Installation,Operation, Maintenanceand PartsManual
IR Series Heaters
3.1 GASSUPPLY
CAUTION!
CORRECT INLET PRESSURES ARE VITAL FOR
EFFICIENT OPERATION OF HEATER. REFER TO
AGA/CGA RATING PLATE AND, IF NECESSARY,
CONSULTGASCOMPANY.
Ifall ora portionof thegassupplylineconsists ofused
pipe,itmustbecleanedandtheninspectedtodetermine
itsequivalency to new pipe. Test all main supplylines
accordingtolocalcodes. (Isolate heatergasvalve and
suppliedgascockduringtest.)
Excessivetorque on manifold maymisalign orifice(s).
Alwaysusetwowrenches whentighteningmating pipe
connections.
WARNING!
Neveruse a match oranyother flame to test for
gasleaks. Useasoapandwatersolutiontocheck
forleaks.
Ifanyportionof thegassupplylineislocatedin anarea
thatcouldcauseanabnormalamountofcondensateto
occurinthepipe,asedimenttrap shouldbe installed.
NOTE: For high pressure gas above 14 in. W.C.P.
(WaterColumn),ahighpressureregulatorandgascock
mustbeused. Ifcompressedairisusedtodetectleaks
inthegassupplyline,disconnectandcapshutoffcock
toavoiddamageto regulatorandgasvalve.
A sediment trap in the gas line will decrease the
possibility of any loose scale or dirt in the supply line
entering the heater’s control system and causing a
malfunction. Providea 1/8 in. (3.2mm) NPT,plugged
tapping accessible for test gauge connection
immediatelyupstreamofgasconnectiontoheater. The
gassupplylinemust beof sufficientsize toprovide the
requiredcapacityandinletpressuretotheheater(consult
gascompany) asfollows:
NOTE: Manifoldpressureshouldbecheckedatthetap
onthegasvalve. Readingswillbeaboveatmospheric
pressure(duringoperation).
Useonlyapipejointcompoundthatisresistanttoliquified
petroleumgases.
•AllowanceforExpansion
Allowancesmustbemadeforthesystemtoexpand.
Theuse ofa stainlesssteel,flexible gasconnector
isrecommended. If, however, local codesrequire
rigidpipingto theheater,aswingjoint canbeused.
•GasLineConnection
a. The gas outlet shall be in the same room as the
applianceandtheconnectormustnotbeconcealed
withinorrun throughanywall, floororpartition.
b. Theconnector shallbeofadequatelength.
c. The final assembly shall be tested for leaks.
CAUTION:Matches,candles,openflameorother
sourcesofignitionshallnotbeusedforthispurpose.
Leaktestsolutionsmaycausecorrosion-waterrinse
aftertest.
d. Contact withforeign objectsor substancesshould
beavoided.
e. The connector should not be kinked, twisted or
torqued.
f. Connectors are for use only on piping systems
havingfuelgaspressuresnotinexcessof ½pound
persquare inchor 14.0 in.W.C.P.
g. Bending,flexingandvibrationtothegasconnections
shouldbeavoided.
CAUTION!
CONNECTOR NUTS MUST NOT BE CONNECTED
DIRECTLYTOPIPE THREADS. THISCONNECTOR
MUSTBEINSTALLEDWITHADAPTORSPROVIDED.
DONOTREUSE.
Figure 3.1
IR Series
Required
Manifold
Pressure (WCP)
Minimum
Inlet Pressure
(WCP)
Maximum
Inlet Pressure
(WCP)
Natural Gas 6.0 in. 7.0 in. 14.0 in.
Liquified
Petroleum Gas 10.0 in. 11.0 in. 14.0 in.
MANIFOLD PRESSURE CHART