  9. Unitronics EX-D16A3-TO16 User manual

Unitronics EX-D16A3-TO16 User manual

Unitronics
1
EX-D16A3-TO16
XL I/O Expansion Module (Built-in Adapter)
Installation Guide
The Unitronics®EX-D16A3-TO16 is an XL I/O expansion module for use in conjunction with specific Unitronics controllers.
XL modules comprise enhanced I/O configurations and detachable I/Oconnectors. In addition, this module comprises a built-
in adapter for communicating with the PLC and providing power to the other expansion modules in the system.
This module provides:
16 digital inputs, including 1 HSC
3 analog inputs
16 transistor outputs,including 1 HSO
For additional information and technical specifications,visit the Technical Libraryat 0Hwww.unitronicsplc.com
Component Identification
8
7
4
6
3
5
2
1
1
Power supplyconnector
2
Status indicators
3
Output connectors
4
Output power supplyconnection points
5
PLC expansion port (for communication with the PLC)
6
Input/output status indicators
7
Module-to-module connector port
8
Input connectors
Failure to complywith appropriate safetyguidelines can
cause severe personal injuryor damage to property.
Onlyqualified personnel should service and operate this
device.
When power is turned on, do not connect or disconnect
the device to avoid damaging the system.
Mounting the Module
Connecting Modules
To mount the module on a 35mm DIN-rail, snap it squarely
onto the DIN-rail, as shown below.
To connect a module to the adapter or expansion
module:
1.Push the module-to-module connector (1) into the port
(2) located on the right side of the module or adapter.
2.Push the protective cap (3) into the connector port of
the last module.The cap is supplied with the adapter.
1
23
65mm (2.56")
135mm(5.31")
80mm (3.15")
154mm(6.06")
60mm
(2.36")
4.0mm(0.16")
Unitronics
EX-D16A3-TO16
2
Install the module in an upright position.
To ensure good ventilation, leave at least 50mm between the
device and all other objects above or below it.
Install at a maximum distance from high-voltage cables and
power equipment.
Connecting the Module to the PLC
Use the communication cable to connect the module’s PLC expansion port to the PLC.
Take care to connect the correct cable. The connectors of this cable are housed in yellow insulation. Note that one end is
marked To PLC and the other To Adapter; insert accordingly.
The module is supplied with a 1-meter cable, part number EXL-CAB100. Other cable lengths are also available.
Use onlyan original Unitronics cable and do not make anychanges to it.
PLC Controller
Earth
Ground
I/O
Expansion
Port To PLC
EXL –CAB100
TO PLC EXL–CAB100
TO
ADAPTER
To Adapter
Wiring Considerations
Use crimp terminals for wiring and use 26-12 AWG wire
(0.13mm2–3.31mm2).
Strip the wire to a length of 7±0.5mm (0.250–0.300”).
Do not route input cables together with output cables
through the same multi-core cable or wire.
Use wire that is correctlysized for the load. Allow for
voltage drop and noise interference with extended input
lines.
Note:Connect the adapter 0Vand the I/O0Vto the same
line
Install an external circuit breaker. Guard against
short-circuiting in external wiring.
Do not connect unused pins. Ignoring this directive
maydamage the device.
To avoid damaging wires,do not exceed a maximum
torque of 0.5 Nm (5 kgf·cm).
Do not use tin, solder, or anysubstance on stripped
wire that might cause the wire strand to break.
Daisy Chaining
To facilitate wiring,you can wire the following pins in series (daisychain). Use both pins provided for this purpose.
Input connector pin: n/p. Output connector pins: +V, 0V. Power connector pins: +V, 0V.
Ensure that the total current drain on anysingle line does not exceed 10A. If a specific pin requires more than 10A,connect it
with a separate wire. The following diagram demonstrates the wiring options:
+V
0V
+V
0V
+V +V 0V 0V +V +V 0V 0V +V +V 0V 0V
Individual ConnectionDaisy-chained Connection
Wiring the Power Supply
Always connect the functional earth pin to the earth ground. Use a dedicated wire for this purpose; it must not exceed 1
meter.
Anon-isolated power supplycan be used provided that the 0Vsignal is connected to the earth ground.
Do not connect the neutral or line signal of the 110/220VAC to the device’s 0V pin.
In the event of voltage fluctuations or non-conformityto voltage power supplyspecifications,connect the device to a
regulated power supply.
0V
+V
Circuit
Protection
Device
Unitronics
EX-D16A3-TO16
3
Wiring Inputs
The following diagram shows the input connectors with pin numbers and corresponding input numbers
14131211109
8
765
4
3
2
1n/p RG
n/p3938373635343332 RG
15 16 17 18 19 20 21 22 23 24 25 26 27 28
AI1 AI0AI2
46454443424140 47
Wiring Digital Inputs
Inputs maybe wired as either pnp (positive logic) or npn (negative logic).
Input 36 can function as a high-speed counter, frequency measurer, or general purpose digital input (set in software).
Input 37 can function either as a counter reset inputor general purpose digital input(set in software).
For correct operation of the digital inputs, connect the n/p pin according to the following figures.
For information on connecting RG pins, refer to Connecting RG Pins.
pnp (positive logic) inputs 32-39
pnp (positive logic) inputs 40-47
14131211109
8
765
4
3
2
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
0V
+V
RG
*‡
*HSC Input ‡Counter Reset
n/p
RG
I32
I33
I34
I35
I36
I37
I38
I39
14131211109
8
765
4
3
2
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
0V
+V
RG
n/p
RG
*HSC Input ‡Counter Reset
I40
I41
I42
I43
I44
I45
I46
I47
npn (negative logic) inputs 32-39
npn (negative logic) inputs 40-47
14131211109
8
765
4
3
2
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
0V
+V
RG
n/p
RG
*HSC Input ‡Counter Reset
*‡
I32
I33
I34
I35
I36
I37
I38
I39
*HSC Input
14131211109
8
765
4
3
2
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
0V
+V
RG
n/p
RG
‡Counter Reset
I40
I41
I42
I43
I44
I45
I46
I47
Wiring Analog Inputs
The following diagram shows the 2-wire and 4-wire current connection.
Use shielded twisted pair cable.
Connect shields to the earth ground at the signal’s source.
14131211109
8
765
4
3
2
1
15 16 17 18 19 20 21 22 23 24 25 26 27 28
0V+V
Expansion
Adapter
+V
0V
Circuit Protection Device Power
Supply
+
-
RG
AI0
Power
-+
-
+
Power Supply
AI2
Unitronics
EX-D16A3-TO16
4
Wiring Outputs
The following diagram shows the output connectors with pin numbers and corresponding output numbers.
+V +V 0V 0V
14 13 12 11 10 9 8 7 6 5 4 3 2 1
28 27 26 25 24 23 22 21 20 19 18 17 16 15
32 33 34 35 36 37 38 39
40 41 42 43 44 45 46 47
npn pnp
32
Wiring the Output Power Supply
Anon-isolated power supplycan be used provided that the 0Vsignal is connected to the earth ground.
Do not connect the neutral or line signal of the 110/220VAC to the device’s 0V pin.
In the event of voltage fluctuations or non-conformityto voltage power supplyspecifications, connect the device to a
regulated power supply.
The adapter 0Vand the I/O0Vmustbe connect to the same line, Ignoring this maydamage the device.
Wiring Transistor Outputs
Output 32 can be wired either as pnp (source) or npn (sink). pnp and npn can be used simultaneously.
Output 32 can be used as a high speed output.
pnp (source) outputs 32-39
pnp (source) outputs 40-47
28 27 26 25 24 23 22 21 20 19 18 17 16 15
0V
+V
Output Power Supply
14 13 12 11 10 9 8 7 6 5 4 3 2 1
O32
O33
O34
O35
O36
O37
O38
O39
Circuit
Protection
Device Load
+V
0V
28 27 26 25 24 23 22 21 20 19 18 17 16 15
0V
+V
Output Power Supply
14 13 12 11 10 9 8 7 6 5 4 3 2 1
O40
O41
O42
O43
O44
O45
O46
O47
Circuit
Protection
Device Load
+V
0V
npn (sink) output
28 27 26 25 24 23 22 21 20 19 18 17 16 15
14 13 12 11 10 98 7 6 5 4 3 2 1
0V
+V
Output Power Supply
Circuit
Protection
Device
O0
Circuit Protection
Device
Load
0V
+V0
+V
0V
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all app licable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, de signs,
materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market. All information in this document is provided "as is" without warranty of any kind, either expressed
or implied, including but not limited to any implied warranties of merchantability, fitness for a particular purpose, or non -infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks p resented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other third parties and you are not per mitted to use them without the prior
written consent of Unitronics or such third party as may own them.
DOC04000-A211-16
Wiring the Power Supply
Connecting RGPins
For correct operation of digital and analog inputs and for EMI immunity, connect the RG pin of all the expansion modules
containing RG signals to the adapter module 0Vsignal.
The overall length of the wire connecting the RG pins to the adapter 0Vsignal must be less than 3 meters.
Connect the RG pins in series (daisychain). To facilitate this, use both the RG pins.
I/O Expansion Modules
0V
RG RG RG
0 1 5432 6
Expansion Module
(Built-in adapter)
7
RG

Other Unitronics I/O System manuals

Unitronics V200-18-E4B User manual

Unitronics

Unitronics V200-18-E4B User manual

Unitronics UG-ULK-EIP-4A4BP6 User manual

Unitronics

Unitronics UG-ULK-EIP-4A4BP6 User manual

Unitronics Vision V350-35-TR34 User manual

Unitronics

Unitronics Vision V350-35-TR34 User manual

Unitronics Uni-I/O UIA-0006 User manual

Unitronics

Unitronics Uni-I/O UIA-0006 User manual

Unitronics IO-ATC8 User manual

Unitronics

Unitronics IO-ATC8 User manual

Unitronics V200-18-E1B User manual

Unitronics

Unitronics V200-18-E1B User manual

Unitronics Uni-I/O UIS-04PTN User manual

Unitronics

Unitronics Uni-I/O UIS-04PTN User manual

Unitronics IO-DI8-TO8 User manual

Unitronics

Unitronics IO-DI8-TO8 User manual

Unitronics V200-18-E5B User manual

Unitronics

Unitronics V200-18-E5B User manual

Unitronics Uni-I/O UIA-0800NH User manual

Unitronics

Unitronics Uni-I/O UIA-0800NH User manual

Unitronics V200-18-E3XBW User manual

Unitronics

Unitronics V200-18-E3XBW User manual

Unitronics Vision OPLC V350-35-B1 User manual

Unitronics

Unitronics Vision OPLC V350-35-B1 User manual

Unitronics V200-18-E46B User manual

Unitronics

Unitronics V200-18-E46B User manual

Unitronics V200-18-E4XB User manual

Unitronics

Unitronics V200-18-E4XB User manual

Unitronics UG-ULK-EIP-4AP6 User manual

Unitronics

Unitronics UG-ULK-EIP-4AP6 User manual

Unitronics V200-18-E62B User manual

Unitronics

Unitronics V200-18-E62B User manual

Unitronics Uni-I/O UIA-0006 User manual

Unitronics

Unitronics Uni-I/O UIA-0006 User manual

Unitronics IO-DI16 User manual

Unitronics

Unitronics IO-DI16 User manual

Unitronics UID-W1616R User manual

Unitronics

Unitronics UID-W1616R User manual

Unitronics IO-DI8-RO8-L User manual

Unitronics

Unitronics IO-DI8-RO8-L User manual

Unitronics Uni-I/O UIS-08TC User manual

Unitronics

Unitronics Uni-I/O UIS-08TC User manual

Unitronics V200-18-E1B User manual

Unitronics

Unitronics V200-18-E1B User manual

Unitronics EX90-DI8-RO8 User manual

Unitronics

Unitronics EX90-DI8-RO8 User manual

Unitronics UG-ULK-1616P2-M2P6 User manual

Unitronics

Unitronics UG-ULK-1616P2-M2P6 User manual

Popular I/O System manuals by other brands

socomec DIRIS O-iod quick start

socomec

socomec DIRIS O-iod quick start

National Instruments USB-9213 USER GUIDE AND SPECIFICATIONS

National Instruments

National Instruments USB-9213 USER GUIDE AND SPECIFICATIONS

Parker AC30 series product manual

Parker

Parker AC30 series product manual

Rockwell Automation Sensia Jiskoot InSpec Remote I/O HUB Installation, operation & maintenance manual

Rockwell Automation

Rockwell Automation Sensia Jiskoot InSpec Remote I/O HUB Installation, operation & maintenance manual

OPTO 22 E1 manual

OPTO 22

OPTO 22 E1 manual

HIMA HIMax  X-AO 16 01 manual

HIMA

HIMA HIMax X-AO 16 01 manual

Magnetek SMART TRAC DM6420 Engineer's guide

Magnetek

Magnetek SMART TRAC DM6420 Engineer's guide

evertz 7780MD Series user manual

evertz

evertz 7780MD Series user manual

King Pigeon M T Series user manual

King Pigeon

King Pigeon M T Series user manual

IFM CompactModule Metal CR2031 Device manual

IFM

IFM CompactModule Metal CR2031 Device manual

WAGO I/O System 750 Series manual

WAGO

WAGO I/O System 750 Series manual

WAGO WAGO-I/O-SYSTEM 750 XTR Series manual

WAGO

WAGO WAGO-I/O-SYSTEM 750 XTR Series manual

Rockwell Automation Allen-Bradley IF2 installation instructions

Rockwell Automation

Rockwell Automation Allen-Bradley IF2 installation instructions

ICP DAS USA I-7018 quick start guide

ICP DAS USA

ICP DAS USA I-7018 quick start guide

Allen-Bradley SLC 500 1746-NT8 installation instructions

Allen-Bradley

Allen-Bradley SLC 500 1746-NT8 installation instructions

M-system R5T-PA2 instruction manual

M-system

M-system R5T-PA2 instruction manual

WAGO I/O-SYSTEM 750 753-501 manual

WAGO

WAGO I/O-SYSTEM 750 753-501 manual

Siemens Binary Input N 260 Technical product information

Siemens

Siemens Binary Input N 260 Technical product information

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.