V-GREAT VG-6132 User manual

VG-6132 Gas Extinguishing Panel
Installation and Operation Manual
(Ver 1.02, October 2019)
V-GREAT GLOBAL CORPORATION

VG-6132 Gas Extinguishing Panel
1
CONTENTS
Chapter 1 Overview ....................................................................................................................................... 1
Chapter 2 Technical Specifications .............................................................................................................. 1
2.1 Functions .................................................................................................................................................. 1
2.2 Technical Specifications........................................................................................................................... 1
Chapter 3 Structure ....................................................................................................................................... 1
3.1 Appearance and structure dimension .................................................................................................... 1
3.2 Installation Dimension............................................................................................................................. 2
3.3 Front Panel ............................................................................................................................................... 2
3.4 Internal Structure .................................................................................................................................... 4
3.5 Terminals Description ............................................................................................................................. 4
Chapter 4 Installation and Commissioning ................................................................................................. 4
4.1 Unpacking and Inspecting ...................................................................................................................... 5
4.2 Installation ................................................................................................................................................ 5
4.3 Wiring Requirements .............................................................................................................................. 5
4.4 Check of Control Panel ........................................................................................................................... 5
4.5 Wiring ....................................................................................................................................................... 6
4.6 Start ........................................................................................................................................................... 6
4.7 Configure .................................................................................................................................................. 6
Chapter 5 System Setting and Operation .................................................................................................... 6
5.1 System Setup ............................................................................................................................................ 6
5.2 System Operation .................................................................................................................................... 7
5.3 Self-test ..................................................................................................................................................... 8
5.4 Reset .......................................................................................................................................................... 8
5.5 Silence .................................................................................................................................................... 8
5.6 Records .................................................................................................................................................. 8
5.7 Start and stop sounder strobe ................................................................................................................. 8
5.8 Switch between manual and auto ........................................................................................................... 8
Chapter 6 Commissioning ............................................................................................................................. 9
6.1 Commissioning notes ............................................................................................................................... 9
Chapter 7 Trouble Shooting ........................................................................................................................ 10
Chapter 8 Cautions ...................................................................................................................................... 11
Chapter 9 Storage and Transportation ...................................................................................................... 11
9.1Package and Transportation .................................................................................................................. 11
9.2 Storage .................................................................................................................................................... 11

VG-6132 Gas Extinguishing Panel
1
Chapter 1 Overview
VG-6132 Gas Extinguishing Panel(called the panel or control panel for short)is a kind of extinguishant gas
releasing equipment of low cost and high efficiency Use the graphic dot matrix as liquid crystal display (LCD).
The panel is able to monitor two protection zones against emergency fire. It is mainly designed for small and
medium fire protection projects, widely applicable for banks, data room, telecom station and manufacturing
plants. The panel has a reliable performance and complies with international standards for safety and
environment concern.
Chapter 2 Technical Specifications
2.1 Functions
2.1.1 Liquid Cristal Display (LCD)
The panel uses the graphic dot matrix as its LCD and adopts LEDs to indicate critical status of the system.. It is
easy and convenient to view the fire messages and status of the system from the LCD.
2.1.2 Wiring
The panel connects with external devices controlled through multi-wire.
2.2 Technical Specifications
2.2.1 Power:Switch between the main power and the battery power automatically.
Main power:AC 220V(187V~242V)/0.5A,50Hz
Standby power:DC 12V/4AH(12V/2.7AH, two units)
Battery protection voltage:11V-10.6V
Battery recharging voltage:11.5V-12.3V
Maximum input power:100W
2.2.2 Load capability :
Maximum protection zones: Two zones(loads types:smoke detector, heat detector, emergency start/abort button,
sounder strobe, gas releasing sign and solenoid valve)
Load action voltage:DC20V~24V
Load standby current <200mA
Load action current >1A
2.2.3 Operating Environment:
Ambient temperature:0℃~45℃
Relative humidity ≤95%RH(40℃±2℃)
2.2.4 Standard:GA 61-2010
Chapter 3 Structure
3.1 Appearance and structure dimension
Dimension of the control panel is shown in Fig. 3-1: 430mm* 330mm* 24mm (L*W*D).

VG-6132 Gas Extinguishing Panel
2
VG-6132 Gas Extinguishing Panel
Override
12
Pre-Alarm
Fire
Activate
Sounder
Delay
Discharge
Response
Start
Abort
Fault
SYS Inspect
Reserve
Silence
BatteryPower On
Abort 2
Auto
Manual Standby
Start 2
Start 1 Abort 1
Enter
ResetSelf-testSilenceCancel
Menu
Power Fault Battery Fault COM Fault
430mm
330mm
106mm
Fig. 3-1
3.2 Installation Dimension
Mounting hole of VG-6132 Gas Extinguishing Panel is shown in Fig. 3-2 ( 360mm*135mm ) .
Two Mounting Holes
Fig. 3-2
3.3 Front Panel
Front panel of VG-6132 Gas Extinguishing Panel is shown in Fig. 3-3.

VG-6132 Gas Extinguishing Panel
3
Fig. 3-3
Critical status of VG-6132 Gas Extinguishing Panel are indicated by LEDs, description is shown as below.
Main control section
◇ Power(Green):It turns on when the main power is supplied and turns off when the power is low
voltage or the power cable is broken.
◇ Battery(Green):It turns on when the battery power is working normally, and turns off when the
battery power is low voltage or the power cable is broken.
◇ Silence(Green): The LED turns on when the Silence key is pressed.Reserve(Amber):LED Reserve
for other usage.
◇ Power Fault(Amber):It turns on when the main power is low voltage or the cable is broken, and turns
off when the main power is working normally.
◇ Batt Fault(Amber):It turns on when the standby power is low voltage or the cable is broken and turns
off when the standby power is working normally.
◇ COM Fault(Amber):It runs on when there is any fault occurred on the control panel and turns off when
all faults are removed.
◇ SYS Inspect(Amber):It turns on when the panel is under self-testing.
◇ Manual(Red):It turns on when Manual/Auto lock is set to manual.
◇ Auto(Red):It turns on when Manual/Auto lock is set to auto.
◇ Standby(Red):It turns on when Override lock is closed.
◇ Override(Red):It turns on when Override lock is opened.
Fire Protection Zone Section
◇ Pre-alarm(Red):It turns on when there is fire and turns off automatically if there is no fire alarm within
30 minutes.
◇ Fire (Red):It turns on when there is fire and turns off automatically if there is no alert signal within 30
minutes.
◇ Activate(Red):In AUTO mode, LED turns on when the panel activates the action outputs.
◇ Sounder(Red):It turns on when the sounder strobe is activated and turns off when the sounder strobe is
off.
◇ Delay(Red):It turns on when the panel is in delay mode.
◇ Discharge(Red):It turns on when the control panel activates the cylinder valve.
◇ Response(Red):It turns on when the panel receiving feedback from solenoid valve, and LED
illuminates until reset.
◇ Start(Red):It turns on when the Start button is pressed and turns off whenthe Abort button is pressed.
◇ Abort(Red):It turns on when the Abort button is pressed and turns off after reset.

VG-6132 Gas Extinguishing Panel
4
◇ Fault(Amber):It turns on whenthere is open or short occurred in the output circuits, and turns off when
the circuit is back to normal.
3.4 Internal Structure
3.5 Terminals Description
3.5.1. Wiring description of terminal 1 is shown below.
Cylinder+
Cylinder-
Detection 1 +
Start
Com
Pressure+
Pressure-
Gas Release+
Gas Release-
Sounder+
24V -
AC Panel+
Detection 1 -
Detection 2 +
Detection 2 -
Abort
solenoid
valve
Pressure
Switch
4.7K
Gas Release
Indicate
4.7K
24V+ 24V-
Sounder
4.7K
24V+ 24V-
AC Panel
4.7K
Gas Extinguishing Zone
Cylinder Room
DC 24V VSS
COM
4.7K 4.7K
Start/Abort Button
12
43
12
43
12
43
12
43
4.7K 4.7K

VG-6132 Gas Extinguishing Panel
5
Detection 1+
Start
Detection 1-
Detection 2+
Detection 2-
Cylinder +
Abort
Com
Pressure +
24V-
AC Panel +
Cylinder -
Pressure -
Gas Release+
Gas Release-
Sounder+
3.5.2. Wiring description of terminal 2 is shown below.
COM Fire COM Fault COM Start COM Response
1 2 3 4 5 6 7 8
Notes:
1. COM Fire, COM Start and COM Response are normally closed, and open when activated.
2. COM Fault is normally open and closed when activated.
Chapter 4 Installation and Commissioning
4.1 Unpacking and Inspecting
Open the package carefully not to damage the control panel. Check the items against the packing list. Check
internal configuration and connection of different parts. Then inspect the appearance of the control panel. If a
problem is found, solve it as soon as possible and then install the control panel.
4.2 Installation
Mounting dimension is shown as Fig. 3-2.
4.3 Wiring Requirements
◇ Wiring for terminals inside the cabinet: all wires should be peeled 0.5cm and tinned or clipped before
connecting into the cabinet.
◇ Control Output Cable:
Conductor:1.0 mm2 or above copper conductor, withstand voltage≥ 250V,twisted pair.
Cable:0.75 mm2 or above copper cable,withstand voltage≥ 250V.
Total resistance of cable<50Ω,otherwise increase the cross section of the cable.
◇ Conduit Pipe: The cable should be installed in a individual conduit pipe, and be away from others cables such
as power line, lighting cable, AC cable, CCTV cable, VA cable etc.
◇ Wiring in cable shaft: The loop wires should be installed in a respective metal sink, away from those wires
such as power line, lighting cable, CCTV cable etc, the parallel distance between the loop wite and other power
supply lines should be further than 500mm.
◇ Connectors: all connectors for wiring should be welded or crimped and sealed by isolated sleeves to avoid
short circuit and current leaking.
4.4 Check of Control Panel
When the control panel is installed in the field, turns on the power and do the functional checks at first, including:
(1) Observe if the LEDs and sections of LCDs are lit and the loudspeaker gives a resonant sound.

VG-6132 Gas Extinguishing Panel
6
(2) Enter into the standby state, check the power fault and operating keys, as well as field devices are in
good condition.
4.5 Wiring
After checking the control panel, if the results of all the tests meet the requirements, please refer to Chapter 3
Structure in this manual for connecting terminals with field devices. All cables should comply with 4.3 Wiring
Requirement in this manual.
4.6 Start
Check AC input cable and make sure it is connected firmly. Then apply AC power, test the voltage. Switch on the
power after the voltage is correct, observe LCD and all LEDs and ensure they are working well. Switch off AC
power immediately if there is any fault occurred and find out the reason. The panel can be restarted only after the
fault is removed.
If there isn’t AC power, the standby power is only used, in this case, press the Start button of the battery after
connection.
4.7 Configure
After check with the wiring and connection carefully, configure can be started according to the following steps.
(1) Switching on the power, the control panel tests LEDs, LCD and sounds automatically. After self-test, the
control panel enters the standby mode.
(2) Ensure the panel is placed in the clean air and then make commissioning. Refer to “Chapter 5 System Setting
and Operation
”
and “Chapter 6 Commissioning
”
for details.
Chapter 5 System Setting and Operation
5.1 System Setup
System setup mainly include system time set, delay set, loop check, printer set and so on.
How to enter system setup: Switch on the power, press Menu to input “▲▼▲▼” password under system running
screen, and then press “▼” to enter system setup screen.
5.1.1 Time Set
Go to 3 time set. Press “Enter” key to go to system time set screen, shown as Fig. 5-1.
Fig. 5-1
Pressing “Enter” key, the cursor _ will be switched. Pressing “▼” key, the number positioned at cursor, is
added up 1 p.
Pressing “Enter” saves the time after complete setting. Press Menu or Cancel to return.
5.1.2 Delay Set
Press “Menu” and type-in passwords. Then press “▼” key down to choose “4 Delay Set” and press “Enter” key to
set delay time.
Y:10 M:03 D:05
15:18:58
Zone 1 Delay 08 seconds
Zone 2 Delay 18 seconds

VG-6132 Gas Extinguishing Panel
7
Fig. 5-2
Pressing “Enter ” key, the cursor can move up and down to set delay time. Pressing “▼” key, delay time will be
added 1.
Pressing “Enter” key saves the delay time.
Then pressing “Cancel” key returns to the loop check.
5.1.3 Loop-checking Set
Pressing “Menu” key and “▼” key, choose “7 Loop check”. Press “Enter” key to go to the screen for setting
number of loop-check, as shown in Fig. 5-2.
Fig. 5-2
Pressing “▼” key, the number of Loop-check will be added 1.
Pressing “Enter” key saves the set.
Pressing “Cancel” returns to system operation page.
5.1.4 Printer Set
Press “Menu” key, enter the password and then press “▼” key, choose “8 Printer Set”. Press “Enter” key to go to
the screen for setting printer, as shown in Fig. 5-2.
Fig. 5-3
Press “▼” key, the printer can be set to ON or OFF states.
Press “Enter” key to save the set.
Press “Cancel” to return to system operation page.
5.2 System Operation
LCD of the system displays time as shown in Fig. 6-1 after power on.
Fig. 6-1
The First Lineindicates the system time.
The Second Lineindicates that there is no fire and fault message.
The First line indicates the system time.
The Second LinThat there is short or open circuit in Zone 2. Please view details by entering Fault Query menu.
08: 23: 15
System Operation On
Polling Coil No: 05
Printer Off
08: 23: 15
Circuit Fault In Zone 2
08: 23: 15
Fire In Zone 2

VG-6132 Gas Extinguishing Panel
8
The First Line indicates the system time.
The Second Linethat there is fire alarm message in Zone 2.
5.3 Self-test
Pressing “Self-test” key,and then “Enter” key four times, the system begins self-testing. All LEDs of the system
are lit, the buzzer gives continuous alarm sound and LCD display “self-testing…”.
5.4 Reset
Pressing “Reset ” key, and then “▲” key four times, the system is reset.
5.5 Silence
Pressing Silence key when there is fire or fault, sound of the control panel can be silenced.
5.6 Records
5.6.1 Fault records
In system operation page, press Menu, and input “▲▼▲▼” password. Pressing “▼” can enter the screen
shown in Fig. 6-2. Then press “Enter” to go to “Fault query”. Press “▼” to display fault messages. It returns to
fire condition if there is a fire.
Fig. 6-2
5.6.2 History Record
In system operation page, press “Menu” and press “▼” to enter the screen shown as Fig. 6-3. Then pressing
“Enter” goes to “History Record Query”. Press “▼” to display history records. This panel can record 999
messages.
Fig. 6-3
5.7 Start and stop sounder strobe
When there is fire, the souder strobe is activated automatically. When there is not fire, press Menu to enter the
password, and then press “▼” and “Enter” to start the sounder strobe. If the sounder strobe should be stopped,
repeate the previous steps and then press Enter to stop.
5.8 Switch between manual and auto
Warning:The right side of the display is auto-switching and special function area. Please don’t operate it
unless you are special trained person, in order to avoid property loss and personal injuries.
Fault Record
History Record

VG-6132 Gas Extinguishing Panel
9
Chapter 6 Commissioning
6.1 Commissioning notes
1. Before commissioning works, please take off the wires, and use the Multimeter to test the resistance value
of cables at first. The resistance of all wires should be over 4.7 kΩ.
2. If connected more than one Start/Abort Button, the end resistor must be installed on the last Start/Abort
Button.
3. If the extinguishing panel was connected with Aerosol products or Electrical-explosion initiator, please set
the Jumper P4 and P5 same as the Pic 6-1 shown.
Pic 6-1
4. In some projects with special requirements, if the function of loop testing for short or open circuit is not
required, please turn the switch to the right side as Pic 6-2 shown.

VG-6132 Gas Extinguishing Panel
10
Pic6-2
Chapter 7 Trouble Shooting
Trouble shooting is shown in Table 8-1.
Table 8-1
Problem Reason Solution
Circuit fault 1. Polarity reversed or incorrect
connection.
2. End of line resistor is fault.
3. The panel is damaged.
1.Correct the connection.
2.Replace the fault end of line resistor.
3.Contact the manufacturer.
No display or black
block on LCD
1.The connection with display
board is loose.
2. CPU board is loose or mis-placed.
3. The panel crashes.
4. Other reasons.
1.Fasten the connector.
2.Re-start the control panel.
3.Please contact with the manufacturer.
Detector reporting
fault
1. Incorrect connection.
2. Strong interference around the
detector or the detector is damaged.
3. end voltage is extra low because
power is abnormal, circuit is extra
long or the wire diameter is too
small.
1. Check the circuit.
2. Eliminate the interference and replace the
detector.
3. Check the reason for low voltage and
enhance the end voltage to normal.

VG-6132 Gas Extinguishing Panel
11
Chapter 8 Cautions
This product belongs to precise electronics, it should be kept by a special person, others are not allowed to
touch it at random.
Customers should record the information on duty. If there is an alarm, first press Silence key on the control
panel, confirm the fire and take proper procedures immediately. After that, make a record and press
“Reset” key to clear. If there is a false alarm, remove the detector or the module that giving an alarm after
making the record. Contact customer service of our company for repair.
Note:The control panel only connects with the standby power, and the batter will be run out. Charge the
battery in time after the battery is discharged completely; otherwise the battery will be damaged. Please
disconnect the battery line if it is not used for a long period. To extend battery’s life, recharge the battery if
it is placed for future use over three months.
We are responsible for repairing the control panel, so please let us know if there is any problem. Users are
not allowed to disassembly or repair without permission, otherwise we don’t take the consequences.
Chapter 9 Storage and Transportation
9.1Package and Transportation
Control panels are packed by materials with vibration reduction, damp proof, withstand compression. Common
vehicles can be used to transport control panels and awful weather such as rain and snow, and mechanical impact
should be avoided. Box for control panel shouldn’t be reversed.
9.2 Storage
Before installation, those control panels should be placed in a warehouse. There should have 1 meter at minimum
distance far from surrounding walls. In the warehouse, it is dry and ventilated without corrosion gas such as acid
or alkali. Strong impact should be avoided.
Company: V-GREAT GLOBAL CORPORATION
Add.: Second Floor, Capital City, Independence Avenue,
P.O. Box 1008, Victoria, Mahe, Seychelles
Web:http://www.vgreatglobal.com Email: tech@vgreatglobal.com
Table of contents
Other V-GREAT Security System manuals
Popular Security System manuals by other brands

Bosch
Bosch SOLUTION 6000 user guide

Xeos Technologies Inc.
Xeos Technologies Inc. Resilient user manual

Fortinet
Fortinet FortiAnalyzer-800B quick start guide

Night Watcher
Night Watcher NW700 user guide

Defender
Defender WHDREC quick start guide

ADEMCO
ADEMCO Security System VISTA-10SE installation instructions