© 2018 United Technologies Corporation 1 / 2 P/N 3102365-EN • REV 003 • ISS 14FEB18
SIGA-HFD Intelligent Fixed-
Temperature Heat Detector
Installation Sheet
Description
The Signature Series SIGA-HFD Intelligent Fixed-Temperature Heat
Detector that contains a fixed-temperature heat sensor to detect heat
from fire. The heat sensor monitors the temperature of the air in its
surroundings and the detector analyzes the data to determine whether
to initiate an alarm.
LED indicator. The LED indicator (see Figure 1) displays the following
states:
•Normal: Green LED indicator flashes, no action
•Alarm/active: Red LED indicator flashes, evacuate the area
Figure 1: SIGA-HFD features
(1) Self-locking tab
(2) LED indicator
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
WARNINGS
•This detector does not operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards
with the local fire protection specialist.
•This detector does not sense fires in areas where heat cannot
reach the detector. Heat from fires in walls, roofs, or on the
opposite side of closed doors may not reach the detector.
•This detector by itself does not provide smoke or fire protection.
Use this detector with ionization or photoelectric smoke detectors,
or both.
•This detector does not detect oxygen levels, smoke, toxic gases,
or flames. Use this device as part of a broad-based life safety
program, which includes a variety of information sources pertaining
to heat and smoke levels, extinguishment systems, visible and
audible devices, and other safety measures.
•Independent studies indicate that heat detectors should only be
used when property protection alone is involved. Never rely on
heat detectors as the sole means of fire protection.
Note
•To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to room
temperature before applying power.
•The dust cover (supplied) must remain on the detector during
installation and be removed prior to commissioning and service.
The dust cover is not a substitute for removing the detector during
new construction or heavy remodeling.
•In Canada, install according to CAN/ULC-S524 Standard for the
Installation of Fire Alarm Systems, CSA C22.1 Canadian Electrical
Code Part 1, and the local authority having jurisdiction.
To install the detector:
1. Install and wire the base, as described on the installation sheet
supplied with the base.
2. Remove the serial number label from the detector and attach it to
the project documentation.
3. Attach the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
Testing
Before testing, notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
Caution: Heat damage. Excessive heat may damage the detector
outer cover. Do not apply excessive heat when using a hair dryer.
When using a Testifire detector tester, you must install a SIGA2
Testifire Adapter Assembly.
Make sure the SIGA2 Testifire Adapter Assembly (model
SIGA2-TSTSPACER) is installed in the Testifire detector tester before
testing. Refer to the SIGA2-TSTSPACER Testifire Adapter Assembly
Installation Sheet (P/N 3101942-ML) for further details.
(1)
(2)
2 / 2 P/N 3102365-EN • REV 003 • ISS 14FEB18
To perform an initial installation test:
1. Visually inspect each detector and verify that it is installed in the
correct location. Make sure it is not adversely affected by factors
not apparent on the plans.
2. Remove the detector from its base and verify that the proper
detector address, trouble signals, and messages are reported.
3. If wired for Class A operation, verify that the detector continues to
operate first with SLC_IN disconnected, and then with SLC_OUT
disconnected. (Refer to the installation sheet for the base.)
4. Place a momentary ground fault on the SLC to verify operation of
ground fault detection circuitry.
5. Perform a function test, as described below.
To perform a function test:
1. If desired, use the fire alarm control panel to put the detector or
zone into a service group for testing. (Refer to the panel technical
reference manual for instructions.)
2. Activate the heat sensor using a hair dryer (maintaining a distance
of three inches) or using a Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance in accordance with the
requirements of the authority having jurisdiction. Refer to
CAN/ULC-S536 Standard for the Inspection and Testing of Fire Alarm
Systems and NFPA 72 National Fire Alarm and Signaling Code.
Refer to application bulletin P/N 3102403-EN for additional information
and cleaning instructions.
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Maximum spacing [1]
50 ft. (15.2 m) centers
Compatible bases
Standard
Relay
Isolator
Audible
SIGA-SB, SIGA-SB4
SIGA-RB, SIGA-RB4
SIGA-IB, SIGA-IB4
SIGA-AB4, SIGA-AB4G
SIGA-AB4GT, SIGA-AB4G-LF
Compatible detector testers [2]
Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
[1] When replacing SIGA-HRS and SIGA-HFS detectors with the
SIGA-HFD, ensure that the spacing is 50 ft. (15.2 m) or less.
[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory information
North American
standards
CAN/ULC-S530-M91, UL 521
UL and ULC fixed-
temp alarm rating
135°F (57.2°C)
Actual alarm point
129 to 141°F (53.9 to 60.6°C)
Response time
index
Quick(evaluated by FM Approvals)
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.edwardsfiresafety.com

Other United Technologies Smoke Alarm manuals

United Technologies DET-TRONICS SmokeWatch U5015 User manual

United Technologies

United Technologies DET-TRONICS SmokeWatch U5015 User manual

United Technologies Kidde P4010ACSCO-WCA User manual

United Technologies

United Technologies Kidde P4010ACSCO-WCA User manual

Popular Smoke Alarm manuals by other brands

Ei Electronics Ei405TY RF Optical Technical specifications

Ei Electronics

Ei Electronics Ei405TY RF Optical Technical specifications

System Sensor Innovair DH100ACDCLWP Installation and maintenance instructions

System Sensor

System Sensor Innovair DH100ACDCLWP Installation and maintenance instructions

System Sensor 22051EI Installation and Maintenance

System Sensor

System Sensor 22051EI Installation and Maintenance

Ei Electronics Ei 176 Optical Technical specifications

Ei Electronics

Ei Electronics Ei 176 Optical Technical specifications

ELRO CBFS58R instruction manual

ELRO

ELRO CBFS58R instruction manual

Kidde KN-COSM-IBCA user guide

Kidde

Kidde KN-COSM-IBCA user guide

Notifier 851 Series manual

Notifier

Notifier 851 Series manual

XINDAO HS-103 Instruction

XINDAO

XINDAO HS-103 Instruction

UTC Fire and Security Kidde 900-0257 user guide

UTC Fire and Security

UTC Fire and Security Kidde 900-0257 user guide

Firex ADC owner's manual

Firex

Firex ADC owner's manual

Nittan EVCA-P instruction manual

Nittan

Nittan EVCA-P instruction manual

Ei Electronics EI 103C Instruction leaflet

Ei Electronics

Ei Electronics EI 103C Instruction leaflet

Kidde TRUSENSE SMOKE 2050-DS10 user guide

Kidde

Kidde TRUSENSE SMOKE 2050-DS10 user guide

Quell Q1400 user guide

Quell

Quell Q1400 user guide

Honeywell 5193SD Installation and maintenance instructions

Honeywell

Honeywell 5193SD Installation and maintenance instructions

Ei Electronics Ei 105R Optical product manual

Ei Electronics

Ei Electronics Ei 105R Optical product manual

Synova SynoDEC 300 OP320C Installation

Synova

Synova SynoDEC 300 OP320C Installation

Kidde PI9000 UK user guide

Kidde

Kidde PI9000 UK user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.