adjust the Range
Shortage of PV over the Low value
vnd
Ovr
All LED’s and
display not light
No power to the controller
Controller circuit failed
Check the power connection
Check the supply voltage.
4.4 Change Password Mode
4.5 Error Message.
Range / Values
Parameter
CPAS
0000
CHANGE PASSWORD MODE
Password for Change Password Mode.
Display
Scroll the digit by key, Increase by key.
Range : Values between to0000 9999
Default Value : 0000
opas
0000
OLD EXISTING PASSWORD
Old - Default or Existing Password
Scroll the digit by key, Increase by key.
Range : Values between to0000 9999
Default Value : 0000
npas
8888
NEW DESIRED PASSWORD
Set new Required Desired Password
Range : Values between to0000 9999
Default Value : As per new required.
(Any value) Scroll the digit by key, Increase by key.
CAUTION
PASSWORD PRECAUTIONS
FAILURE TO COMPLY WITH THESE INSTRUCTION MAY RESULT IN INSTRUMENT DAMAGE
*
*
After Changing old password, all parameter are locked. All Modes are not
accessible without new password.
Changed password should be remembered , it cannot be Reset at site.

5. COMMUNICATION [MODBUS RTU] PROTOCOL
5.1 Introduction
The unit can be connected in MODBUS/RTU communication data link protocol to messaging
structure, widely used to establish master - slave communications between devices. Each
device must have unique No. node address. Before starting any communication, choose a
baud rate compatible to the host device. A Modbus data sent from a master to slave tells the
selected slave what to do and what information to send back. The MODBUS/RTU protocol
works with RS232, RS485 and RS422 standards
5.2 MODBUS Configuration Basic settings
The Basic settings for RS-485 Modbus protocol are as follows :
Band rate
Start bit
Data bit
Stop bit
Parity
9600
1
8
1
none
5.3 Register addresses for MODBUS / RTU Protocol
The addressees for RS-485 Modbus protocol are as follows :
READ ONLY
SR. NO.
1
TEMP VALUE
PARAMETER ABSOLUTE ADDRESS ACCESS TYPE
40001
3
PRESSURE VALUE
40003
READ ONLY
2 40002
READ / WRITE
4
TEMPERATURE 1SET POINT-
40004
5 40005
6 40006
www.utplindia.in
@
www
+91 7046223333 , 9427301436
All content are subject to change without notice
due to continuous improvements.
Doc. Ref. 1410/R04/0819
UNITECH TECHNOCRATS PVT LTD
FACTORY:- 78/1/Z/3-Makarpura G I D C.. . .,
N/R Vadasar Bridge. /p-Gayatri empleOT
VADODARA - 390010 INDIA. Gujarat, 13
UT-1405
CLEAN ROOM INDICATOR [T+DP]
TEMPERATURE 2SET POINT-
READ / WRITE
READ / WRITE
7 40007
8
PRESSURE SET POINT-1
40008
READ / WRITE
9 40009
10 40010
TEMP. ALARM SE 1TPOINT-
READ / WRITE
PRESSURE SET POINT-2
TEMP. ALARM SE 1TPOINT-
PRESS. ALARM SE 1TPOINT-
PRESS. ALARM SE 1TPOINT-
READ / WRITE
READ / WRITE
READ / WRITE

5.4 MODBUS system schematic.
DATA+
The system schematic for RS-485 Modbus protocol are as follows :
DATA-
Ethernet
RS-232
or
RS-485
CONVERTER
D- D+
12
UT-1405 Device-1
D- D+
12
D- D+
12
D- D+
12
RS-485 BUS
ADD:1 ADD:2 ADD:3 ADD:N
RS-485 BUS
Upto 128
devices
UT-1405 Device-2 UT-1405 Device-3 UT-1405 Device-128
2 core 1 sq/mm shielded cable
www.utplindia.in
@
www
+91 7046223333 , 9427301436
All content are subject to change without notice
due to continuous improvements.
Doc. Ref. 1410/R04/0819
UNITECH TECHNOCRATS PVT LTD
FACTORY:- 78/1/Z/3-Makarpura G I D C.. . .,
N/R Vadasar Bridge. /p-Gayatri empleOT
VADODARA - 390010 INDIA. Gujarat, 14
UT-1405
CLEAN ROOM INDICATOR [T+DP]
COMPUTER- SCADA

Other manuals for UT-1405
2
Table of contents
Other Unitech Measuring Instrument manuals