manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Unitronics
  6. •
  7. I/O System
  8. •
  9. Unitronics Uni-I/O UIA-0800NH User manual

Unitronics Uni-I/O UIA-0800NH User manual

Unitronics
1
Uni-I/O™ Modules
User Guide
UIA-0800NH
Uni-I/O™is a family of Input/Output modules that are compatible with the UniStream® control
platform.
This guide provides basic installation information for the UIA-0800NH module.
Technical specifications may be downloaded from the Unitronics website.
The UniStream® platform comprises
CPU controllers, HMI panels, and local
I/O modules
that snap together to form an
all-in-one Programmable Logic
Controller (PLC).
Install Uni-I/O™modules:
▪Onto the back of any UniStream®
HMI Panel comprising a CPU-for-
Panel.
▪Onto a DIN-rail, using a
Local Expansion Kit.
The maximum number of Uni-I/O™modules that can be connected to a single CPU controller is limited.
For details, please refer to the specification sheets of the UniStream® CPU or any of the relevant Local
Expansion Kits.
Before You Begin
Before installing the device, the installer must:
▪Read and understand this document.
▪Verify the Kit Contents.
Installation option requirements
If you are installing a Uni-I/O™module onto:
▪A UniStream® HMI Panel; the Panel must comprise a CPU-for-Panel, installed according to the CPU-for-
Panel installation guide.
▪A DIN-rail; you must use a Local Expansion Kit, available by separate order, to integrate the Uni-
I/O™modules on the DIN-rail into a UniStream® control system.
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Caution
Use caution.
▪All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
▪Please dispose of this product according to local and national standards and regulations.
▪This product should be installed only by qualified personnel.
▪Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
▪Do not attempt to use this device with parameters that exceed permissible levels.
▪Do not connect/disconnect the device when power is on.
Environmental Considerations
UniStream™
Unitronics
2
▪Ventilation: 10mm (0.4”) of space is required between the device top/bottom edges and the
enclosure’s walls.
▪Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture
or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the
standards and limitations given in the product’s technical specification sheet.
▪Do not place in water or let water leak onto the unit.
▪Do not allow debris to fall inside the unit during installation.
▪Install at maximum distance from high-voltage cables and power equipment.
Kit Contents
▪1 UIA-0800NH module
▪4 I/O terminal blocks (2 black and 2 gray)
UIA-0800NH Diagram
1
DIN-rail clips
Provide physical support for CPU and modules. There are two clips: one
at the top (shown), one at the bottom (not shown).
2
Inputs 0-1
Input connection points
3
Inputs 2-3
4
I/O Bus - Left
Left-side Connector
5
Bus Connector Lock
Slide the Bus Connector Lock to the left, to electrically connect the Uni-
I/O™module to the CPU or adjacent module.
6
I/O Bus - Right
Right-Side Connector, shipped covered. Leave covered when not in use.
Bus Connector
Cover
7
Inputs 6-7
Input connection points
8
Inputs 4-5
9
Input LEDs (4-7)
Red LEDs
10
Input LEDs (0-3)
Red LEDs
11
Status LED
Tricolor LED, Green/Red/Orange
NOTE
▪Refer to the module's specification sheet for LED indications.
12
Module door
Shipped covered with protective tape to prevent the door from being
scratched. Remove tape during installation.
13
Screw holes
Enable panel-mounting; hole diameter: 4mm (0.15”).
UG_UIA-0800NH
User Guide
Unitronics
3
About the I/O Bus Connectors
The I/O Bus connectors provide the physical and electrical connection points between modules. The
connector is shipped covered by a protective cover, protecting the connector from debris, damage, and
ESD.
The I/O Bus - Left (#4 in diagram) can be connected to either a CPU-for-Panel, a
Uni-COM™module, to another Uni-I/O™module or to the End Unit of a Local Expansion Kit.
The I/O Bus - Right (#6 in diagram) can be connected to another I/O module, or to the Base Unit of
the Local Expansion Kit.
Caution
▪If the I/O module is located last in the configuration, and nothing is to be connected to it, do
not remove its Bus Connector Cover.
Installation
▪Turn off system power before connecting or disconnecting any modules or devices.
▪Use proper precautions to prevent Electro-Static Discharge (ESD).
Installing a Uni-I/O™Module onto a UniStream® HMI Panel
NOTE
The DIN-rail type structure on the back of the panel provides the physical support for the Uni-
I/O™module.
1. Check the unit to which you will connect the Uni-I/O™module to verify that its Bus Connector is not
covered.
If the Uni-I/O™module is to be the last one in the configuration, do not remove the cover of its I/O
Bus Connector - Right.
2. Open the door of the Uni-I/O™module and
hold it as shown in the accompanying
figure.
3. Use the upper and lower guide-tunnels
(tongue & groove) to slide the Uni-I/O™
module into place.
4. Verify that the DIN-rail clips located at the
top and bottom of the Uni-I/O™module
have snapped onto the DIN-rail.
5. Slide the Bus Connector Lock all the way to the left as
shown in the accompanying figure.
6. If there is already a module located to its right,
complete the connection by sliding the Bus Connector
lock of the adjacent unit to the left.
7. If the module is the last in the configuration, leave the
I/O bus connector covered.
Removing a Module
8. Turn off the system power.
9. Disconnect the I/O terminals (#2,3,7,8 in the diagram).
10. Disconnect the Uni-I/O™module from the adjacent units: slide its Bus Connector Lock to the
right. If there is a unit located on its right, slide the lock of this module to the right as well.
11. On the Uni-I/O™module, pull the top DIN-rail clip up and the bottom clip down.
12. Open the door of the Uni-I/O™and hold it with two fingers as shown in the figure on page 3;
then pull it carefully from its place.
UniStream™
Unitronics
4
Installing Uni-I/O™modules onto a DIN-rail
To mount modules onto a DIN-rail, follow steps 1-7 in Installing a Uni-I/O™Module onto a UniStream®
HMI Panel on page 3.
In order to connect the modules to a UniStream® controller, you must use a Local Expansion Kit.
These kits are available with and without power supplies, and with cables of varying lengths. For complete
information, please refer to the installation guide of the relevant Local Expansion Kit.
Numbering Modules
You can number modules for reference purposes. A set of 20 stickers is provided with every CPU-for-
Panel; use these stickers to number the modules.
▪The set contains numbered and blank stickers as shown
in the figure to the left.
▪Place them on the modules as shown in the figure to the
right.
UG_UIA-0800NH
User Guide
Unitronics
5
UL Compliance
The following section is relevant to Unitronics’ products that are listed with the UL.
The following models: UIA-0006, UIA-0800N, UID-0808R, UID-W1616R,UIS-WCB1 are UL listed for
Hazardous Locations.
The following models: UIA-0006, UIA-0402N,UIA-0402NL, UIA-0800N, UID-0016R, UID-0016RL,
UID-0016T, UID-0808R, UID-0808RL, UID-0808T, UID-0808THS, UID-0808THSL, UID-0808TL, UID-1600,
UID-1600L, UID-W1616R, UID-W1616T, UIS-04PTKN, UIS-04PTN, UIS-08TC, UIS-WCB1, UIS-WCB2
are UL listed for Ordinary Location.
UL Ratings, Programmable Controllers for Use in Hazardous Locations,
Class I, Division 2, Groups A, B, C and D
These Release Notes relate to all Unitronics products that bear the UL symbols used to mark products that
have been approved for use in hazardous locations, Class I, Division 2, Groups A, B, C and D.
Caution
▪This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, or Non-
hazardous locations only.
▪Input and output wiring must be in accordance with Class I, Division 2 wiring methods and in
accordance with the authority having jurisdiction.
▪WARNING—Explosion Hazard—substitution of components may impair suitability for Class I,
Division 2.
▪WARNING –EXPLOSION HAZARD –Do not connect or disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
▪WARNING –Exposure to some chemicals may degrade the sealing properties of material used
in Relays.
▪This equipment must be installed using wiring methods as required for Class I, Division 2 as
per the NEC and/or CEC.
Certification UL des automates programmables, pour une utilisation en environnement à
risques, Class I, Division 2, Groups A, B, C et D.
Cette note fait référence à tous les produits Unitronics portant le symbole UL - produits qui ont été certifiés
pour une utilisation dans des endroits dangereux, Classe I, Division 2, Groupes A, B, C et D.
Attention
▪Cet équipement est adapté pour une utilisation en Classe I, Division 2, Groupes A, B, C et
D, ou dans Non-dangereux endroits seulement.
▪Le câblage des entrées/sorties doit être en accord avec les méthodes
de câblage selon la Classe I, Division 2 et en accord avec l’autorité compétente.
▪AVERTISSEMENT: Risque d’Explosion – Le remplacement de certains composants rend
caduque la certification du produit selon la Classe I, Division 2.
▪AVERTISSEMENT - DANGER D'EXPLOSION - Ne connecter pas ou ne débranche pas
l'équipement sans avoir préalablement coupé l'alimentation électrique ou la zone est
reconnue pour être non dangereuse.
▪AVERTISSEMENT - L'exposition à certains produits chimiques peut dégrader les propriétés
des matériaux utilisés pour l'étanchéité dans les relais.
▪Cet équipement doit être installé utilisant des méthodes de câblage suivant la norme Class
I, Division 2 NEC et /ou CEC.
UniStream™
Unitronics
6
Wiring
▪This equipment is designed to operate only at SELV/PELV/Class 2/Limited Power environments.
▪All power supplies in the system must include double insulation. Power supply outputs must be
rated as SELV/PELV/Class 2/Limited Power.
▪Do not connect either the ‘Neutral’ or ‘Line’ signal of the 110/220VAC to device’s 0V point.
▪Do not touch live wires.
▪All wiring activities should be performed while power is OFF.
▪Unused points should not be connected (unless otherwise specified). Ignoring this directive may
damage the device.
▪Double-check all wiring before turning on the power supply.
Caution
▪To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm).
▪Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to
break.
▪Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring; use 26-12 AWG wire (0.13 mm2–3.31 mm2).
1. Strip the wire to a length of 7±0.5mm (0.250–0.300 inches).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
UIA-0800NH Connection Points
All wiring diagrams and instructions in this document
refer to the UIA-0800NH connection points.
These points are arranged in four groups of 7 points as
shown in the figure to the right.
Two top groups
Input connection points (0,1,2,3)
Two bottom groups
Input connection points (4,5,6,7)
Wiring Guidelines
In order to ensure that the device will operate properly and to avoid electromagnetic interference:
▪Use a metal cabinet. Make sure the cabinet and its doors are properly earthed.
▪Use wires that are properly sized for the load.
▪Use shielded twisted pair cables for wiring Analog I/O signals;
do not use the cable shield as a signal common (CM) / return path.
▪Route each I/O signal with its own dedicated common wire. Connect common wires at their
respective common (CM) points at the I/O module.
Individually connect each 0V point and each common (CM) point in the system to the power supply 0V
terminal, unless otherwise specified.
▪Individually connect each functional ground point ( ) to the earth of the system (preferably to the
metal cabinet chassis).
Use the shortest and thickest wires possible: less than 1m (3.3’) in length, minimum thickness 14 AWG
(2 mm2).
▪Connect the power supply 0V to the earth of the system.
▪Earthing the cables' shield:
UG_UIA-0800NH
User Guide
Unitronics
7
➢Connect the cable shield to the earth of the system - preferably to the metal cabinet chassis. Note
that the shield must be connected only at one end of the cable; typically, earthing the shield at the
UIA-0800NH end performs better.
➢Keep shield connections as short as possible.
➢Ensure shield continuity when extending shielded cables.
NOTE
For detailed information, refer to the document System Wiring Guidelines, located in the
Technical Library in the Unitronics’ website.
Wiring the Analog Inputs
NOT
E
▪The inputs are not isolated.
▪Each input has its own common point (CM0 for I0, etc.).
2-wire
3-wire
4-wire
UniStream™
Unitronics
8
UniStream® Uni-I/O™ Module
Technical Specifications
UIA-0800NH
This guide provides specifications for Unitronics’ Uni-I/O™module UIA-0800NH. This module comprises:
•8 analog inputs, 12 bit, supports HART protocol
Uni-I/O modules are compatible with UniStream family of Programmable Logic Controllers. They may
be either snapped onto the back of a UniStream HMI Panel next to a CPU-for-Panel to create an all-
in-one HMI + PLC controller, or installed on a standard DIN Rail using a Local Expansion Adapter.
Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com
Analog Inputs
Number of inputs
8
Input range (1) (2)
Input
Type
Nominal
Values
Over-range
Values
Overflow Values
0 ÷ 20mA
0 ≤ in ≤
20mA
20 < in ≤
20.3mA
in > 20.3mA
Absolute maximum
rating
±30mA (Current)
Isolation
None
Conversion method
Successive approximation
Resolution
12 bits
Accuracy
(25°C / -20°C to
55°C)
±0.5% / ±0.7% of full scale (Current)
Input impedence
251Ω (Current)
Noise rejection
10Hz, 50Hz, 60Hz, 200Hz
Step response (3)
(0 to 100% of final
value)
Smoothing
Noise Rejection Frequency
200Hz
60Hz
50Hz
10Hz
None
48ms
67ms
70ms
150ms
Weak
63ms
117ms
130ms
450ms
Medium
83ms
184ms
210ms
850ms
Strong
123ms
317ms
370ms
1650ms
Update time (3)
Noise Rejection Frequency
Update Time
200Hz
2.5ms
60Hz
8.33ms
50Hz
10ms
10Hz
50ms
Operational signal
range (signal +
common mode)
Current mode –x: -1V ÷ 5.4V ; CMx: -1V ÷ 0.4V
( x=0,1,2 or 3 )
Common mode
rejection
30dB @ 10Hz, 50Hz, 60Hz or 200Hz noise rejection mode
Normal mode
rejection
60dB @ 10Hz, 50Hz or 60Hz noise rejection mode
45dB @ 200Hz noise rejection mode
Cable
Shielded twisted pair
UG_UIA-0800NH
User Guide
Unitronics
9
Diagnostics (4)
Analog input overflow
IO/COM Bus
Bus current
consumption
85mA maximum
LED Indications
Input LEDs
Red
On: Input value is in Overflow
Status LED
A triple color LED. Indications are as follows:
Color
LED State
Status
Green
On
Operating normally
Slow blink
Boot
Rapid blink
OS initialization
Green/Red
Slow blink
Configuration mismatch
Red
On
Supply voltage is low or missing
Slow blink
No IO exchange
Rapid blink
Communication error
Orange
Rapid Blink
OS Upgrade
Environmental
Protection
IP20, NEMA1
Operating
temperature
-20°C to 55°C (-4°F to 131°F)
Storage temperature
-30°C to 70°C (-22°F to 158°F)
Relative Humidity
(RH)
5% to 95% (non-condensing)
Operating altitude
2,000 m (6,562 ft)
Shock
IEC 60068-2-27, 15G, 11ms duration
Vibration
IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude, 8.4Hz to 150Hz,
1G acceleration
UniStream™
Unitronics
10
Dimensions
Weight
0.13 Kg (0.286 lb)
Size
Refer to the images below
Top View
Side View
Front View
UG_UIA-0800NH
User Guide
Unitronics
11
Notes:
1. The 4-20mA input option is implemented using 0-20mA input range.
2. The UIA-0800NH measures values that are up to 1.5% higher than the nominal input range (i.e.
Input Over-range). Note that when the input overflow occurs, it is indicated in the corresponding
system tag while the input value is registered as the maximum permissible value. The Over-range
values can reach up to 20.3mA, and any input current higher than that will still register as 20.3mA
while the Overflow system tag is turned on.
3. Step response and update time are independent of the number of channels that are used.
4. See LED Indications Table above for description of the relevant indications. Note that the
diagnostics results are also indicated in the system tags and can be observed through the
UniApps™or the online state of the UniLogic™.
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its
sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either
permanently or temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied
warranties of merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the
information presented in this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind,
or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G)
Ltd. or other third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
UG_UIA-0800NH.pdf 09/22

Other manuals for Uni-I/O UIA-0800NH

1

Other Unitronics I/O System manuals

Unitronics V200-18-E4XB User manual

Unitronics

Unitronics V200-18-E4XB User manual

Unitronics Uni-I/O UIS-08TC User manual

Unitronics

Unitronics Uni-I/O UIS-08TC User manual

Unitronics Uni-I/O UIA-0006 User manual

Unitronics

Unitronics Uni-I/O UIA-0006 User manual

Unitronics IO-DI16 User manual

Unitronics

Unitronics IO-DI16 User manual

Unitronics UG-ULK-EIP-4AP6 User manual

Unitronics

Unitronics UG-ULK-EIP-4AP6 User manual

Unitronics V200-18-E2B User manual

Unitronics

Unitronics V200-18-E2B User manual

Unitronics V200-18-E46B User manual

Unitronics

Unitronics V200-18-E46B User manual

Unitronics UG-ULK-1616P2-M2P6 User manual

Unitronics

Unitronics UG-ULK-1616P2-M2P6 User manual

Unitronics Vision V350-35-TR34 User manual

Unitronics

Unitronics Vision V350-35-TR34 User manual

Unitronics IO-DI8-RO8-L User manual

Unitronics

Unitronics IO-DI8-RO8-L User manual

Unitronics Vision OPLC V350-35-B1 User manual

Unitronics

Unitronics Vision OPLC V350-35-B1 User manual

Unitronics V200-18-E62B User manual

Unitronics

Unitronics V200-18-E62B User manual

Unitronics EX-D16A3-TO16 User manual

Unitronics

Unitronics EX-D16A3-TO16 User manual

Unitronics UG-ULK-EIP-4A4BP6 User manual

Unitronics

Unitronics UG-ULK-EIP-4A4BP6 User manual

Unitronics V200-18-E4B User manual

Unitronics

Unitronics V200-18-E4B User manual

Unitronics IO-DI8-TO8 User manual

Unitronics

Unitronics IO-DI8-TO8 User manual

Unitronics Uni-I/O UIS-04PTN User manual

Unitronics

Unitronics Uni-I/O UIS-04PTN User manual

Unitronics EX90-DI8-RO8 User manual

Unitronics

Unitronics EX90-DI8-RO8 User manual

Unitronics V200-18-E5B User manual

Unitronics

Unitronics V200-18-E5B User manual

Unitronics UID-W1616R User manual

Unitronics

Unitronics UID-W1616R User manual

Unitronics IO-RO16 User manual

Unitronics

Unitronics IO-RO16 User manual

Unitronics Uni-I/O UIA-0006 User manual

Unitronics

Unitronics Uni-I/O UIA-0006 User manual

Unitronics V200-18-E3XBW User manual

Unitronics

Unitronics V200-18-E3XBW User manual

Unitronics IO-ATC8 User manual

Unitronics

Unitronics IO-ATC8 User manual

Popular I/O System manuals by other brands

WAGO 750-585 manual

WAGO

WAGO 750-585 manual

Siemens Simatic ET200pro manual

Siemens

Siemens Simatic ET200pro manual

SBC PCD2 Series manual

SBC

SBC PCD2 Series manual

TAC Xenta 400 Series manual

TAC

TAC Xenta 400 Series manual

Pilz PSS u2 ES 8DOD 0.5A operating manual

Pilz

Pilz PSS u2 ES 8DOD 0.5A operating manual

Jung KNX 2214REGA-01 operating instructions

Jung

Jung KNX 2214REGA-01 operating instructions

National Instruments R Series Getting started guide

National Instruments

National Instruments R Series Getting started guide

M-system R7L-EA16 instruction manual

M-system

M-system R7L-EA16 instruction manual

Tews Technologies TPCE636 user manual

Tews Technologies

Tews Technologies TPCE636 user manual

National Instruments NI USB-9219 user guide

National Instruments

National Instruments NI USB-9219 user guide

Siemens SIMATIC ET 200eco manual

Siemens

Siemens SIMATIC ET 200eco manual

ICP DAS USA M-7000 series quick start guide

ICP DAS USA

ICP DAS USA M-7000 series quick start guide

National Instruments FIELDPOINT FP-DO-403 operating instructions

National Instruments

National Instruments FIELDPOINT FP-DO-403 operating instructions

Bosch Rexroth IndraControl S20 manual

Bosch

Bosch Rexroth IndraControl S20 manual

Siemens Simatic 6DL2804-0 Series installation manual

Siemens

Siemens Simatic 6DL2804-0 Series installation manual

National Instruments NI-9477 Getting started guide

National Instruments

National Instruments NI-9477 Getting started guide

Casio I/O-PB-12 Service manual

Casio

Casio I/O-PB-12 Service manual

Honeywell T2 quick start guide

Honeywell

Honeywell T2 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.