Valworx 561020C User manual

Doc: iom5610.5616.onoff.trouble.0618 Cornelius, N.C. • USA www.valworx.com
Troubleshooting Guide
Multi-Voltage On/Off Electric Actuators
5610/5616 Series
IOM
5610
5616
TSG On/Off
PROBLEM POSSIBLE CAUSE SOLUTION
Actuator will not open or close during
inial startup
Incorrect wiring of the gray DIN power
connector
Rewiring the gray DIN power plug per the
actuator electrical diagram and instrucons.
No suitable switching device Customer to supply a SPDT mechanical relay or a
3-way 2-posion manual switch to open and close
the actuator.
Incorrect voltage being supplied to actuator Conrm correct voltage is being applied to the
actuator. Connecng incorrect voltage may
damage the actuator beyond repair. Do not apply
more than 25.2 volts to the 12-24 volt actuators
(24volts +5%).
Power supply is not sized large enough This is a motor circuit, therefore power supply
should be sized at least 3 mes full load current.
Actuator does not have an isolated circuit or is
connected in parallel with other actuators or
equipment
Actuator should have its own fused and isolated
circuit. Do not connect actuators in parallel or
with other equipment on the same circuit.
Controls or controller is not compable with
the actuator. Leakage current from solid state
relays or contacts may cause actuator
malfuncon.
If possible, bench test the actuator without user
controls or controller. This will help determine
whether there is a problem with the actuator or
the input control circuit.
Actuator (valve) will close, but will not
open during inial startup. Slow LED
blink with DC voltage models.
Incorrect wiring of the gray DIN power
connector
Neutral or minus (-) power lead MUST be
connected to PIN 1 on gray power connector
(polarity sensive).
Actuator will not power up, LED on top
of actuator does not turn ON
Excessive power surge and/or an over voltage
condion. Damaged main circuit board.
LED light should be ON when power is applied. If
actuator was damaged by a power surge or over
voltage condion, replace with new actuator
Actuator runs but does not rotate
LED double blink or blinking orange
Actuator may be in the manual mode Move “MAN” selector lever to “AUTO”
Over-torque (possible valve jam). Remove over-torque condion, repower and try
again
Actuator will not complete the cycle
LED blinking on-o, red or green
Main control board or motor failure Replace with new actuator or return to factory for
evaluaon and/or possible repair
Valworx 5610/5616 series
On/O Electric Actuators
Models 561020C, 561055C, 561085C, 561020A,
561021A, 561020, 561021, 561055A, 561056A,
561085A, 561086A, 561603A, 561604A
Valworx electric actuators are 100% tested to
ensure trouble free installaon and operaon. 5610 Series 5616 Series

2
Doc: iom5610.5616.onoff.trouble.0618 Cornelius, N.C. • USA www.valworx.com
Manual Override
Selector Lever
MAN: Manual Mode
AUTO: Automac Mode
Visual Posion
Indicator (shown in
open posion)
LED Power On and
Diagnosc Light
Manual Override
Knob
PROBLEM POSSIBLE CAUSE SOLUTION
Cannot turn the manual override knob
Manual override selector lever in ‘AUTO’ mode Move manual override selector to ‘MAN’ mode
Excessive force applied to manual override
knob, this may have damaged the gear drive
If aer selecng ’MAN’, manual override sll does
not work, replace with a new actuator
Valve jam Clear valve jam and try again
Actuator fails to operate and
condensaon or water is found inside
the actuator
DIN plug connectors are loose, missing or have
damaged seals. Connector seal installed
incorrectly.
Inspect seals and replace if necessary. Make sure
seals are installed correctly and ghten DIN
connectors screw securely (0.4 to 0.5Nm).
Built in heater was not acvated connuously Power must be maintained to the actuator either
in the open or closed posion to acvate internal
heater. This heater will help prevent condensa-
on buildup inside the actuator. If the actuator
has failed due to excessive condensaon or water
inside the actuator, replace with a new actuator.
Actuator fails and excessive black dust
and/or corrosion is found under the
red cover
Excessive condensaon or water inside
actuator. Highly corrosive environment,
saltwater, chemicals, other.
If the actuator has failed due to excessive black
dust or corrosion inside the actuator, typically it is
non-repairable and must be replaced with a new
actuator.
Black dust from motor brush wear may be
caused by exceeding the 75% duty rang of the
actuator.
Actuator must be operated within the 75% duty
cycle rang. Typically, this means the motor can
be running for 45 seconds, then must be o for
15 seconds of each minute.
Actuator is worn out Replace with a new actuator
Switches are wired incorrectly Check the switch wiring and make sure the
common for limit switches is on PIN 1. If checking
connuity, you should have connuity between
PIN 1 and 2 when actuator is closed and
connuity between PIN 1 and 3 when open. No
connuity when actuator is moving in between
closed and open posions.
No output signal from posion
conrmaon limit switches Exceeding the current capacity has damaged
the limit switch. Switch rang 3 amps @
125/250VAC, 30VDC resisve load.
Damage to the limit switches is not a eld
repairable item. Either return actuator to the
factory for possible repairs or replace with a new
actuator.
Limit switch cams are out of adjustment. Limit switch cams can be adjusted if necessary.
Contact customer service for Service Procedure.
Troubleshooting Guide
Multi-Voltage On/Off Electric Actuators
5610/5616 Series
IOM
5610
5616
TSG On/Off
DIN Plug Connectors

3
Doc: iom5610.5616.onoff.trouble.0618 Cornelius, N.C. • USA www.valworx.com
Troubleshooting Guide
Multi-Voltage On/Off Electric Actuators
5610/5616 Series
IOM
5610
5616
TSG On/Off
Electrical Wiring Diagram for 5610/5616 series On-O Actuators
Before connecting
power, confirm
correct voltage is
being applied
12
3
CLOSEDOPEN
Customer
Supplied
Relay or
Switch
Power Connecon
LS1
OPEN
Signal
LS2
CLOSED
Signal
Posion Conrmaon
Limit Switches
12
3
N / -
L / +
LS1
N / -
LS2
N / -
COM
L / +
Earth
Ground
Power
VAC or VDC
Wiring Posion Conrmaon Limit Switches:
Two auxiliary dry contact limit switches are provided to conrm the
actuator (valve) open and closed posion. Use of these switches is
oponal and not required for the actuator to funcon properly. Switch
rang 3A@125/250VAC, 30VDC resisve load. Do not connect a
ground to this connector.
PIN 1: Common
PIN 2: Output Signal to conrm Closed Posion
PIN 3: Output Signal to conrm Open Posion
Wire Idencaon for Oponal Prewired DIN Cables
PIN 1 - Brown PIN 3 - Black
PIN 2 - Blue GROUND - Green/Yellow
Wiring Main Power Connecon:
Power is connected to the actuator via the large gray DIN plug
connector. Wires are connected to screw terminals located inside the
connector. User/installer to supply a SPDT mechanical relay or a 3-way
2-posion switch to control the actuator open and closed posion.
Power supplied to PIN 1 and PIN 2: CLOSED POSITION
Power supplied to PIN 1 and PIN 3: OPEN POSITION
Ground: Connect the at pin on DIN connector to earth ground
NOTES:
1. The Neutral (AC voltages) or Negave (DC voltages) must be connected
to PIN 1. The actuator is polarity sensive.
2. Power should be maintained, either in the open or closed posion to
acvate the internal heater. This heater will help prevent condensaon
build up inside the actuator.
3. Actuator should have it’s own fused and isolated circuit. Do not connect
actuators in parallel or on the same circuit with other equipment.
4. Supply voltage to 24 volt actuators should not exceed 25.2 volts
(24 volts +5%).
DIN Plug Connectors
1.Seal
2.Screw terminal block (Pins 1, 2, 3 & G)
3.Connector housing
4.Retainer screw
5.Cable retainer gland
Power
Connector
Posion
conrmaon
switches

4
Doc: iom5610.5616.onoff.trouble.0618 Cornelius, N.C. • USA www.valworx.com
Troubleshooting Guide
Multi-Voltage On/Off Electric Actuators
5610/5616 Series
Valve Misapplicaon
Somemes electric actuated valves may fail due to misapplicaon or using the valve in the wrong applicaon. Reviewing
and complying with the product specicaons will ensure long-term trouble free operaon. Specicaons can be found
online or in the product data sheet. Customers that connue to have problems with an actuator will usually indicate one
of two things. Either the actuated valve is unsuitable for the applicaon or it’s not in compliance with one or more of the
following issues:
Voltage: The voltage must be within the operang range of the actuator.
Over voltage or under voltage may cause premature failure.
Temperature: Operang outside the temperature rang will shorten the
life and ulmately cause the actuator to fail. Valworx 5610/5616 series
actuators must operate within the range of -4 to +158°F (-20 to +70°C).
Environment: The 5610/5616 series actuators have an IP67 weather-
proof rang. Generally suitable for indoor or outdoor applicaons. Provides
a degree of protecon against rain, splashing water and hose directed water
(Do not pressure wash). Protecng the actuator against rain, snow, ice and
UV (sunlight) will typically extend the life of the product. Highly corrosive
environments may cause premature failure of electronic components. Do not
use these actuators where explosion proof equipment is required.
Duty Cycle: Exceeding the 75% duty cycle rang of the 5610/5616 series
actuators will cause premature failure of the motor and/or electronic boards.
The motor should not move for at least 25% of the me (or typically 15
seconds of each minute).
Fluid Media: The valve materials of construcon should be compable
with the media (uid) owing through the valve. This would include all weed
parts or parts in contact with the media. Contacng the manufacturer of the
uid or consulng a media compability guide may be helpful. Ball valves and
buery valves generally require good clean owing media.
Pressure: Valves must operate within the pressure rang as listed in the
specicaons. The pressure rang is typically the highest non-shock working
pressure allowed within certain temperature limits. Reference the P/T chart
(pressure/temperature chart) to conrm the valve will operate within the
required pressure and temperature limits.
Fluid Velocity: The uid velocity should not exceed certain limits to help
avoid excessive noise, shock and damage to the piping system, seals and
valves. Typically, the maximum velocity of the uid owing through Valworx
metal valves should be less than 10 feet/second (3 m/s). The maximum
velocity for plasc valves should be less than 5 feet/second (1.5 m/s).
IOM
5610
5616
TSG On/Off
This manual suits for next models
12
Other Valworx Controllers manuals
Popular Controllers manuals by other brands

red lion
red lion TSC instruction manual

starlight
starlight CR1R instructions

UTC Fire and Security
UTC Fire and Security TruVision TVS-C100 user manual

Mitsubishi Electric
Mitsubishi Electric MELSERVO-J2S-S061 Specifications and Instruction Manual

Hissmekano
Hissmekano Viksam 3.0 manual

Quark-Elec
Quark-Elec QK-G033 Setup guide