Veeder-Root DPLLD User manual

DPLLD
Site Prep and Installation Guide
Manual No: 577013-933 l Revision: G

Notice
Veeder-Root makes no warranty of any kind with regard to this publication, including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose.
Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages
in connection with the furnishing, performance, or use of this publication.
Veeder-Root reserves the right to change system options or features, or the information contained in this publication.
This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this publication
may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-Root.
Contact Red Jacket Technical Support for additional troubleshooting information at 800-323-1799.
DAMAGE GOODS/LOST EQUIPMENT
Thoroughly examine all components and units as soon as they are received. If any cartons are damaged or missing, write a
complete and detailed description of the damage or shortage on the face of the freight bill. The carrier's agent must verify the
inspection and sign the description. Refuse only the damaged product, not the entire shipment.
VR must be notified of any damages and/or shortages within 30 days of receipt of the shipment, as stated in our Terms and
Conditions.
VEEDER-ROOT’S PREFERRED CARRIER
1. Fax Bill of Lading to V/R Customer Service at 800-234-5350.
2. Call V/R Customer Service at 800-873-3313 with the specific part numbers and quantities that were received damaged or
lost.
3. VR will file the claim with the carrier and replace the damaged/missing product at no charge to the customer. Customer
Service will work with production facility to have the replacement product shipped as soon as possible.
CUSTOMER’S PREFERRED CARRIER
1. Customer files claim with carrier.
2. Customer may submit a replacement purchase order. Customer Service will work with production facility to have the
replacement product shipped as soon as possible.
3. If “lost” equipment is delivered at a later date and is not needed, VR will allow a Return to Stock without a restocking fee.
4. VR will NOT be responsible for any compensation when a customer chooses their own carrier.
RETURN SHIPPING
For the parts return procedure, please follow the instructions in the “General Returned Goods Policy” pages of the “Policies and
Literature” section of the Veeder-Root North American Red Jacket Mechanical Products Price Book. Veeder-Root will not accept
any return product without a Return Goods Authorization (RGA) number clearly printed on the outside of the package.
RESPONSIBILITIES OF THE INSTALLER AND STATION OWNER
This installation, operation and service instruction manual shall be left with the owner of the service station at which this equipment
is installed. Retain these instructions for future use and provide them to persons servicing or removing this equipment.
ã Veeder-Root 2021. All rights reserved.

Table of Contents
iii
Introduction
Contractor Certification Requirements ..............................................................................1
Product Marking Information .............................................................................................1
Related Documents..................................................................................................1
Safety Symbols .................................................................................................................3
Safety Warnings ...............................................................................................................4
Reference Manuals ..................................................................................................4
Before You Begin ..............................................................................................................5
Warning Tags ...................................................................................................................5
Site Considerations
Manholes ..........................................................................................................................6
Unused Piping Runs .........................................................................................................6
Existing Check Valves ......................................................................................................6
Manifolded Product Lines .................................................................................................6
DPLLD Equipment Overview
DPLLD Components .........................................................................................................7
DPLLD Installation Example .............................................................................................7
DPLLD Transducer Installation
Red Jacket Standard Pumps (DPLLD w/SwiftCheck) .......................................................8
Red Jacket Standard Pumps (DPLLD) ...........................................................................14
The Red Jacket Pump ....................................................................................................15
Red Jacket Maxxum Big-Flo ...........................................................................................16
FE Petro Pumps .............................................................................................................17
FE Petro High Capacity Pumps..............................................................................19
FE Petro Variable Speed Pump System Modifications ..........................................19
DPLLD Field Wiring
DPLLD Transducers .......................................................................................................21
DPLLD Wiring Connections In the Console
DPLLD Transducer Wiring Connections .........................................................................23
Pump Wiring Connections ..............................................................................................23
DPLLD Equipment Checkout Steps
1. Vent The Line .............................................................................................................32
2. Reset FE Relief Pressure ...........................................................................................32
Procedure For RJ Standard pump with PLLD (w/o SwiftCheck) ............................32
Procedure For Maxxum pump with PLLD And Pressurstat ....................................32
3. Determine DPLLD Transducer Pressure Offset ..........................................................33
4. Purge Air from the Line ...............................................................................................33
5. Enable the Line for Dispensing ...................................................................................34

Table of Contents
iv
Figures
Figure 1. Warning tag ............................................................................................5
Figure 2. Example DPLLD Equipment Installation .................................................7
Figure 3. Sealing Surface For SwiftCheck Valve’s External O-Ring ......................9
Figure 4. DPLLD Transducer Installation .............................................................10
Figure 5. DPLLD Install W/Healy Mini-Jet System ..............................................10
Figure 6. Modifying The Functional Element In Red Jacket Pumps ....................11
Figure 7. Functional Element Screw Tightening Sequence .................................12
Figure 8. Functional Element Screw Tightening Sequence .................................12
Figure 9. Functional Element O-Rings .................................................................12
Figure 10. Installing Check Valve And Spring In Packer .......................................13
Figure 11. DPLLD Installation ................................................................................14
Figure 12. Locating Discharge Port Plug For Line Leak Transducer .....................15
Figure 13. Example DPLLD Installation In A Red Jacket Maxxum Big-Flo Pump.....16
Figure 14. Location of DPLLD Transducer And Model ‘R’ Precision
Check Valve In FE Petro Pump ............................................................18
Figure 15. Identifying A FE Petro ‘R’ Style Precision Check Valve ........................18
Figure 16. Dip Switch SW2 And Rotary Switch Locations In The
FE-Petro IST-VFC Unit .........................................................................20
Figure 17. Field Connections Of DPLLD Transducer ............................................21
Figure 18. Epoxy Sealing Pressure Transducer Field Connections ......................22
Figure 19. DPLLD Transducer Wiring To USM Module .........................................23
Figure 20. DPLLD Pump Control Diagram For Red Jacket Relay Control Box.........24
Figure 21. Red Jacket Maxxum Big-Flo Single-Phase Wiring ...............................25
Figure 22. Red Jacket Maxxum Big-Flo 3-Phase Wiring .......................................26
Figure 23. DPLLD Pump Control Diagram For
Non-Red Jacket Relay Control Box ......................................................27
Figure 24. Wiring Diagram - Manifolded Lines DPLLD - Multiple Tanks ...............28
Figure 25. DPLLD Pump Control Diagram For Gilbarco Dispenser Isolation Box .29
Figure 26. Manifolded Product Lines - Dual FE Petro IST-VFC Controllers ..........30
Figure 27. Manifolded Product Lines - Dual Red Jacket IQ Controllers ................31
Figure 28. Functional Element (Red Jacket Standard Pump Shown) ....................33
Tables
Table 1. FE-IST-VFC Product Type Dip Switch (SW2) Settings ..........................19
Table 2. FE-IST-VFC Rotary Switch Positions W/V1.1/1.2 Software ...................20

1
Introduction
This manual contains instructions for installing the components for Veeder-Root Digital Pressurized Line Leak
Detection (DPLLD). The DPLLD equipment performs 3.0 gph line leak tests following each dispense. Depending
on the software enhancement module installed, the DPLLD equipment will also allow, with certain pump types, 0.2
and/or 0.1 gph line tests at full pump pressure. The DPLLD equipment executes leak tests automatically to
eliminate the need for separate annual line leak testing.
1. The DPLLD, Digital Pressure Line Leak Detector, Form Number 8590, is Intrinsically Safe when
installed according to Control Drawing Number 331940-008.
2. The TLS-450PLUS/TLS-450 console/DPLLD sensors are not supported by the Red Jacket Variable
Speed Flow Controller (VSFC). The VSFC is designed for use with PLLD sensors/TLS-350
consoles only!
3. You must consult the Veeder-Root Line Leak Detection Systems Application Guide (P/N 577013-
465) for all information relating to DPLLD applicable pipe types, equipment requirements,
installation kits, and pump compatibilities.
4. A Sump Sensor is recommended for sites with line leak in the event the pump develops a leak.
Line leak will only detect a leak in the line, not in the pump.
Contractor Certification Requirements
Veeder-Root requires the following minimum training certifications for contractors who will install and setup the
equipment discussed in this manual:
Service Technician Certification (Previously known as Level 2/3): Contractors holding valid Technician
Certifications are approved to perform installation checkout, startup, programming and operations training, system
tests, troubleshooting and servicing for all Veeder-Root Series Tank Monitoring Systems, including Line Leak
Detection.
TLS-4xx Technician Certification: Contractors holding valid TLS-450 Technician Certifications are approved to
perform installation checkout, startup, programming and operations training, troubleshooting and servicing for all
Veeder-Root TLS-450 Series Tank Monitoring Systems, including Line Leak Detection and associated accessories.
All service personal on site must comply with all recommended safety practices identified by OSHA and your
employer.
Review and comply with all the safety warnings in the manuals listed in this document above and any other
Federal, State or Local requirements.
Warranty Registrations may only be submitted by selected Distributors.
Product Marking Information
RELATED DOCUMENTS
Documents Required to Install Equipment
This intrinsically safe apparatus is only for use as part of a Veeder-Root Automatic Tank Gauging System (ATG
Console with probes and sensors). To install intrinsically safe apparatus, use the specific control drawing that
appears on the nameplate of the applicable associated apparatus (ATG Console):
Associated Apparatus UL/cUL Control Drawing Number
TLS-450PLUS&TLS-450/8600 331940-008

Introduction Product Marking Information
2
The control drawings contain information related to the correct installation of the overall intrinsically Safe System.
This includes information such as maximum number of apparatus, specific apparatus allowed in the system,
maximum cable lengths, references to codes, proper grounding and so on. Control drawings can be found on the
accompanying Compact Disk (TECH DOCS CD) or on the INTERNET at veeder.com under SUPPORT; VR
TECHNICAL DOCUMENTS; DRAWINGS.
Product Label Contents

Introduction Safety Symbols
3
Safety Symbols
The following safety symbols may be used throughout this manual to alert you to important safety hazards and
precautions.
EXPLOSIVE
Fuels and their vapors are extremely explo-
sive if ignited.
FLAMMABLE
Fuels and their vapors are extremely flammable.
ELECTRICITY
High voltage exists in, and is supplied to,
the device. A potential shock hazard exists.
TURN POWER OFF
Live power to a device creates a potential
shock hazard. Turn Off power to the device and
associated accessories when servicing the unit.
WEAR EYE PROTECTION
Fuel spray from residual pressure in the
lines can cause serious eye injuries.
Always wear eye protection.
INJURY
Careless or improper handling of materials can
result in bodily injury.
GLOVES
Wear gloves to protect hands from irrita-
tion or injury.
APPROVED CONTAINERSS
Use nonbreakable, clearly marked containers,
suitable for collecting and transporting hazard-
ous fuels during service.
WARNING indicates a hazardous situa-
tion which, if not avoided, could result in
death or serious injury.
CAUTION indicates a hazardous situation
which, if not avoided, could result in minor or
moderate injury.
USE SAFETY BARRICADES
Always use safety cones or barricades,
safety tape, and your vehicle to block the
work area.
NOTICE is used to address practices not related
to physical injury.
READ ALL RELATED MANUALS
Knowledge of all related procedures
before you begin work is important. Read
and understand all manuals thoroughly. If
you do not understand a procedure, ask
someone who does.

Introduction Safety Warnings
4
Safety Warnings
To protect yourself and your equipment, observe the following warnings and important information:
Failure to install this product in accordance with its instructions and warnings will result in
voiding of all warranties with this product.
REFERENCE MANUALS
577013-465 Line Leak Application Guide
577014-073 TLS-450PLUS Site Prep and Installation Manual
577013-879 TLS-450 Console Site Prep and Installation Manual
WARNING
This product is to be installed in systems operating near locations where
highly combustible fuels or vapors may be present.
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY
PRECAUTIONS COULD CAUSE DAMAGE TO PROPERTY, ENVIRONMENT,
RESULTING IN SERIOUS INJURY OR DEATH.
1. Read and follow all instructions in this manual, including all safety
warnings to protect yourself and others from serious injury, explosion, or
electrical shock.
2. Comply with all applicable codes including: the National Electrical Code;
federal, state, and local codes; and other applicable safety codes.
3. To protect yourself and others from being struck by vehicles, block off
your work area during installation or service.
4. Do not alter or modify any component or substitute components in this
kit.
5. Warning! Substitution of components may impair intrinsic safety.
6. Field wiring to the DPLLD Transducer must not share a conduit with any
non-intrinsically safe device’s wiring.
7. To prevent ignition of flammable or combustible atmospheres, turn off,
tag and lockout power to console and pumps before servicing.
8. Before installing or taking the transducer into a hazardous area, earth the
unit in a safe area to remove any static charge. Then immediately
transport the unit to the installation site. Do not rub or clean the unit prior
to installation. Cleaning is not required under normal service conditions.
Do not rub or clean the unit after installation. If the unit is not fixed to a
known earth point when installed, ensure that a separate earth
connection is made to prevent the potential of a static discharge. When
fitting or removing the unit, use of anti-static footwear or clothing is
required.
9. Materials used in the construction of this device do not contain, by mass,
more than 10% in total of aluminum, magnesium, zirconium and titanium
or 7.5% in total of magnesium, titanium and zirconium.

Introduction Before You Begin
5
Before You Begin
1. Ensure that the submersible turbine pump (STP) is properly grounded as per the manufacturer’s instructions.
2. A shutoff valve installed between the DPLLD transducer and the product pipeline is recommended. Although
not required for the DPLLD equipment to work, the valve will aid in troubleshooting the system and in reducing
any product spillage when performing service work in the sump.
3. The SwiftCheck valve requires a 3” hex socket (or wrench) for tightening it in the pump’s leak detector port.
The non-vented SwiftCheck valve requires a 1-1/2” hex socket (or wrench) for tightening it in the pump’s leak
detector port.
4. If you are installing DPLLD into a Red Jacket Standard STP you will need a new Functional Element.
Warning Tags
Turn off, tag (using the warning tags provided), and lockout power to the console and
submersible pumps while installing the DPLLD equipment. This will prevent either a
dispense attempt or the DPLLD equipment from automatically starting up the pump.
Warning tags [Figure 1] are provided with the DPLLD equipment. For your safety and the safety of others who may
service dispensers, submersible pumps, or DPLLD equipment, you must attach a tag to each of the following
devices where it can clearly be seen by a service person performing work on the system:
• Console
• Submersible pump
• Dispenser filter
Figure 1. Warning tag

6
Site Considerations
Manholes
When using a SwiftCheck Valve, the manhole must provide at least 8 inches of clearance above the pump head to
install the DPLLD components.
Unused Piping Runs
Where piping runs have been installed for future use, but are connected to the active piping system, isolate the
inactive lines from the active lines using a shutoff valve. Failure to do so may harm system performance.
Existing Check Valves
You must ensure that there are no existing check valves already installed in the pipeline. The presence of any check
valve (other than the one used with the DPLLD equipment) can prevent the DPLLD equipment from detecting line
leaks in the area of pipeline downstream from the check valve.
Manifolded Product Lines
Follow these guidelines as you install a DPLLD equipment into multiple manifolded tanks:
• Dielectric unions and flexible piping elements should be used as required by federal, state, and local
requirements for the specific piping application. Location of unions may vary with configuration.
• An I/O Module in the console is required to control the pump on the higher-numbered tank and pump control
output for the primary tank, and the “Pump In” (Dispenser ON) signal for the set.
• A DPLLD transducer is only required in the primary pump.
• Remove any other check valve or leak detect device in the line that is not shown.
• Refer to the Line Leak Application Guide for check valve requirements.

7
DPLLD Equipment Overview
DPLLD Components
• TLS-450/TLS-450PLUS console with DPLLD feature.
• DPLLD pressure transducer (one for each product line monitored) - vented or non-vented check valves may be
required depending on pump type and application
• USM Module to monitor DPLLD transducers
• I/O Module to control site primary and secondary STPs
DPLLD Installation Example
Figure 2 shows an example DPLLD installation for a single tank and a manifolded tank set having Red Jacket
Standard pumps.
Figure 2. Example DPLLD Equipment Installation

8
DPLLD Transducer Installation
This section discusses DPLLD transducer installation for the following DPLLD approved pumps:
• Red Jacket Standard pumps - DPLLD transducer/SwiftCheck valve (page 8)
• Red Jacket Standard pumps - DPLLD transducer (page 14)
• The Red Jacket (page 15)
• Red Jacket Maxxum Big-Flo (page 16)
• FE-Petro (page 17)
Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
Use this installation procedure to install a DPLLD transducer with a SwiftCheck valve in a Red Jacket Standard
pump.
Disconnect, lock out, and tag all AC power to the TLS console, dispens-
ers and submersible pumps.
When servicing equipment, use non-sparking tools and use caution when removing or in-
stalling equipment to avoid generating a spark.
1. If a ball valve is installed down line from the pump, close it.
2. Back out the electrical connector disconnect bolt.
3. Swing electrical connector aside.
4. To relieve pressure, back out the Functional Element screw or remove the 2 – ½-13 Hex Screws on the
Packer-To-Manifold flange interface and rock the Packer/Extractable section of the pump to allow excess
pressure to flow into the tank.
5. Do one of the following:
a. If the submersible turbine pump is equipped with a mechanical LLD, remove the mechanical unit and any
related tubing and fittings, and install ¼” NPT pipe plugs into the respective “Line Test” and Tank Test”
ports on the packer. Be certain to apply an adequate amount of fresh, UL “Classified for Petroleum”, non-
setting thread sealant on the ¼” NPT pipe plugs and then torque each plug at 14-24 ft-lbs (19.4-29 Nm).
b. If the submersible turbine pump is not equipped with a mechanical LLD, remove the 2-inch mechanical
LLD port plug.
6. Ensure that the sealing surface for the SwiftCheck valve’s external o-ring is smooth and free from corrosion,
pitting, and any material build-up [Figure 3].

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
9
Failure to ensure a smooth seal surface can result in false line leak alarms.
Figure 3. Sealing Surface For SwiftCheck Valve’s External O-Ring
7. Lubricate the external o-ring on the SwiftCheck valve using mineral oil or other suitable lubricant.
8. If there is a Stage II vapor recovery device installed, go to Step 7. If there is no Stage II vapor recovery, install
the SwiftCheck valve [Figure 4] in the mechanical LLD pump port. Thread the DPLLD transducer into the
SwiftCheck Valve.
Do not overtighten the SwiftCheck valve when installing it into the pump. Over
tightening the valve can cause a flow restriction in the line!
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
10
Figure 4. DPLLD Transducer Installation
9. If there is a Stage II vapor recovery device installed in the pressurized piping you must install the SwiftCheck
valve into a Red Jacket leak detector fitting (P/N 038-072) as shown in Figure 5 instead of in the pump’s leak
detector port. Because the DPLLD transducer must be installed downstream from these devices, a monitored
containment sump is required.
There must not be a check valve installed between the SwiftCheck valve and the pump
for DPLLD to function properly.
Ensure that the Healy pump is wired according to the manufacturer’s instructions and utilizes isolation relays.
Lubricate the external o-ring on the SwiftCheck valve using mineral oil or other suitable lubricant and thread
the valve into the Red Jacket fitting.
Figure 5. DPLLD Install W/Healy Mini-Jet System (Required Dielectric Union And Shutoff Valve Not Shown)

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
11
10. Thread the DPLLD transducer into the SwiftCheck valve (ref. Figure 4 or Figure 5 as appropriate).
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.
11. Get a watertight cord grip from the transducer installation kit and coat its 1/2” NPT threaded end with UL-
Classified, nontoxic pipe sealant suitable for the fuel involved. Screw the cord grip into one of the openings in
the weatherproof junction box. Feed the end of the DPLLD transducer cable through the cord grip and then
tighten the nut to ensure a watertight seal. Connect and seal the pressure transducer wires to the wires from
the TLS console as described in ‘Epoxy Sealing DPLLD Transducer Field Wiring Connections’ on page 21.
12. The DPLLD Swiftcheck valve eliminates the need for the pumps Functional Element relief valve function.
Remove the existing Functional Element from the packer and discard. Obtain a new Pump Service Kit (P/N
344-001-5) which includes the new Functional Element, Check Valve and Seals. Using the new Functional
Element, remove the 6 – ¼-28 Fillister Head Screws and set aside. Remove the top assembly of the
Functional Element from its body by pulling straight upward from to separate the top from the body. Gently
fold back/separate the diaphragm from the top and remove the poppet and the spring. Discard the spring but
reinstall the poppet (see Figure 6).
Figure 6. Modifying The Functional Element In Red Jacket Pumps

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
12
13. Lubricate the o-ring on the Lockdown Screw, using petroleum jelly (see Figure 7).
Figure 7. Functional Element Screw Tightening Sequence
14. Return the Diaphragm to the normal position on the top of the Functional Element. Install the top of the
Functional Element, Poppet, and Diaphragm assembly onto the body of the Functional Element using the 6 –
¼-28 Fillister Head Screws and torque these fasteners, sequentially as shown in Figure 8 to 40-65 in-lbs.
Figure 8. Functional Element Screw Tightening Sequence
15. Be certain all mating surfaces are clean on the body of the Functional Element and the Packer. Lubricate the
three new functional element O-rings from the kit with petroleum jelly. Install the 2.193” O.D. and 0.63” O.D.
O-rings in the bottom of the functional element as shown in Figure 9. Install the new 0.379” O.D. O-ring in the
groove around the packer’s diaphragm vent port.
Figure 9. Functional Element O-Rings
16. Position the new check valve in the packer in same position as was the old check valve (see Figure 10).
Position the new check valve spring on top of the new check valve with the larger diameter end of the spring

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD w/SwiftCheck)
13
facing up. Clean the packer facing prior to installing new Functional Element.
Figure 10. Installing Check Valve And Spring In Packer
17. Carefully set the new functional element assembly in place, then install the two new 3/8-inch securing bolts
from the kit and torque to 20 - 35 ft-lb (27 - 50 N•m).
18. If siphon tubing is installed, remove the siphon plug from the new functional element. Connect the siphon
tubing fitting to the siphon port using fresh, UL classified for petroleum, non-setting thread sealant.
19. If applicable, open ball valve down line from the pump. Upon start-up of the pump, check for leaks to ensure
that the system is leak free.
WARNING
Failure to properly reseal the Functional Element may result in product
leakage, which could create serious environmental and safety hazards.
Fire, explosion, or ground contamination could occur.
Carefully reassemble and reseal the Functional Element, following the
procedures described in this manual.

DPLLD Transducer Installation Red Jacket Standard Pumps (DPLLD)
14
Red Jacket Standard Pumps (DPLLD)
Use this installation procedure to install a DPLLD transducer in a Red Jacket Standard pump that has a Functional
Element that will be used for leak detection. NOTE: This installation method is approved for 3.0 gph testing only
and cannot be used if there is a Stage II vapor recovery device installed in the pressurized piping.
Disconnect, lock out, and tag all AC power to the TLS console, dispens-
ers and submersible pumps.
When servicing equipment, use non-sparking tools and use caution when removing or
installing equipment to avoid generating a spark.
1. If a ball valve is installed down line from the pump, close it.
2. Do one of the following:
a. If the submersible turbine pump is equipped with a mechanical LLD, remove the mechanical unit and any
related tubing and fittings, and install ¼” NPT pipe plugs into the respective “Line Test” and Tank Test”
ports on the packer. Be certain to apply an adequate amount of fresh, UL “Classified for Petroleum”, non-
setting thread sealant on the ¼” NPT pipe plugs and then torque each plug at 14-24 ft-lbs (19.4-29 Nm).,
or
b. If the submersible turbine pump is not equipped with a mechanical LLD, remove the 2-inch mechanical
LLD port plug.
3. Thread the DPLLD transducer into the LLD port (Figure 11).
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.
Figure 11. DPLLD Installation
4. Get a watertight cord grip from the transducer installation kit and coat its 1/2” NPT threaded end with UL-
Classified, nontoxic pipe sealant suitable for the fuel involved. Screw the cord grip into one of the openings in
the weatherproof junction box. Feed the end of the DPLLD transducer cable through the cord grip and then

DPLLD Transducer Installation The Red Jacket Pump
15
tighten the nut to ensure a watertight seal. Connect and seal the pressure transducer wires to the wires from
the TLS console as described in ‘Epoxy Sealing DPLLD Transducer Field Wiring Connections’ on page 21.
5. If applicable, open ball valve down line from the pump. Upon start-up of the pump, check for leaks to ensure
that the system is leak free.
The Red Jacket Pump
The DPLLD transducer mounts directly into the line leak detector pump port. It eliminates the need to break
product lines for installation and service.
Since the DPLLD transducer replaces the existing mechanical device, it is suitable in applications where there is
no sump.
Disconnect, lock out, and tag all AC power to the TLS console, dispens-
ers and submersible pumps.
When servicing equipment, use non-sparking tools and use caution when removing or
installing equipment to avoid generating a spark.
1. If a ball valve is installed down line from the pump, close it.
2. If the pump does not have a Stage II vapor recovery device installed in the pressurized piping, remove the 2’’
NPT plug from line leak detector port. Install the DPLLD transducer into the 2’’ NPT port (see Figure 12).
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.
Figure 12. Locating Discharge Port Plug For Line Leak Transducer
3. If the pump does have a Stage II vapor recovery device installed in the pressurized piping, lubricate the
external o-ring on the SwiftCheck valve using mineral oil or other suitable lubricant and thread the valve into
the Red Jacket leak detector fitting (P/N 038-072) as shown in Figure 5 on page 10 instead of in the pump’s
leak detector port. Next thread the DPLLD transducer into the 038-072 fitting.
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.

DPLLD Transducer Installation Red Jacket Maxxum Big-Flo
16
Because the DPLLD transducer must be installed downstream from these devices, a monitored containment
sump is required.
There must not be a check valve installed between the SwiftCheck valve and the pump
for DPLLD to function properly.
Ensure that the Healy pump is wired according to the manufacturer’s instructions and utilizes isolation relays.
4. Get a watertight cord grip from the transducer installation kit and coat its 1/2” NPT threaded end with UL-
Classified, nontoxic pipe sealant suitable for the fuel involved. Screw the cord grip into one of the openings in
the weatherproof junction box. Feed the end of the DPLLD transducer cable through the cord grip and then
tighten the nut to ensure a watertight seal. Connect and seal the pressure transducer wires to the wires from
the TLS console as described in ‘Epoxy Sealing DPLLD Transducer Field Wiring Connections’ on page 21.
5. If applicable, open ball valve down line from the pump. Upon start-up of the pump, check for leaks to ensure
that the system is leak free.
Red Jacket Maxxum Big-Flo
Disconnect, lock out, and tag all AC power to the TLS console, dispens-
ers and submersible pumps.
When servicing equipment, use non-sparking tools and use caution when removing or
installing equipment to avoid generating a spark.
1. If a ball valve is installed down line from the pump, close it.
2. If any in-line check valves or Big-Flo Diaphragm Valve are installed in the line, they must be removed.
3. Remove the cap from the 2-inch Transducer port next to the 3-inch discharge port. Thread the DPLLD
transducer into the transducer port (see Figure 13).
Seal the NPT threads only with a UL-Classified, nontoxic pipe sealant suitable for the
fuel involved (for high-alcohol fuel blend applications, Loctite 564 is recommended).
Apply sealant in a manner that prevents it from entering and contaminating hydraulic
cavities.
Figure 13. Example DPLLD Installation In A Red Jacket Maxxum Big-Flo Pump
4. Get a watertight cord grip from the transducer installation kit and coat its 1/2” NPT threaded end with UL-
Classified, nontoxic pipe sealant suitable for the fuel involved. Screw the cord grip into one of the openings in
the weatherproof junction box. Feed the end of the DPLLD transducer cable through the cord grip and then
Other manuals for DPLLD
1
Table of contents
Other Veeder-Root Security Sensor manuals