Vemmio DS-100 User manual

WWW.VEMMIO.COM
double
switch
MODEL: DS-100
V1.0
INTRODUCTION
Thank you for choosing Vemmio. We welcome you in our cus-
tomer society.
Vemmio Double Switch is a dual relay in-wall module. The prod-
uct works as a transceiver and is a Z-Wave Plus enabled device.
Mini size design lets the module be easily hidden into the wall
box to do not interfere with house decoration. One of many uses
of the Double Switch is to turn on or off the connected fittings
and monitor power consumption in real time. The new smart re-
lay calibration technology can work perfectly with many kinds
of lights like: incandescent, fluorescent and LED lights.
PACKAGE CONTENTS:
• user manual
• Double Switch.
KEY FE ATURES
Remotely control your equipment and fittings ( On/Off )
Two channels used separately ( 2x 1500 W )
Monitor power consumption in real time
If an overload (>1600-1700 W) is detected, the module auto-
matically cuts off the powered circuit
Mini size design lets the module be easily hidden into the wall
box
SPECIFICATION
Wireless standard Z-Wave Plus
Frequency 868.40 MHz
Network range 40 m indoor/ 100 m line
of sight
Operating temperature 0°C ~ 40°C
Maximum Load 6.5 A (230 VAC/120 VAC)
(Resistive load)
Operating Voltage 100 to 240 VAC
Control circuits Two channels 2 x 1500 W
INSTALLATION
DANGER
RISK OF ELECTROCUTION
All work on the device should only be carried out by trained
and skilled electricians. Observe the country-specific regula-
tions.
DANGER
RISK OF FATAL INJURY FROM ELECTRIC CURRENT.
The device has no basic insulation and must therefore be in-
stalled in a way that protects against accidental contact.
DANGER
RISK OF FATAL INJURY FROM ELECTRIC CURRENT.
When installing a wall plate, the distance between the cover’s
fixing brackets or screws and the connections of the flush-
mounted Double Switch must be at least 4 mm once installed.
If the distance is less than 4 mm, a deeper installation box must
be used. The fixing brackets or screws of the cover must not
press against the housing. Only insulated tools may be used for
operation on the device, e.g. an insulated phase tester.
ADDING TO Z-WAVE NETWORK
The Z-Wave button, located in the front casing, can toggle Dou-
ble Switch on and off, add, remove, reset or associate the sensor
to Z-Wave network.
FIRST INCLUSION
Follow the instructions for your Z-Wave certified controller to
enter the desired mode and then follow the instructions from
the table below. When power is applied for the first time, LED
flashes on and off at 0.5 second intervals. It implies that the
Double Switch has not been assigned a node ID and starts auto
inclusion. Auto inclusion will be executed.
Please note: first inclusion may vary depending on your gate-
way - please see gateway manual for details.
Please note: Auto inclusion timeout is 2 minute during which
the node information of explorer frame will be emitted once
every several seconds. Unlike “inclusion” function as shown
in the table below, the execution of auto inclusion is free from
pressing the Z-Wave button.
Function Description Annotation
No node
ID
The Z-Wave Controller does
not allocate a node ID to the
Switch.
LED 2-second on,
2-second off
Inclusion
*
1. Put your Z-Wave control-
ler into inclusion mode by
following the instructions
provided by the controller
manufacturer.
One press one
flash LED
2. Pressing Z-Wave button
three times within 2 seconds
will enter inclusion mode.
Exclu-
sion
1. Put your Z-Wave control-
ler into exclusion mode by
following the instructions
provided by the controller
manufacturer.
One press one
flash LED
1. Pressing Z-Wave button
three times within 2 seconds
will enter exclusion mode.
3. Node ID has been excluded. LED 0.5s On, 0.5s
Off (Enter auto
inclusion)
Factory
Reset
1. Pressing Z-Wave button
three times within 2 seconds
will enter inclusion mode.
Use this procedure
only in the event
that the primary
controller is lost or
otherwise inoper-
able.
2. Within 1 second, press On/
Off button again for 5 seconds.
3. IDs are excluded. LED 0.5s On, 0.5s
Off (Enter auto
inclusion)
Associa-
tion
1. The Double Switch is an
always listening Z-Wave de-
vice, so associations can
be added or removed by a
controller at any time.
Or If your controller requires
to have the Double Switch
send a ‘node information
frame’ or NIF for associations,
pressing the Z-Wave button
three times within 2 seconds
will cause the Double Switch
to send
LED one press one
flash
2. There are 3 groups for the
switch
Including a node ID allocated by Z-Wave Controller means
inclusion. Excluding a node ID allocated by Z-Wave Controller
means exclusion.
If the first attempt of exclusion is unsuccessful, please repeat
the process following all steps carefully.
*Please note: Always exclude a Z-wave product before trying
to add it to a Z-Wave network.
ASSOCIATION
Group ID Maximum
Nodes
Description
1 1 For group 1, the Switch will report (1)
ON/OFF status of Relay1 and Relay2
(2) Instant Power Consumption
(Watt) of Relay1 and Relay2 (3) Accu-
mulated Power Consumption (KWh)
of Relay1 and Relay2 to Group1 node.
2 1 For group 2, the Switch will report (1)
ON/OFF status of Relay1 (2) Instant
Power Consumption (Watt) of Relay1
(3) Accumulated Power Consumption
(KWh) of Relay1 to Group2 node.
3 1 For group 3, the Switch will report (1)
ON/OFF status of Relay2 (2) Instant
Power Consumption (Watt) of Relay2
(3) Accumulated Power Consumption
(KWh) of Relay2 to Group3 node.
PHYSICAL INSTALLATION
Choosing a Suitable Location
1. Do not locate the Double Switch facing direct sunlight, humid
or dusty place.
2. The suitable ambient temperature for the Double Switch is
0°C~40°C.
3. Do not locate the Double Switch near combustible substanc-
es or any source of heat, e.g. fires, radiators, boiler etc.
4. After putting it into use, the body of Double Switch will be-
come a little bit hot.
Assembly drawings
MOUNTING
1. Put the Double Switch into a wall box and connect the wires L,
N to the Double Switch connector L, N.
2. Connect the wall switch to the Double Switch according to
the above assembly drawings.
3. To manually turn on the Double Switch, press and release the
Z-Wave button. The LED will flash for 1 second, and the load
plugged into the Double Switch will become active.
4. To manually turn off the Double Switch, simply press and re-
lease the Z-Wave button. The LED will flash for 1 second and
the load plugged into the Double Switch will become inactive.
FIRMWARE UPDATE OVER THE AIR (OTA)
Double Switch supports Firmware Update Command
Class, it can receive the updated firmware image sent by con-
troller via the Z-wave RF media.
Supported Command Classes
COMMAND_CLASS_ZWAVEPLUS_INFO
COMMAND_CLASS_VERSION_V2
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V2
COMMAND_CLASS_DEVICE_RESET_LOCALLY
COMMAND_CLASS_ASSOCIATION_V2
COMMAND_CLASS_ASSOCIATION_GRP_INFO
COMMAND_CLASS_POWERLEVEL
COMMAND_CLASS_SWITCH_BINARY
COMMAND_CLASS_BASIC
COMMAND_CLASS_SWITCH_ALL
COMMAND_CLASS_ALARM
COMMAND_CLASS_SCENE_ACTIVATION
COMMAND_CLASS_SCENE_ACTUATOR_CONF
COMMAND_CLASS_PROTECTION
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V2
COMMAND_CLASS_MULTI_CHANNEL_V3
COMMAND_CLASS_METER_V3
COMMAND_CLASS_CONFIGURATION
PROGRAMMING
BASIC COMMAND CLASS / BINARY SWITCH COMMAND
CLASS
The Switch will respond to BASIC and BINARY SWITCH com-
mands that are part of the Z Wave system.
1-1 BASIC_GET / BINARY_SWITCH_GET
Since the switch has two relays, the Switch will report its On/
Off state to the Controller by setting Configuration parameter 3.
Configuration parameter 3=1
Report ON when relay 1 ON
Report OFF when relay 1 OFF
Configuration parameter 3=2
Report ON when relay 2 ON
Report OFF when relay 2 OFF
Configuration parameter 3=3 (default)
Report ON when either relay 1 ON or relay 2 ON
Report OFF when both relay 1 and relay 2 OFF
Basic Get Command: [Command Class Basic, Basic Get]
Basic Report Command:
Report OFF: [Command Class Basic, Basic Report, Value =
0(0x00)]
Report ON: [Command Class Basic, Basic Report, Value =
255(0xFF)]
Binary Switch Get Command: [Command Class Switch Bi-
nary, Switch Binary Get]
Binary Switch Report Command:
Report OFF: [Command Class Switch Binary, Switch Binary
Report, Value =0(0x00)]
Report ON: [Command Class Switch Binary, Switch Binary
Report, Value = 255(0xFF)]
1-2 BASIC_SET / SWITCH_BINARY_SET
Since the switch has two relays, the load attached to the Dou-
ble Switch will turn on or off upon receipt of the following
commands from a Z-Wave Controller by setting Configuration
parameter 3.
Configuration parameter 3=1
switch ON and OFF of relay 1
Configuration parameter 3=2
switch ON and OFF of relay 2
Configuration parameter 3=3(default)
double
switch

WWW.VEMMIO.COM
switch ON and OFF both relay 1 and relay 2
[Command Class Basic, Basic Set, Value = 1~99, 255(0xFF)]:
the load attached to the Switch turns on.
[Command Class Basic, Basic Set, Value = 0(0x00)]: the load
attached to the Switch turns off.
[Command Class Switch Binary, Switch Binary Set, Value =
1~99, 255(0xFF)]: the load attached to the Switch turns on.
[Command Class Switch Binary, Switch Binary Set, Value =
0(0x00)]: the load attached to the Switch turns off.
2. Z-Wave’s Groups (Association Command Class Version 2)
The Switch can be set to send reports to control associ-
ated Z-Wave devices. It supports 3 association groups which
every group has one node support. Group1~Group3 support
SWITCH_BINARY_REPORT,
METER_REPORT_COMMAND_V3
For group 1, the Double Switch will report (1) ON/OFF status
of Relay1 and Relay2 (2) Instant Power Consumption (Watt) of
Relay1 and Relay2 (3) Accumulated Power Consumption (KWh)
of Relay1 and Relay2 to Z-Wave Controller.
For group 2, the Double Switch will report (1) ON/OFF status
of Relay1 (2) Instant Power Consumption (Watt) of Relay1 (3)
Accumulated Power Consumption (KWh) of Relay1 to Z-Wave
Controller.
For group 3, the Double Switch will report (1) ON/OFF status
of Relay2 (2) Instant Power Consumption (Watt) of Relay2 (3)
Accumulated Power Consumption (KWh) of Relay2 to Z-Wave
Controller.
2-1 Auto report to Grouping 1 ~3 (Maximum Node 1)
2-1-1 On/Off Event Report
When “on” or “off” state has been changed, it will send Binary
Switch Report to the nodes of Group1~3.
Binary Switch Report
ON:[Command Class Switch Binary, Switch Binary Report,
Value =255 (0xFF)]
OFF:[Command Class Switch Binary, Switch Binary Report,
Value =0 (0x00)]
2-1-2 Instant Power Consumption vary over 5% report
When the power consumption of load vary over 5%, it will send
Meter report to the nodes of Group
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01, Me-
ter Type = 0x01,
Precision = 1, Scale = 0x02, Size = 4, Meter Value(W) ]
2-1-3 overload alarm report command
When DOUBLE SWITCH detects the overload, it will send
Alarm Report to the correspond Group.
The content of Alarm Report
Alarm report command: [Command_Class_Alarm, Alarm_Re-
port, Alarm Type = 0x08,
Alarm Level = 0xFF]
2-2 Response to Meter Get Command
The Double Switch will report its (1) instant Power Consump-
tion (Watt) or (2) accumulated power consumption(KWH) or
(3) AC load Voltage (V) or (4) AC load current ( I ) (5) load power
factor (PF) to Z-Wave Controller after receive the Meter Get
Command from Z-Wave Controller.
2-2-1 Instant Power Consumption (Watt) of Switch
When receiving Meter Get Command, it will report Meter Re-
port Command to the node asked.
Meter Get Command: [Command Class Meter, Meter Get,
Scale =0x02(W)]
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01, Me-
ter Type = 0x01,
Precision = 1, Scale = 0x02, Size = 4, Meter Value(W) ]
2-2-2 Accumulated Power Consumption (KW/h)
When receiving Meter Get Command, it will report Meter Re-
port Command to the node asked.
Meter Get Command:
[Command Class Meter, Meter Get, Scale = 0x00 KW/h)]
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01, Me-
ter Type =0x01, Precision = 2, Scale = 0x00, Size = 4, Meter
Value (KWh)]
Accumulated power consumption (KW/h) = (Meter Value
2*65536) + (Meter Value 3*256) + (Meter Value 4) = 800.35
(KW/h)
2-2-3 Clearing accumulated power consumption
Whenever re-start counting the accumulated power consump-
tion is needed, you can use Meter Reset Command to clear it.
Meter Reset Command: [Command Class Meter, Meter Reset]
2-2-4 AC load Voltage (V)
When receiving Meter Get Command, it will report Meter Re-
port Command to the node asked.
Meter Get Command: [Command Class Meter, Meter Get,
Scale =0x04(V)]
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01, Me-
ter Type = 0x01, Precision = 1, Scale = 0x04, Size = 2, Meter
Value(V)]
2-2-5 AC load current ( I )
When receiving Meter Get Command, it will report Meter Re-
port Command to the node asked.
Meter Get Command: [Command Class Meter, Meter Get,
Scale =0x05(I)]
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01, Me-
ter Type = 0x01,
Precision = 2, Scale = 0x05, Size = 2, Meter Value(I)]
2-2-6 load power factor (PF)
When receiving Meter Get Command, it will report Meter Re-
port Command to the node asked.
Meter Get Command: [Command Class Meter, Meter Get,
Scale =0x06(PF)]
Meter Report Command:
[Command Class Meter, Meter Report, Rate Type = 0x01,
Meter Type = 0x01, Precision = 2, Scale = 0x06, Size = 1 Bytes,
Meter Value(PF)]
2-3 Multi Channel Command Class Version 3
DOUBLE SWITCH also supports Multi Channel command class
(version 3), which include
BINARY_SWITCH_GET, BINARY_SWITCH_SET, BASIC_GET,
BA SIC_SET,
METER_SUPPORTED_GET, METER_RESET, METER_GET
You may control or get report from 3 endpoints of DOUBLE
SWITCH.
2-3-1 BINARY_SWITCH_GET,
You may get the ON/OFF state from every endpoint, when
endpoint set to 1, DOUBLE SWITCH will reply state of Relay1.
If endpoint set to 2, DOUBLE SWITCH will reply state of Relay2.
If endpoint set to 3, DOUBLE SWITCH will reply ON (0xFF)
when either Relay 1 or Relay2 is ON, report OFF (0x00) when
both Relay 1 and Relay2 are OFF. Below is an example show-
ing a source endpoint 5 sending a Get command to DOUBLE
SWITCH endpoint 3.
Please note: the below tables present information for the following:
COMMAND_CLASS_MULTI_CHANNEL
MULTI_CHANNEL_CMD_ENCAP
Source End Point = 0x05 (this is the endpoint of
command inquirer here we
assume endpoint is 5, if the
inquirer doesn’t suport multi
Channel this value will be 0)
(Bit Address+Destination End
Point = 0x03)
(Bit Address =0; Destination
End Point range from 1~3)
Command Class = 0x25 (Command_Class_Switch_Bi-
nary = 0x25)
Command =0x02 (Switch_Binary_Get = 0x02)
Below is the example show DOUBLE SWITCH report to last
command
Source End Point = 0x03 Since the endpoint is 3 so
DOUBLE SWITCH will reply
ON(0xFF) when either Relay
1 or Relay2 is ON, report OFF
(0x00) when both Relay 1 and
Relay2 are OFF
(Bit Address+Destination End
Point = 0x05)
(Bit Address = 0; Destination
End Point
Command Class = 0x25 (Command_Class_Switch_
Binary=0x25)
Parameter 1 = 0xFF (ON=0xFF, OFF=0x00)
2-3-2 BINARY_SWITCH_SET
By using BINARY_SWITCH_SET Command of Multi Channel
Command Class Encapsulation Command, you can switch Re-
lay1 ON/OFF by setting endpoint to 1, or switch Relay2 ON/
OFF by setting endpoint to 2, or switch both Relay1 and Relay2
ON/OFF by setting endpoint to 3
The example of the command shows that switch off relay1 of
DOUBLE SWITCH
Source End Point = 0x01 (this is the endpoit of com-
mand inquirer here
we assume ednpoint is 1, if the
inquirer doesn’t
suport multi channel, this
value will be 0)
(Bit Address+Destination End
Point=0x01)
(Bit Address = 0; Destination
End Point range 1-3
Command Class = 0x25 (Command_Class_Switch_
Binary=0x25)
Command =0x01 (Switch_Binary_Set = 0x01)
Parameter 1 = 0x00 (ON=0xFF , OFF=0x00)
2-3-3 METER_SUPPORTED_GET
This command is to ask the endpoint of DOUBLE SWITCH what
kind of meter data can be reported.
The example shows how to get the meter report type
Source End Point = 0x01 (this is the endpoint of
command inquirer here we
assume endpoint is 1, if the
inquirer doesn’t support Multi
Channel this value will be 0)
(Bit Address+Destination End
Point = 0x03)
(Bit Address =0; Destination
End Point range1~3)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x03 (Meter_Supported_Get =
0x03)
Below is the example show DOUBLE SWITCH report to last
command
Source End Point = 0x03
(Bit Address+Destination End Point = 0x01)
Command Class = 0x32
Command Class = 0x32
(Command_Class_Meter_V3
= 0x32)
Command =0x04 (Meter_Supported_Report
= 0x04)
Parameter 1 = 0x81 (Meter Reset =1, Meter
Type=0x01)
Parameter 2 = 0x75 (Scale Supported =
KWh+W+V+A+Power Factor
= 0x75)
2-3-4 METER_RESET
This command is to reset the Accumulated Power Consumption
(KWh) to 0
The example shows how to reset the KWh
Source End Point = 0x03 (this is the endpoint of com-
mand
inquirer, here we assume
endpoint is 3, if the inquirer
doesn’t support multi
Channel this value will be 0)
(Bit Address+Destination End
Point = 0x01)
(Bit Address = 0; Destination
End Point = range 1-3
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x05 (Meter Reset = 0x05)
2-3-5 METER_GET:
Using meter get command to get the KWH, W, V, I, PF from end-
point of DOUBLE SWITCH 2-3-5-1 Get KWH from endpoint
Meter_GET example:
Source End Point = 0x05 (this is the endpoint of
command inquirer, here we
assume endpoint is 5, if the
inquirer doesn’t support multi
Channel this value will be 0)
(Bit Address+Destination End
Point = 0x03)
(Bit Address =0 ; Destination
End Point range1~3)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x01 (Meter_Get = 0x01)
Parameter 1 = 0x00 (Scale = KWH = 0X00)
Accumulated power consumption (KWH) Report example:
Source End Point = 0x03 (Meter report = Endpoint3)
(Bit Address+Destination End
Point = 0x05)
(Bit Address =0; Destination
End Point = command in-
quirer’s Endpoint value)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x02 (Meter_Report = 0x02)
Parameter 1 = 0x21 (Scale Bit2 = 0, Rate Type =
0x01, Meter Type=0x01)
Parameter 2 = 0x44 (Precision = 2, Scale Bit1Bit0
= 0, Size = 4)
Accumulated Power Con-
sumption =0x000005FD =
15.33 KWh
Parameter 3 = 0x00
Parameter 4 = 0x00
Parameter 5 = 0x05
Parameter 6 = 0xFD
2-3-5-2 Get Instant Power Consumption (Watt) from endpoint
METER_GET example:
Source End Point = 0x05 (this is the endpoint of
command inquirer, here we
assume endpoint is 5, if the
inquirer doesn’t support multi
Channel this value will be 0)
(Bit Address+Destination End
Point =0x03)
(Bit Address =0:Destination
End Point range 1~3)
Command Class = 0x32 ( Command_Class_Meter_V3
= 0x32)
Command = 0x01 (Meter_Get = 0x01)
Parameter 1 = 0x10 (Scale = W = 0x02)
DOUBLE SWITCH Instant Power Consumption (W) Report
example:
Source End Point = 0x03 (Meter report = Endpoint 3)
(Bit Address+Destination End
Point = 0x05)
(Bit Address =0 ; Destination
End Point = command in-
quirer’s Endpoint value)

WWW.VEMMIO.COM
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command = 0x02 (Meter_Report = 0x02)
Parameter 1 = 0x21 (Scale Bit2 = 0, Rate Type =
0x01,Meter Type=0x01)
Parameter 2 = 0x34 (Precision = 1, Scale Bit1Bit0
= 0x02, Size = 4)
Parameter 3 = 0x00 Instant Power Consumption =
0x000003EA = 100.2W
Parameter 4 = 0x00
Parameter 5 = 0x03
Parameter 6 = 0xEA
2-3-5-3 Get load voltage V from endpoint:
Meter_GET example:
Source End Point = 0x05 (this is the endpoint of com-
mand inquirer, here we as-
sume endpoint is 5, if the
inquirer doesn’t support multi
Channel this value will be 0)
(Bit Address+Destination End
Point = 0x03)
(Bit Address =0; Destination
End Point range1~3)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x01 (Meter_Get = 0x01)
Parameter 1 = 0x20 (Scale = V = 0x04)
DOUBLE SWITCH AC load Voltage report example:
Source End Point = 0x03 (Meter report = Endpoint3)
(Bit Address+Destination End
Point = 0x05)
(Bit Address =0 ; Destination
End Point = command in-
quirer’s Endpoint value)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x02 (Meter_Report = 0x02)
Parameter 1 = 0xA1 (Scale Bit2 = 1, Rate Type =
0x01, Meter Type=0x01)
Parameter 2 = 0x22 (Precision = 1, Scale Bit1Bit0
= 0x00, Size = 2)
Parameter 3 = 0x09 Voltage = 0x0910 = 232.0V
Parameter 4 = 0x10
2-3-5-4 Get load current I from endpoint:
Meter_GET example:
Source End Point = 0x05 (this is the endpoint of
command inquirer, here we
assume endpoint is 5, if the
inquirer doesn’t support multi
Channel this value will be 0)
(Bit Address + Destination
End Point = 0x03)
(Bit Address =0;Destination
End Point range1~3)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x01 (Meter_Get = 0x01)
Parameter 1 = 0x28 (Scale = A = 0x05)
DOUBLE SWITCH AC load current (I) example:
Source End Point = 0x03 (Meter report = Endpoint3)
(Bit Address+Destination End
Point = 0x05)
(Bit Address =0;Destination
End Point = command in-
quirer’s Endpoint value)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x02 (Meter_Report = 0x02)
Parameter 1 = 0xA1 (Scale Bit2 = 1, Rate Type =
0x01, Meter Type=0x01)
Parameter 2 = 0x4A (Precision = 2, Scale Bit1Bit0
= 0x01, Size = 2)
Parameter 3 = 0x00 Current = 0x002B= 0.043A
Parameter 4 = 0x2B Current = 0x002B= 0.043A
2-3-5-5 Get power factor PF from endpoint
Meter_GET example:
Source End Point = 0x05 (this is the endpoint of
command inquirer, here we
assume endpoint is 5, if the
inquirer doesn’t support multi
Channel thiS value will be 0)
(Bit Address+Destination End
Point = 0x03)
(Bit Address =0;Destination
End Point range 1-3)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x01 (Meter_Get = 0x01)
Parameter 1 = 0x30 (Scale = PF = 0x06)
DOUBLE SWITCH power factor report example:
Source End Point = 0x03 (Meter report = Endpoint 3)
(Bit Address+Destination End
Point = 0x05)
(Bit Address =0;Destination
End Point = command in-
quirer’s Endpoint value)
Command Class = 0x32 (Command_Class_Meter_V3
= 0x32)
Command =0x02 (Meter_Report = 0x02)
Parameter 1 = 0xA1 (Scale Bit2 = 1, Rate Type =
0x01,Meter Type=0x01)
Parameter 2 = 0x51 (Precision = 2, Scale Bit1Bit0
= 0x10, Size =1)
Parameter 3 = 0x63 Power Factor = 0x63 = 0.99
3. Z – Wave’s Configuration
Configuration
Parameter
Size (Byte) Unit Default
Function Value Description
1Watt Me-
ter Report
Period
20x01-
0x7FFF
5s 720 720*5s=3600s=1
hour
2KWH Me-
ter Report
Period
20x01-
0x7FFF
10min 66*10min= 1 hour
3Selected
Relay
11-3 31:Relay 1
2:Relay 2
3:Relay 1 &
Relay 2
4Edge or
Pulse mode
or Edge-
Toggle
mode
11-3 11:Edge mode
2:Pulse mode
3:Edge-Toggle
mode
5 Threshold
of current
for Load
Caution
210-750 0.01A 750 750*0.01A = 7.5A
6 Threshold
of KWH
for Load
Caution
21-
10000
1KWh 10
00
0
7 Restore
switch
state
mode
10-2 10 Swith off
1 Last switch
state
2 Switch on
8Auto off
timer
20-0x
7FFF
1s 00 Disable auto off
function
1 0x7FFF 1s-
32767s
9RF off
command
mode
10-3 00 Switch off
1 Ignore
2 Switch toggle
3 Switch on
10 Existance
of End-
point 3
11-2 11 Endpoint 3 exist
2 No Enpoint 3
3-1 Watt Meter Report Period:
If the setting is configured for 1hour (set value =720), the
DOUBLE SWITCH will report its instant power consumption
every 1 hour to the node of correspond Group. The maximum
interval to report its instant power consumption is 45 hours
(5s*32767/3600=45hr).
3-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), the DOU-
BLE SWITCH will report its Accumulated Power Consumption
(KW/h) every 1 hour to the node of correspond Group. The
maximum interval to report its Accumulated Power Consump-
tion (KW/h) is 227.55 days (10min*32767/1440=227.55 days).
3-3 Selected Relay
If Controller not using Multi_Channel command class to access
the relay of DOUBLE SWITCH, you may configure the select
value to react the Basic Command Class Binary Switch Com-
mand Class or Meter Command Class V3
3-3-1 Selected Relay1:
Only relay1 can be controlled and report.
3-3-2 Selected Relay 2:
Only relay2 can be controlled and report.
3-3-3 Selected Relay1 and Relay2: Default select is 3
Both relay1 and relay2 can be controlled and report.
Get Command parameter Raport to command sender
Meter Get KWh Relay1 KWh1+Relay2 KWh2
Meter Get Watt Relay1 W1+Relay2 W2
Meter Get Voltage Relay1 and Relay2 are the
same voltage
Meter Get Current Relay1 I1+Relay2 I2
Meter Get Power fac-
tor PF
Relay1
3-4 Edge and Pulse mode
Manual switch S1 and S2 can set to Edge mode or Pulse mode or
Edge-Toggle mode, default value is Edge mode.
3-4-1 Edge mode: this mode is suitable for the bi stable wall
switch that has indicator point on the switch, and the same
position correspond to same state of relay1 and relay2. if the
DOUBLE SWITCH relay change the state because of receiving
Z-Wave RF command, it may need two times of change (switch
on to off or switch off to on) to let relay back to the correspond
state.
3-4-2 Pulse mode: this mode is suitable for the toggle type wall
switch to swap the state of Relay1 or Relay2.
3-4-3 Edge-Toggle mode: this mode is suitable for the normal
bi-stable switch, every time when change the state of the wall
switch will also swap the state of Relay1 or Relay2.
3-5 Threshold of current for Load Caution
This is a warning when the current of load over the preset
threshold value, if the setting value is 750, when the load cur-
rent of Relay1 or Relay2 over this value, DOUBLE SWITCH will
send current meter report to the node of correspond Group,
the Range of the setting value is from 10 to 750, and the default
value is 750.
3-6 Threshold of KWh for Load Caution
This is a warning when the KWh of load over the preset thresh-
old value, If the setting value is 10000, when the Accumulated
Power Consumption of Relay1 or Relay2 over this value, DOU-
BLE SWITCH will send KWh Meter Report command to the
node of correspond Group, minimum value is 1KWh and default
value is 10000 kWh.
3-7 Restore switch state mode
Whenever the AC power return from lost, DOUBLE SWITCH
will restore the switch state which could be SWITCH OFF, LAST
SWITCH STATE, SWITCH ON. The default setting is LAST
SWITCH STATE.
3-8 Auto off timer:
Whenever DOUBLE SWITCH switches to on, the auto off timer
begin to count down. After the timer decrease to zero, it will
switch off automatically. However if Auto off timer is set as 0,
the auto off function will be disabled. The default setting is 0.
3-9 RF off command mode
Whenever a switch off command, BASIC_SET BINARY_
SWITCH_SET SWITCH_ALL_OFF, is received, it could be inter-
preted as 4 kinds of commands.
3-9-1 Switch Off: It switches to OFF state. The default setting
is Switch Off.
3-9-2 Ignore: The switch off command will be ignored.
3-9-3 Switch Toggle: It switches to the inverse of current state.
3-9-4 Switch On: It switches to ON state.
3-10 Existence of Endpoint3:
Multi-Channel Command is a good way to control relay1 and re-
lay2 of DOUBLE SWITCH individually. The endpoint3 of DOU-
BLE SWITCH is related to both relay1 and relay2. In some con-
dition it becomes redundant in Multi-Channel Command Class.
When the Existence of Endpoint3 is set as 2, the endpoint3 will
be disabled. The default value is 1.
Endpoint1 and Endpoint2 are fixed, only Endpoint3 is dynamic.
4.Protection Command Classes
DOUBLE SWITCH supports Protection Command Class ver-
sion 2, it can protect the switch against unintentionally control
by e.g. a child. And it can also protect the switch from being
turned off by setting it in “No RF Control” state.
After being set to “Protection by sequence” state, any inten-
tional pressing of On/Off button or S2/S2 should be hold longer
than 1 second, or the switch state will not change. However, the
operation of learn function does not change, because learning
will not be protected.
5. Firmware update over the air (OTA)
DOUBLE SWITCH is based on 500 series SoC and supports
Firmware Update Command Class, it can receives the updated
firmware image sent by controller via the Z-wave RF media. It
is a helpful and convenient way to improve some functions if
needed.
Troubleshooting
Symptom Cause of failure Recommendation
The Double Switch
is not working and
LED is off
1. The Switch is not
connected to the
Main Power.
2. The Double
Switch has broken
down
1. Check power
connections
2. Don’t open up
the Double Switch
and send it for
repair.
The Double Switch
LED is flashing, but
can not control the
ON/OFF Switch of
the load attached
Check if the load
connected into the
Switch has its own
ON/OFF switch
Set the ON/OFF
switch of the load
attached to ON
Reffering to assem-
bly drawing, check
if all conections are
correct.
The Switch LED is
flashing, but the
Detector cannot
control the Switch
1. Association not
carried out.
2. Same frequency
interference.
1. Carry out as-
sociation
2. Wait for a while
to re-try
LED is flashing, but
cannot control the
Switch
Overload occurs Remove the load
attached or check
max. load cannot
exceed 6.5A
DIMENSIONS

WWW.VEMMIO.COM
WARRANTY
This Limited Warranty applies to physical goods, and only for
physical goods, purchased from Vemmio (the „Physical Goods”).
This Limited Warranty of Vemmio, applies to products manufac-
tured and distributed by Vemmio.
PRODUCTS COVERED AND DURATION OF WARRANTY
Warranty Period: 12 months for business customer and 24
months for individual customer from the date of purchase.
The product purchased shall be free from defects in material
and workmanship from the date of purchase.
This Limited Warranty covers any defects in material or work-
manship under normal use during the Warranty Period.
PRODUCTION STATUS
Each product is manufactured from new parts.
TERMS OF THE WARRANTY
Vemmio warrants that the product you have purchased from
Vemmio or a Vemmio’s authorized reseller is free from defects
in materials and workmanship under normal use during the
warranty period. The warranty period begins on the day of pur-
chase. The warranty extends only to the original purchaser. It
is not transferable to anyone who subsequently purchases the
product from the original purchaser.
During the Warranty Period, Vemmio will repair or replace (at
the sole discretion of Vemmio), at no charge, products or parts
of a product that proves defective. Once the defected product,
during the guarantee period, is returned, it will be repaired or
replaced no later than within 30 days. The warranty period is
extended by the amount of days it has taken to repair or replace
the product. All used elements changed under the guarantee
become the property of Vemmio. The warranty period for re-
placed elements expires on the same date as the original war-
ranty period for the product. There is a possibility that it will not
be feasible to repair or replace the product ( for example when
the product is no longer a part of Vemmio’s offer). Should this
happen, Vemmio will repair/replace the product with parts/
product of similar technical characteristics. Such procedure will
result in fulfilling Vemmio’s warranty obligation against the cus-
tomer. It is not possible to have money returned by Vemmio for
the purchased product.
Warranty claim rated by Vemmio as unwarranted will be
charged for handling and servicing costs.
Vemmio may reject a warranty claim if:
• the product has not been operated according to its intended
purpose and the user manual,
• the returned product is incomplete,
• the cause of insufficient operation is other than a material or
production defect,
• warranty date has expired or if the customer can not provide
proof of purchase.
The Limited Warranty extends only to products purchased from
Vemmio or a Vemmio’s authorized reseller. The Limited War-
ranty does not extend to any product that has been damaged or
rendered defective (a) as a result of accident, misuse or abuse;
(b) as a result of an act of God; (c) by operation outside the us-
age parameters stated in the user manual; (d) by the use of parts
not manufactured or sold by Vemmio (e) by modification of the
product; (f) as a result of war or terrorist attack; or (g) as a result
of service by anyone other than Vemmio or a Vemmio’s author-
ized service center.
EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY,
VEMMIO MAKES NO OTHER WARRANTIES EXPRESSED
OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OR
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PUR-
POSE. VEMMIO EXPRESSLY DISCLAIMS ALL WARRANTIES
NOT STATED IN THIS LIMITED WARRANTY. ANY IMPLIED
WARRANTIES THAT MAY BE IMPOSED BY LAW ARE LIMIT-
ED TO THE TERMS OF THIS EXPRESS LIMITED WARRANTY.
LIMITED WARRANTY STATEMENT
VEMMIO is not liable for any damages caused by the product
or by the failure of the product to perform, including any lost
profits, lost savings, incidental damages, or consequential dam-
ages. VEMMIO is not liable for any claim made by a third party
or made by you for a third party.
This limitation applies whether damages are sought, or a claim
made, under this warranty or as a tort claim (including negli-
gence and strict product liability), a contract claim, or any other
claim. This limitation can not be waived or amended by any per-
son. This limitation of liability will be effective even if VEMMIO
or an authorized VEMMIO’S representative has been advised
by you of the possibility of any such damages.
HOW TO OBTAIN WARRANTY SERVICE?
Please contact us first through support@vemmio.com for ad-
vice because we are very often able to resolve issues/problems
without the need for warranty claim.
For a defect during the warranty period, you will need a proof of
purchase. Contact your place of purchase or a Vemmio’s author-
ized service center. Return the defective item, freight and insur-
ance prepaid, in the original packaging to your place of purchase.
Vemmio is not responsible for any loss or damages incurred in
shipping. A Vemmio Failure Analysis/Test Engineer or a Vem-
mio’s authorized reseller must validate all warranty claims.
WHAT IS NOT COVERED BY THIS WARRANTY?
Product purchased from anyone other than Vemmio or a Vem-
mio’s authorized reseller.
Routine cleaning or normal cosmetic and mechanical wear.
Damage from misuse, abuse or neglect including ingress of wa-
ter, dust or damage from dropping.
Damage from use outside the product’s usage or storage pa-
rameters.
Damage from use of parts not manufactured or sold by Vemmio.
Damage from modification or incorporation into other products.
Damage from repair or replacement of warranted parts by a ser-
vice provider other than a Vemmio’s authorized service provider.
Damage from failure to perform preventative maintenance
as imposed by the application environment (such as recurrent
cleaning in dusty surroundings).
DECLARATION OF CONFORMITY
The manufacturer Vemmio Sp. z o.o. declares under sole respon-
sibility that the product:
Marketing model: Double Switch
Regulatory model: DS-100
Brand name: Vemmio
is in conformity with the Low Voltage Directive 2009/95/EC,
EMC Directive 2004/108/EC, R&TTE Directive 1995/5/EC and
carries the CE marking accordingly.
The following harmonized standards were applied:
R&TTE (1995/5/EC)
EN 300 220-1: V2.4.1
EN 300 220-2: V2.4.1
EMC (2004/108/EC)
EN 301 481-1: V1.9.2
EN 301 489-3: V1.6.1
LVD (2006/95/EC)
EN 60950-1:2006 + A11:2009 + A1:2010 + A12:2011
Changes of modification not expressly approved by Vemmio Sp.
z o.o. for compliance could void the user’s authority to operate
the equipment.
FCC INTERFERENCE STATEMENT
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protec-
tion against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio com-
munications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on,
the user is encouraged to try to correct the interference by one
of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different
from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician
for help.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including
interference that may cause undesired operation.
FCC Caution: Any changes or modifications not expressly ap-
proved by the party responsible for compliance could void the
user’s authority to operate this equipment.
This transmitter must not be co-located or operating in conjunc-
tion with any other antenna or transmitter.
IN ACCORDANCE WITH ROHS 2011/65/EU
WARNING
Do not dispose of electrical appliances as unsorted municipal
waste, use separate collection facilities. Contact your local gov-
ernment for information regarding the collection systems avail-
able. If electrical appliances are disposed of in landfills or dumps,
hazardous substances can leak into the groundwater and get
into the food chain, damaging your health and well-being.
When replacing old appliances with new once, the retailer is
legally obligated to take back your old appliance for disposal at
least for free of charge.
Please note: Vemmio provides this publication “as is” without
warranty of any kind, either express or implied, including, but
not limited to implied warranties of merchantability or fitness
for a particular purpose. The published information in the man-
ual is subject to change without notice. Vemmio reserves the
right to make changes in the product design, layout, and driver
revisions without notification to its users. This version of the
installation guide supersedes all previous versions.
Although Vemmio has attempted to ensure the accuracy of the
content of this manual, it is possible that this document may
contain technical inaccuracies, typographical, or other errors.
Vemmio assumes no liability for any error in this publication,
and for possible damages, whether direct, indirect, incidental,
and consequential or otherwise, that may result from such er-
ror, including, but not limited to loss of data or profits.
Other manuals for DS-100
1
Other Vemmio Switch manuals
Popular Switch manuals by other brands

Micas
Micas M2-S6510-32C Hardware installation and reference guide

Sony
Sony MCS-8M operating instructions

AETEK
AETEK H51-044-30-150 Quick installation guide

ZyXEL Communications
ZyXEL Communications XGS1210-12 user guide

Siemens
Siemens RUGGEDCOM RSG2300F installation manual

Pilz
Pilz PSEN cs3.1p/M12 operating manual