INTRODUCTION
This Installation and Quick Help Guide contains the necessary information to connect a wireless modem
to a TLS-300, TLS-350, TLS4, or TLS-450PLUS console and obtain the tank information in the DataLink
program on a PC.
DESCRIPTION:
Kit Number
Description
General Contents and Comments
0845900-037
TLS-3XX Consoles Interface Kit
- XTend 900 MHZ
This TLS kit includes:
•Wireless modem with standard antenna
•Special 9-pin connector for modem
•Special 25-pin connector for console
•25-foot Ribbon cable for console to modem
connection
•Power supply for modem
•This manual
0845900-040
TLS-4XX Consoles Interface Kit
- XTend 900 MHZ
This TLS kit includes:
•Wireless modem with standard antenna
•9-pin connectors for modem and console
•25-foot ribbon cable for console to modem
connection
•Power supply for modem
•This manual
INDIVIDUAL MODEM UNIQUE ADDRESS - IMPORTANT
Each modem has a unique address assigned by Veeder-Root. This number is on the label on
the modem itself, and on the box. This number is your traceability from the TLS console to the
office software. The TLS connected modem number will be entered into the office software in
the TLS modem location on the DataLink configuration page.
TLS CONNECT KIT MODEM:

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 2 of 18
XTend 900 MHz, 1 Watt, Serial
Unique Address Assigned
By Veeder-Root
Example of Label on Side of Modem
FOR XTEND 900 MHz SERIAL MODEMS
TLS CONNECTED MODEM MOUNTING AND CONNECTION:
1. The DIP switches on the XTend modem should be set to: 1=ON 2=OFF 3=OFF 4=OFF
5=ON 6=ON
Label on side of modem

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 3 of 18
2. Screw the antenna into the modem and hand tighten.
3. Connect the serial connector to the modem and plug the cable into the connector.
4. Plug the power supply into a normal 110 volt outlet. The red light on the modem will be lit.
5. The modem can sit on or near the console. If the console will be located a long distance
from the office modem, the modem should be placed as high as possible. A high-gain
antenna (kit 0845900-033) may be needed for some applications.

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 4 of 18
TLS CONSOLE CONNECTION AND SETUP
For a TLS-300 console:
Use the Direct Connect location and connector shown:
For a TLS-350 Console:
For Serial communications, the console needs to have the RS-232 Serial Interface Module
(329362-001 in-console part or 847490-301 spare part) installed in the console.
Look on the bottom of the console for the 25-pin serial connector shown.
Look for this connector in
the bottom of the console

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 5 of 18
For a TLS4 Console:
Look on the bottom of the console for the 9-pin serial connectors shown.
For a TLS-450PLUS Console:
Look on the bottom of the console for an available 9-pin serial connector.
Look for these connectors in
the bottom of the console

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 6 of 18
Use the chart below to verify the configuration of the desired TLS-450PLUS serial connector:
NOTE: A RS-232 module is required for DataLink.
CONSOLE SET-UP
The unit will be set up by the installer for normal operation. The steps in this procedure are for
setting up the console for communication using the DataLink serial modem.
Security Code Enable/Disable
Security needs to be “Disable” for obtaining data via the DataLink modem. For TLS-3XX
Consoles place all DIP switches in the OPEN position as shown below:

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 7 of 18
TLS-300 Console

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 8 of 18
TLS-350 Console With CPU Board

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 9 of 18
TLS-4XX Consoles
From the Home Screen, navigate to Setup>System>Security and ensure Front Panel Security is
Disabled:
Serial Communications Protocol Setup
TLS-3XX Consoles
On the console keypad with Date and Time and “All Functions Normal” showing:

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 10 of 18
1. Push MODE button to SETUP MODE
2. Push FUNCTION Button to COMMUNICATIONS SETUP
3. Push STEP button to PORT SETTINGS
4. ENTER
COMM BOARD 2 (RS-232) (May be different Board Number but will be RS-232)
BAUD RATE 9600
a. If not 9600, then push the CHANGE KEY until 9600 and ENTER
STEP to PARITY
oIf not NONE, then push the CHANGE KEY until NONE and ENTER
STEP to STOP BIT
oIf not 1 STOP, then push the CHANGE KEY until 1 STOP and ENTER
STEP to DATA LENGTH
oIf not 8 DATA, then push the CHANGE KEY until 8 DATA and ENTER

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 11 of 18
STEP to CODE
oIf not DISABLED, then push the CHANGE KEY until DISABLED and ENTER.
STEP to CONTINUE to PORT SETTINGS
5. MODE, MODE back to Normal screen
TLS-4XX Consoles
From the Home Screen navigate to Setup>Communication>Serial Port screen:
Select the Serial Port connected to the DataLink modem then select:
•Configured = Enabled
•Label = Enter a name
•Baud Rate = 9600
•Data Bits = 8
•Parity = None

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 12 of 18
DATALINK SETUP FOR READNG A TLS CONSOLE
Click on Configuration Page>Settings tab page.
1. In the Modem drop down box select ‘MaxStream Wireless Modem’, then click Save.
Click Save
Select MaxStream
Wireless Modem

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 13 of 18
2. The Configuration Page>Settings tab page will update and display the TLS Modem field.
Also, Tank Page will appear in menu bar. In the TLS Modem field enter the number on
the side of the modem connected to the TLS Console, then click Save.
Click Save
Enter TLS Console
modem number

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 14 of 18
Click on Tank Page
Detail of Tank
Click on tank name to get details
Last time tank was
polled by DataLink

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 15 of 18
TROUBLESHOOTING
After launching DataLink you can verify that the modem is online by following the steps below.
1. Click on the up arrow in the lower right hand corner of the screen:
\
2. Locate the red EMR in the task bar popup and double left click on it:
3. If you are communicating you will see this confirmation screen.
XP Example
Win 10 example

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 16 of 18
4. If you are not communicating you will see this screen:

INSTALLATION and QUICK HELP
FOR TLS CONSOLE INTERFACE TO THE
VEEDER-ROOT EMR4 DATALINK
USING AN XTEND 900 MHZ WIRELESS MODEM
577014-353 Rev. A
Veeder - Root Page 18 of 18
WARRANTY OF MODEMS BY DIGI:
To view warranties for modems by Digi visit https://www.digi.com/legal/terms.
MODEM REGULATORY APPROVALS:
To view information on regulatory approvals for the Digi XTP9B-PKI-RA (or XT09-PKI-R) and XTP9B-
PKC-UA (or XT09-PKC-UA) modems refer to the latest version of the XTP9B-PKI-RA (or XT09-PKI-R)
and XTP9B-PKCUA (or XT09-PKC-UA) user guides and datasheets at https://www.digi.com.
Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to,
the implied warranties of merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential
damages in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this
publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No
part of this publication may be photocopied, reproduced, or translated to another language without the
prior written consent of Veeder-Root.
DAMAGE CLAIMS
1. Thoroughly examine all components and units as soon as they are received. If damaged, write a
complete and detailed description of the damage on the face of the freight bill. The carrier's agent must
verify the inspection and sign the description.
2. Immediately notify the delivering carrier of damage or loss. This notification may be given either in
person or by telephone. Written confirmation must be mailed within 48 hours. Railroads and motor
carriers are reluctant to make adjustments for damaged merchandise unless inspected and reported
promptly.
3. Risk of loss, or damage to merchandise remains with the buyer. It is the buyer's responsibility to file a
claim with the carrier involved.
RETURN SHIPPING
For the parts return procedure, please follow the appropriate instructions in the "General Returned
Goods Policy" and "Parts Return" section of the Veeder-Root EMR4 price list.
©Veeder-Root 2018. All rights reserved.
This manual suits for next models