5
GENERAL WIRING INSTRUCTIONS
WARNING –THE FAN AND ANY ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED
FROM THE POWER SUPPLY DURING INSTALLATION AND/OR MAINTENANCE. THE
EQUIPMENT MUST BE EARTHED.
1. All electrical connections should be made by a properly qualified electrician.
2. All wiring and connections must be carried out in accordance with current regulations.
3. To comply with safety standards, an all pole isolator switch with a contact gap of at least
3mm must be fitted adjacent to the fan.
4. Remove the cover from the terminal box to expose the main terminal block and the
thermal protection block (TK). The thermal protection device fitted is an automatic
resetting type which must always be included in the circuit. For ducted applications a
manual reset is required, an ancillary circuit will be required with the TK switch connected
into the circuit. See page 6 for instructions.
5. Connect the power supply from the local isolator (via any appropriate controls if fitted) to
the terminal box via the supplied cable gland using between 4.0mm and 7.0mm diameter
cable. Refer to the wiring diagrams and select the appropriate connections for the fan,
controller or other devices as being installed. If in doubt please ask.
6. CAUTION: In order to avoid a hazard due to inadvertent resetting of the thermal cut-out,
this appliance must not be supplied through an external switching device, such as a timer,
or connected to a circuit that is regularly switched on and off by the utility.
7. Ensure that all earth connections have been made.
8. After making connections inside the terminal box, replace the cover ensuring that the
sealing gasket is in place. Also ensure that all cable gland nuts, grommets etc. have been
used correctly to prevent the ingress of water.
NOTES ON RUNNING
Before Connecting the power supply and running the Fan Check…
Are all links and wiring complete as per wiring diagram?
Are all fixings secured?
Are all relevant guards fitted?
Are all Circuit protection devices fitted?
Are all Terminal box covers and sealing glands secured?
Are all Earth connections secured?
Check that no hazard exists for persons in the locality of the fan. Switch on the fan and check
that the fan rotation is correct as per the direction arrows on the fan plate/casing. If not isolate
power supply and check wiring. Check that the current (amps) taken by the fan does not exceed
the current shown on the rating plate.
INSTALLER AND ELECTRICAL CONTRACTOR RESPONSIBILITY
Vent-Axia Ltd, as suppliers of the equipment cannot be responsible for the final installation and
electrical connection of the product on site. We have made reasonable effort to offer guidance
and assistance but the installer and electrical contractor on site have a responsibility for ensuring
the equipment is safely and securely installed and electrically/mechanically safe in accordance
with statutory requirements.
The fans are supplied as a component to be incorporated into a ventilation system. The final
complete system installation that includes the fans MUST meet the requirements of:-
Low voltage Directive - 2014/35/EU
Machinery Directive - 2006/42/EC
Electromagnetic Compatibility Directive - 2014/30/EU
If the fan is installed in an area where there is possible danger to safety or health then guards
MUST be fitted.