*Setting internal parameters.
By pushing the DOWN key for more then 10 seconds, you enter the ‘internal programming menu’. In
the left display the upper and lower segments are blinking. With the UP and DOWN keys the required
parameter can be selected (see parameter table).
If the required parameter is selected, the value can by read-out by pushing the SET key. By pushing
simultaneously the SET key and the UP or DOWN key the parameter value can be changed.
If no key is pushed for 20 seconds, the ALFA(NET) 801 will return to it’s normal operation and the
changes are saved.
*Parameters ALFA 801.
Para-
meter
Description Parameter Range Default
value
01
02
Pulse time
Pause time
0...999
0...999
10
50
03 Unit of parameter 01 and 02 0 = minutes,
1 = seconds
0
04 Start with pause after power failure 0 = no, 1 = yes 0
05 Contact-input mode
0 = Not active.
1 = Start with pulse-time at closing the input.
As long as the input is closed pulse will be
active.
2 = Start with pause-time at closing the input.
As long as the input is closed pause will be
active.
3 = At input impulse start pulse-time
4 = At input impulse start pause-time
0...4 0
90
95
96
97
98
99
Network number (only at ALFANET 801)
Software version
Production year
Production week
Serial number (x 1000)
Serial number (units)
1...250
-
00...99
1...52
0...250
0...999
1
-
-
-
-
-
Remark: In case that the timer-unit is set on minutes (P01= 0), the display shows the last minute of
the current rest time in seconds. To indicate this, the lower segment of the first digit is lit and
the other digits show the time in seconds.