VDH ALFANET TEMPLOGGER 16x PT1000 User manual

User manual
ALFANET TEMPLOGGER
16x PT1000 Module
Several Ranges
Description : ALFANET TEMPLOGGER 16x Pt1000 Doc.nr.: 071867
Type: Manual Number of pages: 10 Version: V2.4
File: Do071867 ALFANET TEMPLOGGER 16x
PT1000 v24 EN.wpd
Software: 061971 V2.01
By: HN Date: 05-02-2014
VDH Products BV - Roden - Holland Signed: File: Doc'07

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 2 van 10
Table of contents
1. Technical specifications. ............................................................ 3
2. Functional specifications. ............................................................ 3
2.1 Installation. .................................................................. 3
2.2 Operation. .................................................................. 3
3. Control. .......................................................................... 4
3.1 Controlling. .................................................................. 4
3.2 Read out. ................................................................... 4
4. Viewing and changing the parameters. ................................................. 4
4.1 Parameter list. ............................................................... 5
5. Front view. ....................................................................... 7
6. Dimensions. ...................................................................... 7
7. Connections. ..................................................................... 8
8. Adress. ......................................................................... 10
The information contained in this document is assumed to be accurate. However VDH Products BV accepts no liability
for eventual mistakes or errors and has the right to change this document without notice.

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 3 van 10
1. Technical specifications.
Type : ALFANET TEMPLOGGER 16x Pt1000
Supply : 12Vdc (-5/+10%)
Used power : Max. 200mA
Control : Through PC
Read out : Through PC
Inputs : 16x Pt 1000
Range : Lower Limit Value (LLV) .. Upper Limit Value (ULV),
see product sticker
Type nr. LLV .. ULV Resolution View per
901.000402 -50 .. +50 °C 0,1 °C 0,1 °C
901.000419 -100 .. +50 °C 0,2 °C 1 °C
901.000425 0 .. +100 °C 0,1 °C 0,1 °C
901.000447 -50 .. +150 °C 0,2 °C 1 °C
901.000467 -100 .. +50 °C 0,2 °C 0,1 °C
901.000468 -50 .. +150 °C 0,2 °C 0,1 °C
Accuracy : [+/-1x Resolution] + [+/-0,5% of (ULV - LLV)]
Example: 901.000468 = [+/- 0,2 °C] + [+/- 0,5 % of 200 °C] = +/- 1,2 °C
Network connections : RS485 0V, Line-A, Line-B (2x Twisted-pair shielded min.
0,5mm2, length max. 500m) for communication through
the ALFANET PC-Interface to the PC.
Front : Mat. Chrome polyester sticker
Dimensions : 90 x 106 x 58 mm (hwd)
Panel cut out : 46 x 106 mm (hw)
Operation temperature : -20/+50 °C
Storage temperature : -20/+60 °C
Operation RH : 10/+90 % RH non condensing
- Provided with memory protection during power failure.
- DIN-rail mounting
- Equipped with self test function and sensor failure detection.
- Special versions are available upon request.
2. Functional specifications.
2.1 Installation.
On the front of the ALFANET TEMPLOGGER 16x Pt1000 and on the connection diagram is
shown how the inputs, power supply and the RS485-network connection should be connected.
After the Controller is connected to the power supply, a self test will be done.
The Controller is adjustable through the ALFANET PC-INTERFACE on the PC.
It is possible to connect a maximum of sixteen ALFANET TEMPLOGGER 16x Pt1000s on the
network. This will make an total of 16 x 16 = 256 sensors.
These modules should have a unique network numbers. This can be adjusted below the
terminal cover by DIP-switches from address: 110 till 125.
2.2 Operation.
From each sensor the measured value is shown on the PC. The refresh rate is at least two time
per minute. When there are big temperature variations, the refresh rate will be higher. It is
possible to adjust a minimum and a maximum alarm for each sensor. If an alarm occurs, there
will be a warning on the pc and the alarm relay from the PC interface will be activated.
It is possible to adjust a time delay for each alarm. The adjusting is per 5 minutes till a maximum
of 300 minutes.
All measured values and alarms are stored in the log from the PC.

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 4 van 10
3. Control.
3.1 Controlling.
The Controller can only be controlled through the PC. See also the manual from the ALFANET
PC-INTERFACE.
3.2 Read out.
On the picture below is shown how the module looks like on the PC.
Inputs which gives strips, are disabled in the
parameters. A warning sign means a alarm
situation. There is no special alarm for sensor
errors. A short circuit sensor will always give a
minimum alarm and a broken sensor will always
give a maximum alarm. In case of sensor failures
the time delays will be ignored.
It is possible to give each sensor it’s own name.
This name will be used on the screen and into the
log. See the manual from the PC-software for
instructions about how to enter the names.
4. Viewing and changing the parameters.
Through the context menu
(= right mouse key) the
parameters can be viewed
and changed.

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 5 van 10
4.1 Parameter list.
Para-
Meter
Parameter description Range Standard
value
1
2
3
4
5
Sensor 1 present
Minimum alarm Sensor 1
Minimum alarm delay Sensor 1
Maximum alarm Sensor 1
Maximum alarm delay Sensor 1
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
6
7
8
9
10
Sensor 2 present
Minimum alarm Sensor 2
Minimum alarm delay Sensor 2
Maximum alarm Sensor 2
Maximum alarm delay Sensor 2
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
11
12
13
14
15
Sensor 3present
Minimum alarm Sensor 3
Minimum alarm delay Sensor 3
Maximum alarm Sensor 3
Maximum alarm delay Sensor 3
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
16
17
18
19
10
Sensor 4present
Minimum alarm Sensor 4
Minimum alarm delay Sensor 4
Maximum alarm Sensor 4
Maximum alarm delay Sensor 4
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
21
22
23
24
25
Sensor 5 present
Minimum alarm Sensor 5
Minimum alarm delay Sensor 5
Maximum alarm Sensor 5
Maximum alarm delay Sensor 5
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
26
27
28
29
30
Sensor 6 present
Minimum alarm Sensor 6
Minimum alarm delay Sensor 6
Maximum alarm Sensor 6
Maximum alarm delay Sensor 6
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
31
32
33
34
35
Sensor 7 present
Minimum alarm Sensor 7
Minimum alarm delay Sensor 7
Maximum alarm Sensor 7
Maximum alarm delay Sensor 7
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
36
37
38
39
40
Sensor 8 present
Minimum alarm Sensor 8
Minimum alarm delay Sensor 8
Maximum alarm Sensor 8
Maximum alarm delay Sensor 8
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
41
42
43
44
45
Sensor 9 present
Minimum alarm Sensor 9
Minimum alarm delay Sensor 9
Maximum alarm Sensor 9
Maximum alarm delay Sensor 9
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
46
47
48
49
50
Sensor 10 present
Minimum alarm Sensor 10
Minimum alarm delay Sensor 10
Maximum alarm Sensor 10
Maximum alarm delay Sensor 10
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 6 van 10
Para-
Meter
Parameter description Range Standard
value
51
52
53
54
55
Sensor 11 present
Minimum alarm Sensor 11
Minimum alarm delay Sensor 11
Maximum alarm Sensor 11
Maximum alarm delay Sensor 11
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
56
57
58
59
60
Sensor 12 present
Minimum alarm Sensor 12
Minimum alarm delay Sensor 12
Maximum alarm Sensor 12
Maximum alarm delay Sensor 12
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
61
62
63
64
65
Sensor 13 present
Minimum alarm Sensor 13
Minimum alarm delay Sensor 13
Maximum alarm Sensor 13
Maximum alarm delay Sensor 13
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
66
67
68
69
70
Sensor 14 present
Minimum alarm Sensor 14
Minimum alarm delay Sensor 14
Maximum alarm Sensor 14
Maximum alarm delay Sensor 14
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
71
72
73
74
75
Sensor 15 present
Minimum alarm Sensor 15
Minimum alarm delay Sensor 15
Maximum alarm Sensor 15
Maximum alarm delay Sensor 15
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
76
77
78
79
80
Sensor 16 present
Minimum alarm Sensor 16
Minimum alarm delay Sensor 16
Maximum alarm Sensor 16
Maximum alarm delay Sensor 16
0=No, 1=Yes
LLV .. ULV °C
0..300 minutes
LLV .. ULV °C
0..300 minutes
0
LLV °C
0
ULV °C
0
101
till
116
Sensor offset sensor 1
till
Sensor offset sensor 16
-10.0 .. 10.0 K
..
-10.0 .. 10.0 K
0.0 K
..
0.0 K
*) LLV = Lower Limit Value p.e.. -50 °C at the range -50..+50 °C
ULV = Upper Limit Value p.e.. +50 °C at the range -50..+50 °C

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 7 van 10
5. Front view.
040207
6. Dimensions.
970904

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 8 van 10
7. Connections.
040206

User manual Document nr. : 071867 Versie : V2.4
ALFANET TEMPLOGGER 16x Pt1000 Client : General Pagina : 9 van 10
042152
Table of contents
Other VDH Control Unit manuals