Veetsan VDU30 User manual

DOC. NO. 5956.6K6.00 P. 2 / 28
INDEX
1 KEYBOARDS Pag. 3
1.1 UNDERCOUNTER Style Pag. 3
1.1 UNDERCOUNTER Style Pag. 3
2 MANUAL ACTIVATION OF DETERGENT AND RINSE AID DISPENSERS Pag. 4
2.1 Detergent Dispenser Activation Pag. 4
2.2 Rinse Aid Dispenser Activation Pag. 4
3 RINSE PUMP MANUAL ACTIVATION Pag. 4
4 DETERGENT AND RINSE AID DOSAGE Pag. 4
4.1 GEn General Parameters Pag. 4
5COUNTERS Pag. 6
5.1 Cnt Counters Pag. 7
6 TEMPERATURE SETTING Pag. 8
6.1 FAC Factory Parameters Pag. 8
7 CYCLE SETTING Pag. 10
7.1 CYCLE DIAGRAM Pag. 11
7.2 CY1 Cycle 1 Parameters Pag. 12
7.3 CY2 Cycle 2 Parameters Pag. 12
7.4 drn Drain/Cleaning Cycle Parameters Pag. 12
7.4 drn Drain/Cleaning Cycle Parameters Pag. 12
8 OTHER PARAMETERS Pag. 13
8.1 dPA Dishwashing Parameters Pag. 13
8.2 ron Read Only Parameters Pag. 14
8.3 HCP Communication and HACCP Parameters Pag. 14
8.4 CFG Configuration Parameters Pag. 15
8.5 dbG Parameters for automatic hood type dishwashers Pag. 16
9 SPECIAL FEATURES Pag. 17
9.1 DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION Pag. 17
9.1 DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION Pag. 17
9.1 DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION Pag. 17
9.2 DISHWASHERS WITH WASH TANK WATER CHANGE FREQUENCY CONTROL Pag. 17
9.2 DISHWASHERS WITH WASH TANK WATER CHANGE FREQUENCY CONTROL Pag. 17
9.2 DISHWASHERS WITH WASH TANK WATER CHANGE FREQUENCY CONTROL Pag. 17
9.3 PERISTALTIC TUBE FITTING AND REPLACEMENT INSTRUCTIONS Pag. 17
10 MAIN BOARD CONFIGURATION Pag. 20
10.1 CODE -> Prog. TABLE Pag. 20
10.2 PROGRAMMING SHEETS Pag. 21
11 DEFAULT VALUES Pag. 22
12 USER INTERFACE AND MAIN BOARD CONNECTORS Pag. 23
12.1 Main malfunctions not due to the main board Pag. 23
12.2 CONNECTORS LAYOUT Pag. 23
14 ALARM MESSAGES AND TROUBLESHOOTING Pag. 24
14.1 ALARMS THAT STOP THE DISHWASHER Pag. 24
14.2 ALARMS THAT DON'T STOP THE DISHWASHER Pag. 25
In the case of a shorted probe error (C 5, C 7 e C11), the displayed temperature
is 210°F. Pag. 26
15 LIST OF PARAMETERS FOR SUBSEQUENT VERSIONS Pag. 27
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 3 / 28
1 KEYBOARDS
1.1 UNDERCOUNTER Style
SETTING MODES:
To enter into one setting mode (Figure 4), (Figure 5) the appliance should be in stand-by: switch on the appli-
ance, no cycles selected. Is useful keep door open to avoid start cycle in case of not simultaneously pressure
of the two keys.
Fig. 1 Detergent dispenser Manual
Activation
Fig. 2 Rinse Aid Dispenser Manual
Activation
Fig. 3 Rinse Pump Manual
Activation (used to EMPTY BOILER)
Fig. 4 Enter into General
Parameters (Hold down buttons for
at least five seconds).
Fig. 5 Enter into Factory
Parameters (Hold down buttons for
at least five seconds).
Fig. 6 Next Parameter Family OR
Increase Parameter Value (in setting
mode only)
Fig. 7 Decrease Parameter Value
(In setting mode only)
Fig. 8 Confirm Value and go to next
Parameter (in setting mode only).
TANK
BOILER
dEt
12 3
TANK
BOILER
rAi
123
TANK
BOILER
---
123
TANK
BOILER
GEn
123
TANK
BOILER
FAC
123
TANK
BOILER
888
123
TANK
BOILER
888
123
TANK
BOILER
888
123
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 4 / 28
2 MANUAL ACTIVATION OF DETERGENT AND RINSE AID DISPENSERS
When replacing detergents may be necessary activate the dispensers to fill hoses.
2.1 Detergent Dispenser Activation
2.2 Rinse Aid Dispenser Activation
3 RINSE PUMP MANUAL ACTIVATION
Use this function to empty the boiler (if the dishwasher is not to be used for a long time, for maintenance oper-
ation: ex. before replacing main board).
4 DETERGENT AND RINSE AID DOSAGE
In this paragraph is explained how to set the working time for the detergent and rinse aid dispensers.
For each dispenser there are two parameters: the initial time and the time during cycle execution.
4.1 General Parameters
How change the duration:
• Switch OFF and switch ON the dishwasher;
• Enter into the USER SETTING mode by pressing and hold down ON/OFF and BUTTON_1 keys for at least five sec-
onds the display shows (Figure 9);
Switch on the dishwasher.
Press and hold down BUTTON_2 and
BUTTON_3 keys, after two 'beep' the
detergent dispenser starts work for 20
sec.
Switch on the dishwasher.
Press and hold down BUTTON_1 and
BUTTON_3 keys, after two 'beep' the
rinse aid dispenser starts work for 40
sec.
Switch on the dishwasher.
Close the door and press and hold
down DRAIN and BUTTON_3 keys. A
buzzer signal indicates the rinse pump
activation and the display shows three
blinking lines. Three beeps indicate
the cycle end.
TANK
BOILER
dEt
12 3
TANK
BOILER
rAi
123
TANK
BOILER
---
123
Sym. Parameter Description Unit Min Max Factory Default
Initial Detergent Dosage (during filling tank) [s] 0 240 90
Initial Rinse Aid Dosage (starts when tank filled) [s] 0 180 10
Detergent Dosage During Cycle Execution (during wash
phase)
[s] 0 182 (*) 8
Rinse Aid Dosage During Cycle Execution (when refill-
ing boiler)
[s] 0 62 (*) 4
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 5 / 28
• Press BUTTON_3. The display shows alternatively the symbol and the duration in seconds (Figure 10) and
(Figure 11);
• Use BUTTON_1 key to decrease the duration and BUTTON_2 key to increase (Figure 11);
• After settled the duration press BUTTON_3 key to store value. The display shows the next parameter (Figure 12) and
the corresponding value (Figure 13);
• In the same way is possible to change the other duration; when finished switch OFF and switch ON.
(*) Note for external dispensers:
•if the detergent dispenser works when WASHING PUMP is being activated; at the
same time voltage is supplied between connectors L17–L19(main terminal box);
•if the detergent dispenser works when LOADING EV is being activated to re-fill boiler
level; at the same time voltage is supplied between connectors L17–L19(main ter-
minal box);
•if the rinse aid dispenser works when LOADING EV is being activated to re-fill boiler
level; at the same time voltage is supplied between connectors L18–L19(main ter-
minal box);
•if the rinse aid dispenser works when WASHING PUMP is being activated; at the
same time voltage is supplied between connectors L18–L19(main terminal box);
- For electrical connections refer to electric diagram -
Fig. 9 Enter into User Mode (press for 5 sec).
Fig. 10 Initial detergent
dosage.
Fig. 11 Change duration.
(Tank LED indicates default).
Fig. 12 Initial rinse aid
dosage
Fig. 13 Change duration
Fig. 14 Cycle detergent
dosage.
Fig. 15 Change time
activation (Tank LED
indicates default)
Fig. 16 Cycle rinse aid
dosage.
Fig. 17 Change time
activation.
TANK
BOILER
GEn
123
TANK
BOILER
888
123
TANK
BOILER
dln TANK
BOILER
rln
90 Val.Fabbr.
123
24
123
dEt rAi
8
Val.Fabbr.
123
7
123
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 6 / 28
Example
Suppose there is connected an external detergent dispenser with a probe into the tank. A typical setting
could be:
the dispenser is not activated during filling tank;
the dispenser is supplied during washing phase and the probe automatically dose the right
detergent amount.
5 COUNTERS
This Parameter Family collects cycle counters and water consumption counters.
For water consumption counters a flow meter must be installed. See (calibration parameter) into
section (8 OTHER PARAMETERS).
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 7 / 28
5.1 Counters
Sym. Parameter Description Unit Min Max Factory
Default
Cycles performed counter.
symbol and two numbers blink consecutively. The cycle number
is obtained by joining the two numbers.
Ex. → → means 10042 cycles executed.
-
Cycle counter (resettable).
This counter is similar to but is resettable by user (see
parameter below).
-
Water Consumption (only for dishwashers with incorporated continuous
water softener).
Counts m3of water consumption.
[m3]
Water Consumption (only for dishwashers with incorporated continu-
ous water softener).
Counts litres of water consumption.
The total consumption is given by adding [m3] and [l] values.
[l]
Water Consumption: resettable counter. [present up to software version
3.12]
Counts the litres of water and is resettable by user (see parame-
ter below).
[l]
Reset resettable counters: and
To reset put 1 this parameter, switch off and then on again: and
will show zero. Note that is used to count cycles for
message (see next parameter, ).
-
Store thousand of cycles after that message appears on dis-
play.
Ex. If this parameter is settled to 20, message appears when
reach 20.000 cycles.
-
Drain/Cleaning cycles performed.
Similar to but counts Cleaning Cycles. -
Numbers of cycles that can be made after a regeneration cycle (only for
dishwashers with non-continuous water softener) [See paragraph 9.1
DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION.].
-20
Regeneration cycle counter (only for water softener dishwasher)
[See paragraph 9.2 DISHWASHERS WITH WASH TANK WATER
CHANGE FREQUENCY CONTROL]. only counts efficient
regeneration cycles, i.e. those carried out with salt in the special con-
tainer (only for dishwashers with incorporated continuous water sof-
tener)
-
Counter of regeneration cycles done without salt in the special con-
tainer. (only for dishwashers with incorporated continuous water sof-
tener) [See paragraph 9.2 DISHWASHERS WITH WASH TANK
WATER CHANGE FREQUENCY CONTROL].
-
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 8 / 28
6 TEMPERATURE SETTING
In this paragraph is explained how to change temperature thresholds and all parameters related to boiler and
tank.
6.1 Factory Parameters
Fig. 18 USER setting mode
(press for 5s).
Fig. 19 Next Family Fig. 20 Counters Fam.:
ENTER
Fig. 21 CYCLES Fig. 22 Thousand. Fig. 23 Units. Fig. 24 Next counter.
TANK
BOILER
GEn
123
TANK
BOILER
GEn
123
TANK
BOILER
Cnt
123
Fig.18
Fig.19
Fig.20
CYC 010 042
123
cYc
123
Sym. Parameter Description Unit Min Max Factory
Default
Boiler Temperature: THRESHOLD.
When boiler temperature reaches this value, heaters switch off. [°F] 113 203 172
Boiler Temperature HISTERESIS, (represent dead band).
Heater switch on if boiler temperature is below: - [°F] 35 50 35
Boiler Temperature: HIGH LIMIT.
When boiler temperature reaches this value alarm appears.
Put 0 to disable alarm.
[°F] 32 208 204
Boiler Temperature: LOW LIMIT.
During boiler warm-up, temperature must increase at least °C
otherwise warning appears.
Put 0 to disable warning.
[°F] 32 50 34
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 9 / 28
To modify thresholds do the following:
• Switch OFF and switch ON the dishwasher;
• Enter into the FACTORY SETTING mode by pressing and hold down ON/OFF and BUTTON_2 keys for at
least five seconds (Figure 25);
• Press BUTTON_3. The display shows alternatively the symbol (Figure 26) and the corresponding
value (Figure 27);
• Use BUTTON_1 key to decrease the value and BUTTON_2 key to increase (Figure 27);
• Press BUTTON_3 key to confirm. The display shows the next parameter (Figure 28) and the correspond-
ing value (Figure 29);
• In the same way is possible to change the other parameters; when finished switch OFF and switch ON.
Boiler Filling Timeout.
If filling time is longer than , alarm appears.
Put 0 to disable alarm.
[min] 0 42 5
Boiler Temperature Adjust. [°F] 32 44 39
Boiler Priority (enable boiler wait function)
0=disabled
1=enabled
-01 1
Booster Function
Overheat gap over Boiler Temperature Threshold [°F] 32 59 35
Boiler temperature negative differential: when the dishwasher is in
standby, boiler threshold becomes: -
(Used to save energy during machine inactivity by keeping boiler
water at a lower temperature).
[°F] 32 68 32
Tub Temperature: THRESHOLD
When tank temperature reaches this value, heater switch off. [°F] 104 185 145
Tub Temperature: HISTERESIS, (represent dead band).
Heater switch on if tank temperature is below: - [°F] 35 86 41
Tank Temperature: HIGH LIMIT.
When tank temperature reaches this value alarm appears.
Put 0 to disable alarm.
[°F] 32 203 167
Tank Temperature: LOW LIMIT.
During tank warm-up, temperature must increase at least °C
otherwise warning appears.
Put 0 to disable warning.
[°F] 32 50 34
Tank Filling Timeout.
If filling time is longer than , alarm appears.
Put 0 to disable alarm.
[min] 0 42 20
Fig. 25 Factory setting
mode.
Fig. 26 Boiler temp.
threshold
Fig. 27 Change value &
Store
Fig. 28 Boiler Temp
Hysteresis
Fig. 29 Change value &
Store
Fig. 30 Tank temp. High
limit.
Fig. 31 Change value &
Store.
TANK
BOILER
FAC
123
bLo
204
123
2
123
bHi
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 0 / 2 8
7 CYCLE SETTING
IIn this paragraph is explained how to change cycle phases duration (see paragraph 7.1 CYCLE DIAGRAM).
• Switch on the dishwasher;
• Enter into the FACTORY SETTING mode: press and hold down ON/OFF and BUTTON_2 keys for at least
5 seconds (Figure 32);
• Press BUTTON_2 key to select cycle 1 parameters.
• Press BUTTON_3. The display shows alternatively the symbol (Figure 35) and the corresponding
value (Figure 36);
• Use BUTTON_1 key to increase the value and BUTTON_2 key to decrease (Figure 36);
• Press BUTTON_3 key to confirm. The display shows the next parameter (Figure 37) and the correspond-
ing value (Figure 38);
• In the same way is possible to change the other parameters;.
After settled all parameters referring Cycle 1, by pressing BUTTON_2 key is possible to change the Cycle 2
parameters (Figure 39), (Figure 40) and so on.
Fig. 32 Factory setting mode.
Fig. 33 Select next class. Fig. 34 Cycle 1 Family: ENTER. Fig. 35 Wash duration [min].
Fig. 36 Change value & Store Fig. 37 Wash duration [sec]. Fig. 38 Wash duration [min]..
Fig. 39 Cycle 1 Parameters. Fig. 40 Cycle 2 Parameters:
ENTER.
Fig. 41 Wash duration [min].
Fig. 42 Cycle 2 Parameters:
next Family
Fig. 43 Cycle 3 Parameters:
ENTER
Fig. 44 Wash duration [min].
TANK
BOILER
FAC
123
CY1
123
FAC
123
Ln1
123
Sh10
123
35
123
CY2
CY1
123
Ln2
123
CY3
CY2
123
Ln3
123
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 2 / 2 8
7.2 Cycle 1 Parameters
7.3 Cycle 2 Parameters
7.4 Drain/Cleaning Cycle Parameters
Sym. Parameter Description Unit Min Max Factory
Default
Wash Phase Long [min] 0 20 0
Wash Phase Short [s] 1 60 35
Pause [s] 0 20 4
Pre-rinse Duration [s] 0 30 0
Rinse Phase Duration [s] 10 45 16
Cold Rinse Phase Duration [s] 0 50 0
Drain [s] 0 40 16
Final Pause at End of Cycle [s] 0 60 0
Long wash time in mode Thermal Label [min] 0 60 0
Short wash time in mode Thermal Label [s] 0 60 59
Sym. Parameter Description Unit Min Max Factory
Default
Wash Phase Long [min] 0 20 0
Wash Phase Short [s] 1 60 40
Pause [s] 0 20 4
Pre-rinse Duration [s] 0 30 0
Rinse Phase Duration [s] 10 45 16
Cold Rinse Phase Duration [s] 0 50 0
Drain [s] 0 40 16
Final Pause at End of Cycle [s] 0 60 0
Long wash time in mode Thermal Label [min] 0 60 2
Short wash time in mode Thermal Label [s] 0 60 12
This parameter allows having a different rinsing temperature for
the second cycle. Only values above 113°F are allowed. [°F] 32 203 32
Sym. Parameter Description Unit Min Max Factory
Default
Initial Drain Phase Duration [s] 0 240 40
Final Drain Phase Duration [s] 0 240 80
Drain without cleaning cycle -01 0
Number of wash cycles possible between one drain cycle and the
next
[wash
cycles] 0200 0
Indicates the maximum permissible delay between drain cycle
start and the reaching of a tank level below the work level. If the
set delay is exceeded, alarm B1 occurs.
[s] x 10 0 100 18
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 3 / 2 8
8 OTHER PARAMETERS
8.1 Dishwashing Parameters
Sym. Parameter Description Unit Min Max Factory
Default
Initial Pause before start washing (for ALL cycles) [s] 0 10 0
Delay for the 2nd wash pump (PW only) [s] 0 10 3
Active a drain phase at the end of washing phase. [s] 0 40 0
Duration of pause after rinse cycle (valid for dishwashers with
door/hood lock device) [See par. 9.1 DETERGENT AND RINSE
AID LEVEL SENSORS ACTIVATION].
[s] 0 60 0
Celsius/Fahrenheit selection
0 = Celsius
1 = Fahrenheit
-01 1
Rinse Temperature Display.
Enable rinse temperature probe (if installed).
0 = during rinse phase the display shows boiler temperature;
1 = during rinse phase the display shows rinse temperature;
-01 0
Pulse Per Litre.
This parameter must be settled in according to flow meter
installed [present up to software version 3.12].
[p/l] 0 255 0
Number of wash cycles performable without detergent (only for
dishwashers with external detergent level sensor – par. 9.1
DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION)
[]
-05 5
Enable mode Thermal Label: if set to 1 it enables the mode and
disables the "endless cycle" button -01 0
Boiler temperature in mode Thermal Label. [°F] 113 206 186
Tank temperature in mode Thermal Label. [°F] 104 194 167
Tank temperature hysteresis in mode Thermal Label. [°F] 32 86 35
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 4 / 2 8
8.2 Read Only Parameters
8.3 Communication and HACCP
Parameters
Sym. Parameter Description Unit Min Max Factory
Default
Main Board Firmware Release --- -
Water softener board software version. (only for dishwashers with
incorporated continuous water softener). --- -
Active column: indicates through which of the two continuous
water softener columns boiler filling is being carried out: 0 = col-
umn A and 1 = column B (only for dishwashers with incorporated
continuous water softener).
--- -
When
message appears, the parameter value becomes 3.
After maintenance, to clear message, insert 0. --- -
When alarm appears, the machine is frozen and this
parameter is 3.
After maintenance (see alarm codes document), insert 0 to ena-
ble the machine.
--- -
This alarm appears in case of malfunctioning in the continuous
water softener. To facilitate fault-finding, see par. In the case of a
shorted probe error (C 5, C 7 e C11), the displayed temperature is
210°F..
--- -
Sym. Parameter Description Unit Min Max Factory
Default
Serial Device
0 = 8N1
1 = PC connection (DAAS 8E1)
7 = HACCP network (ECAP 8E1+LK485) (LK485 board is nec-
essary)
9 = Dishwashers with incorporated continuous water softener
16 = HACCP printer (8N1)
32 = MODEM GSM (DAAS 8N1)
33 = MODEM GSM (DAAS 8E1)
48 = Hyper Terminal (8N1)
-063 1
Address.
This parameter specifies the address of the appliance into the
‘HACCP_network’.
Works only if ‘HACCP network’ is selected (see above parameter).
- 0 255 1
Print parameter table. -01 1
HACCP ‘Basic’ (printer)
Boiler temperature: high limit. [°F] 113 203 194
HACCP ‘Basic’ (printer)
Boiler temperature: gap below high limit. [°F] 32 68 50
HACCP ‘Basic’ (printer)
Tank temperature: high limit. [°F] 95 167 154
HACCP ‘Basic’ (printer)
Tank temperature: gap below high limit. [°F] 32 68 50
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 5 / 2 8
8.4 Configuration Parameters
Sym. Parameter Description Unit Min Max Factory
Default
Dishwasher Model:
0 = UNDERCOUNTER
1 = POT WASHER
2 = AUTOMATIC POT WASHER
3 = MEDICAL LINE DISHWASHER WITH LOCK DOOR/HOOD
DEVICE
-03 0
Boiler type:
0 = ATMOSPHERIC BOILER
1 = PRESSURE BOILER
2 = EXTERNAL BOILER
-02 0
Door type:
0 = AUTOMATIC HOOD
1 = MANUAL HOOD
2 = FRONT LOADING
3 = POT WASHER
03 2
Default model (see Default tables):
1 = HOOD TYPE
2 = POT WASHER
3 = UNDERCOUNTER
-03 -
Solid State Relay (TRIAC).
0 = not enabled;
1 = SOFT START enabled;
3 = SLOW SOFT START enabled
(works only on boards with Solid State Relay).
-03 1
Boiler/Tank heating swap:
0 = boiler heaters and tank heater can work simultaneously;
1 = swap enabled: tank heating starts only boiler temperature is
reached;
2 = The booster heating elements and the wash pump have prior-
ity. The tank heating element is activated only when the booster
has reached the set temperature and the wash pump is not work-
ing.
(Note: disabling this function changes the global electrical power
of appliance; before enabling this function check available power,
supply cable section, fuses in according to User Manual).
-02 1
Tank Filling Mode
Enable filling tank by means of rinsing cycles.
Ex: = 167 means that boiler water is heated at 167°F, then
follows a rinse phase and so on until tank is full.
If = 32 the tank is filled by solenoid valve in the traditional
way (On machines with incorporated continuous water softener,
even if is set to 32, filling occurs through subsequent
rinses).
[°F] 32 185 167
Detergent Level Switches
0 = level switches not enabled;
1 = enable detergent level switches;
-01 0
USER INTERFACE MODEL
24 = under counter, Veetsan
See parameter (family ) to check the software version
installed in the board.
-027 25
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 6 / 2 8
8.5 Parameters for automatic hood type dishwashers
Sym. Parameter Description Unit Min Max Factory
Default
Enable “regeneration cycle” key (only for dishwashers with non-
continuous water softener) [See paragraph 9.1 DETERGENT
AND RINSE AID LEVEL SENSORS ACTIVATION].
-01 0
ALARMS ENABLE
0 = alarms disabled (to disable also warnings see and
);
1 = alarms enabled;
If this function is disabled, faults can be detected so display do not
shows any alarm code.
-01 1
Air gap with float level sensor normally closed (the level sensor is
closed when the boiler is empty). E.g. the boiler level sensor for
machines with incorporated continuous water softener.
-01 0
Forced start of a resin regeneration cycle (only for dishwashers
with incorporated continuous water softener). [See paragraph 9.2
DISHWASHERS WITH WASH TANK WATER CHANGE FRE-
QUENCY CONTROL].
-02 0
Max. rinse water hardness (only for dishwashers with incorpo-
rated continuous water softener). After modifying, disconnect and
reconnect the machine's main power supply by means of the
main switch. [See paragraph 9.2 DISHWASHERS WITH WASH
TANK WATER CHANGE FREQUENCY CONTROL].
°fH 4 14 10
Boiler heating control.
Defines the max. permissible temperature difference during boiler
heating in a time interval of 2 minutes and 30 seconds.
°F 77 176 122
Sym. Parameter Description Unit Min Max Factory
Default
DELAY_K1
Time (during hood lifting) within which S3” must return to the rest
position.
0.1 s 0.0 s. 20.0 s 15
HOOD_TOUT
TIMEOUT – max. time allowed for complete hood opening/clos-
ing.
0.1 s 0.0 s 20.0 s 200
DELAY_K1_S3
During hood lowering, firstly S3” must cut in and then after a time
.the bottom limit switch S3.
0.1 s 0.0 s. 20.0 s 15
DELAY_K
Time within which K and K’ must be both closed or both open. 0.1 s 0.0 s. 20.0 s 10
DELAY_S3
Time during hood lifting within which the bottom limit switch must
return to the rest position..
0.1 s 0.0 s. 20.0 s 20
DELAY_S5
Time during hood lowering within which the top limit switch must
return to the rest position.
0.1 s 0.0 s. 20.0 s 20
Displays the last alarm code relative to automatic hood type dish-
washers. --- 0
Parameter only valid for hood type models.
Hood lifting motor absorption threshold.
(50 units correspond to a current of approx. 1 ampere).
- 0 250 100
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 7 / 2 8
9 SPECIAL FEATURES
9.1 DETERGENT AND RINSE AID LEVEL SENSORS ACTIVATION
By setting the parameter (in the family) to 1, management of the level sensors located inside the
external detergent and rinse aid tanks is enabled. During the rinse phase, when the rinse aid inside the tank
has finished, the message appears on the display.
When the detergent inside the tank is finished, the message is displayed and after a number of wash
cycles equal to (in the family) the dishwasher inhibits the activation of other wash cycles. There-
fore the detergent level in the tank must be restored.
9.2 DISHWASHERS WITH WASH TANK WATER CHANGE FREQUENCY CONTROL
WARNING:
Function included starting from firmware version 5.00.
If the parameter (Cycles before drain) of the family is set to a value higher than , a wash tank
water change frequency control is enabled. The purpose of this function is to display a message telling the
customer when a tank water drain cycle is required. In this way, if the customer does what the machine sug-
gests, washes will be done with sufficiently clean water.
The value set in the parameter (Cycles before drain) indicates the number of wash cycles possible
between one tank water drain cycle and the next. When the number of wash cycles done since the last tank
water change reaches the value contained in the parameter (Cycles before drain), the display shows the
message “” at the start of a wash cycle and the message “” at the end of the same cycle. When
these messages appear on the display at the start and end of the wash cycle, a tank water drain cycle must
be done to ensure washes with sufficiently clean water.
WARNING:
If the tank drain cycle is not done, the machine does not shut down, but will continue to do wash
cycles, showing the messages and at the start and end of the wash cycle
respectively.
9.3 PERISTALTIC TUBE FITTING AND REPLACEMENT INSTRUCTIONS
Described below is the procedure for inserting and removing the tubes from the peristaltic pumps, in case of
tube replacement.
An exploded view of the parts involved in the tube fitting and removal operations is given below.
Ruoller
Front box
Tu b e
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 1 8 / 2 8
STEP 1 - FITTING THE TUBE
1. Position the roller. 2. Insert the tube of the suction part, turning the roller
clockwise.
3. Keep the tube in the seat in the housing and
continue turning the roller clockwise, being
careful not to damage the tube.
4. Keep the tube in the seat in the housing and con-
tinue turning the roller clockwise.
5. Turn the roller a full 360°. 6. Make sure to fit the union in the special seat (deliv-
ery).
https://appliancetechmanuals.com

DOC. NO. 5956.6K6.00 P. 2 0 / 2 8
10 MAIN BOARD CONFIGURATION
When receiving an electronic board (spare part) may be necessary to configure it in according to the machine
where has to be replaced
4. With the machine CODE enter into the following table and read the corresponding Prog. number
5. Follow the instructions reported into the corresponding Prog.XXX sheet (next pages).
6. With the machine CODE find the Layout number in Par. 12.2 CONNECTORS LAYOUT.
10.1 CODE -> Prog. TABLE
MODEL CODE Prog. Layout
VDU30 502350 149 09
https://appliancetechmanuals.com
Other manuals for VDU30
1
Table of contents
Other Veetsan Dishwasher manuals
Popular Dishwasher manuals by other brands

Blomberg
Blomberg LDVN2284 instruction manual

Maytag
Maytag Jetclean III MDB3700AW install guide

CMA Dishmachines
CMA Dishmachines CMA-180VL Quick setup instructions

LG
LG STEAMDISHWASHER LDF7932ST Specifications

Bosch
Bosch SMV6ZCX07E INFORMATION FOR USE

Kuppersbusch
Kuppersbusch IGVS6509.5 operating instructions