UseTECH FlowTimer+ Protect Set User manual

FlowTimer+ Protect Set
Hot water Shut-off valve
for the FlowTimer+ System
Operating Manual

Publisher
usetech GmbH
Tanzplatz 10
D- 55130 Mainz
Phone:
+49 6131 - 921325
Website:
www.use-tech.com
Document
number
FlowTimer+ Protect Set_Manual_EN_V3
Original Operating Manual
Date of issuance
04.03.2019
Printing date
04.03.2019
Copyright
usetech GmbH
This documentation including all its parts is protected by copyright.
Any use or modification outside the narrow limits of copyright law
without the consent of the company usetech GmbH is prohibited
and punishable by law.
This applies in particular to duplications, translations, microfilming
and storage in electronic systems as well as processing in these.

Table of contents
03/19 FlowTimer+ Protect Set 1
Table of contents
Table of contents.........................................................................1
1General information.............................................................3
1.1 Explanation of symbols .........................................................3
2Technical data......................................................................5
2.1 Electrical data........................................................................5
2.2 Fluidic data............................................................................5
2.3 Environmental and climate conditions...................................5
2.4 Lifetime..................................................................................5
3Intended Use ........................................................................6
3.1 Non-approved use.................................................................7
4Basic safety instructions.....................................................8
5System description FlowTimer+ Protect Set......................9
5.1 Content of the FlowTimer+ Protect Set.................................9
5.2 FlowTimer+ Protect front view.............................................10
5.3 FlowTimer+ Protect rear view .............................................11
6Installation..........................................................................12
6.1 Measures before installation ...............................................12
6.2 Installation position..............................................................12
6.3 Installation of the Shut-off valve..........................................13
6.4 Mounting the Electronic on the Shut-off valve ....................14
6.5 Electrical connection ...........................................................15
7Getting Started...................................................................16
7.1 Checking the Hot Water Preparation ..................................17
8Operation and Function.....................................................18
8.1 Operating conditions ...........................................................18

Table of contents
03/19 FlowTimer+ Protect Set 2
8.1.1 Normal operation...........................................................................18
8.1.2 Restarting the system....................................................................18
8.1.3 Bypass operation...........................................................................19
8.2 Status display......................................................................20
9Troubleshooting, Maintenance .........................................21
9.1 No display............................................................................21
9.2 Alarm signals.......................................................................22
9.2.1 Status display permanently red.....................................................22
9.3 Maintenance........................................................................23
10 Shutting down....................................................................24
11 Packaging, Transport, Storage .........................................25
12 Disposal..............................................................................26
13 EC Declaration of Conformity ...........................................27
14 Declaration of Conformity Valve.......................................28

General information
03/19 FlowTimer+ Protect Set 3
1 General information
The operating instructions describe the entire life cycle of the
system. Keep this manual in such a way that it is easily accessible
to any user and available to any new owner of the system.
NOTE
The operating instructions contain important
information on safety!
Non-observance of these instructions can lead to dangerous
situations.
The operating instructions must be read and understood.
1.1 Explanation of symbols
DANGER
Warns of imminent danger!
Failure to do so will result in death or serious injury.
WARNING
Warns of a potentially dangerous situation!
Failure to do so could result in serious injury or death.
CAUTION
Warns of a possible hazard!
Failure to do so may result in moderate or minor injury.
NOTE
Warns of material damage!
Failure to do so may result in damage to the system or
equipment.

General information
03/19 FlowTimer+ Protect Set 4
indicates important additional information, tips and
recommendations that are important for your safety and the
proper functioning of the system.
refers to information in this operating manual or other
documentation.
Action steps
The defined sequence of steps makes it easier for you to
use the system correctly and safely.
Result
Here you will find the result of a sequence of steps
described.

Technical data
03/19 FlowTimer+ Protect Set 5
2 Technical data
2.1 Electrical data
Input voltage: 100 - 240 V~
Power consumption: Ø max. 6 W
Frequency: 50 - 60 Hz
Connection: Euro plug power supply unit
2.2 Fluidic data
Inlet pressure: 0 - 10 bar
Kv value (valve): 4.9 m³/h
Sealing material: EPDM
Connection: G 3/4 inch IT (standard version)
2.3 Environmental and climate conditions
Ambient temperature: +5°C - 40°C
Media temperature (drinking water): 5 - 80°C
Protection class: IP20
Location: only suitable for indoor use
2.4 Lifetime
The function of FlowTimer+ Protect must be checked by a
qualified technician at the scheduled intervals (see also chapter
9.3).
If the fluidic part of the unit shows a fault due to wear, this is
indicated by a fault in the overall system (incl. downstream
piping system) via the control electronics.

Intended Use
03/19 FlowTimer+ Protect Set 6
3 Intended Use
Please observe the notes in this operating manual as well as the
operating conditions and permissible data in the data sheet so that
the system functions perfectly and remains operational for a long
time. In case of non-observance of these instructions as well as in
case of inadmissible interventions into the system, any liability on
our part is void, as is the warranty on the system and accessories!
There are drinking water heating systems in which heated water
runs after the cold water supply has been shut off.
The FlowTimer+ Protect serves thesimultaneous shut-off of the hot
water pipe in case of an alarm by one or more FlowTimer+ (see
also chapter 2 "Technical data").
The use of FlowTimer+ Protect requires at least one FlowTimer+
and one FlowTimer+ Hub!
Any other use or use going beyond this shall be deemed improper
use. The usetech GmbH is not liable for damages resulting from
this. The risk is borne solely by the user.

Intended Use
03/19 FlowTimer+ Protect Set 7
3.1 Non-approved use
Unapproved use in the sense of a foreseeable misuse shall be
deemed to be improper use:
FlowTimer+ Protect was designed exclusively for drinking water.
The system is not suitable for rainwater, other liquids or gases.
The FlowTimer+ Protect may only be used with the components
in the set or other FlowTimer+ products, unless explicitly stated
otherwise! If components of other manufacturers are used,
usetech GmbH is not liable for damages and the warranty also
expires.
FlowTimer+ Protect is not suitable for use within the heating
installation!

Basic safety instructions
03/19 FlowTimer+ Protect Set 8
4 Basic safety instructions
WARNING
Electrical voltage can be life-threatening.
The installation of a stationary power supply must be
carried out by a qualified electrician.
The system must be commissioned and, if necessary,
adapted by a specialist. The local conditions must be
observed.
The measures before installation must be observed (see
also chapter 6.1 "Measures before installation").

System description FlowTimer+ Protect Set
03/19 FlowTimer+ Protect Set 9
5 System description FlowTimer+ Protect Set
5.1 Content of the FlowTimer+ Protect Set
Fig. 5.1: Content of the FlowTimer+ Protect Set
1
Plug-in power supply
2
3/4 inch Shut-off valve
3
FlowTimer+ Protect
4
Anchor pipe

System description FlowTimer+ Protect Set
03/19 FlowTimer+ Protect Set 10
5.2 FlowTimer+ Protect front view
Fig. 5.2: FlowTimer+ Protect front view
5
Device illuminated rim / Status display

System description FlowTimer+ Protect Set
03/19 FlowTimer+ Protect Set 11
5.3 FlowTimer+ Protect rear view
Fig. 5.3: FlowTimer+ Protect rear view
14
I/O connection
15
Solenoid
16
Year of construction / Serial number
17
Pressure sensor connection (not required)
18
Power supply connection

Installation
03/19 FlowTimer+ Protect Set 12
6 Installation
The FlowTimer+ Protect must be installed in the piping
system by a trained technician according to the installation
instructions.
6.1 Measures before installation
If the operating pressure is greater than 10 bar, a pressure
reducer must be installed upstream of the FlowTimer+ Protect.
If no filter has been installed in the cold water inlet of the entire
system, it should now be retrofitted to protect the valve from
contamination.
Existing KFR valves, non-return valves or non-return valves
must be tested for function and tightness and replaced if
necessary.
6.2 Installation position
The FlowTimer+ Protect is always installed upstream of the
pipeline section to be shut off and the consumer.

Installation
03/19 FlowTimer+ Protect Set 13
6.3 Installation of the Shut-off valve
The installation position of the shut-off valve (2) is not arbitrary!
It may be installed rotated around its own axis by max. +/- 90
degrees (armature tube and solenoid coil may point to the side,
but not downwards)! The valve must also be installed in the
correct direction (observe the flow direction arrow on the valve).
The valve body must be easy to open for maintenance work. The
Allen screws on the valve upper body must be accessible from
the outside.
The selected mounting position must allow the assembly and
disassembly of the control electronics (3) with solenoid coil (15).
The shut-off valve may only be screwed into the pipeline at the
flange connections using a fork wrench.
Install the shut-off valve (2) first!
Please observe the cable lengths and the visibility of the
front side of the FlowTimer+ Protect when installing the
valve.
The upper part of the system (FlowTimer+ Protect [3]) and
the plug connections must not be subjected to mechanical
stress (danger of destruction)!

Installation
03/19 FlowTimer+ Protect Set 14
6.4 Mounting the Electronic on the Shut-off valve
The FlowTimer+ Protect electronic (3) is firmly screwed to
the solenoid coil (15) and forms a unit which must never be
separated (loss of warranty).
To mount the FlowTimer+ Protect on the shut-off valve, the
solenoid coil (15) is placed on the armature tube of the valve (4).
Then press briefly and forcefully on top of the solenoid coil (not on
the electronics) until the coil audibly engages in the holder. Thus
the coil is mounted correctly.
The supplied O-ring between valve body and coil is important. In
case of loss or defect, please contact our customer service.
To disassemble, push one or two screwdrivers between valve body
(2) and solenoid coil (15). Then lever the coil away from the valve
body. This requires a little more force than the previous pressing.

Installation
03/19 FlowTimer+ Protect Set 15
Never use tools to lever between the valve and the
FlowTimer+ electronics! (danger of destruction)
6.5 Electrical connection
If the I/O plug is plugged into the socket, this must cause
a clicking noise. If not, please check again whether the
plug is correctly engaged!
When disconnecting connections, please note to press
the locking lugs of the I/O connectors!
Connect the FlowTimer+ Hub to the I/O port (14) of the FlowTimer+
Protect using the I/O connection cable.
Plug the power supply unit into a suitable socket and connect the
power supply unit to the power supply connection (18) of the
FlowTimer+ Protect.
The I/O connection cable incl. the plug connections
between Hub and Protect are monitored by the
electronics as well!
If the FlowTimer+ Protect is supplied with power and this
connection is disturbed, it is shut off for safety reasons.
The I/O connections between the individual FlowTimer+ and the
FlowTimer+ Hub are not monitored to easily find a possible single
alarm in the alarm group.

Getting Started
03/19 FlowTimer+ Protect Set 16
7 Getting Started
WARNING
Electrical voltage can be life-threatening.
The installation of a stationary power supply must be
carried out by a trained electrician.
The system must be commissioned and, if necessary,
adapted by a specialist. The local conditions must be
observed.
Air in the hot water supply, e.g. in the hot water storage
tank, can lead to scalding due to hot water running in if the
water supply is interrupted.
Disconnect the power supply of the FlowTimer+ Protect from the
socket
Establish water supply
Venting and checking the cold and hot water pipes including the
hot water preparation and the heat exchangers
Check consumer for visible leaks, watch out for traces of
limescale! (Toilet flushing, leaking taps, garden connections,
washing machines, dishwashers, etc.).
Restore power supply

Getting Started
03/19 FlowTimer+ Protect Set 17
7.1 Checking the Hot Water Preparation
Setting the water heater to the maximum permissible
temperature and preparing hot water
Open the hot water pipe and test for hot water leakage.
Pull the pressure sensor plug on the FlowTimer+ and interrupt
the cold water supply.
The status display of the FlowTimer+, FlowTimer+ Hub
and FlowTimer+ Protect must now be permanently red!
At the moment of the interruption of the cold water section, it
must no longer be possible to detect that the hot water circuit is
running after the cold water section.
CAUTION
If warm water is added, there is a risk of scalding!
Disconnect the power supply to FlowTimer+ and
FlowTimer+ Protect to prevent possible shut-off.
A technician needs to take a closer look at your
installation.
The system is then not ready for operation until
clarification!

Operation and Function
03/19 FlowTimer+ Protect Set 18
8 Operation and Function
8.1 Operating conditions
8.1.1 Normal operation
In the event of a fault, FlowTimer+ Protect separates the
consumer from the hot water supply by means of a
solenoid diaphragm valve.
The FlowTimer+ Protect operating status can be seen via the
illuminated bezel (5) (see chapter8.2 "Status display").
An operation of FlowTimer+ Protect is not necessary, because an
alarm as well as its resetting is done automatically by the upstream
FlowTimer+ systems.
8.1.2 Restarting the system
Unplug the AC adapter (1) from the wall outlet or disconnect the
power supply.
wait ten seconds
Restore power supply
Table of contents