CURRENT MONITORING INSTALLATION GUIDE
Solid-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Sensor Power Induced from the monitored conductor
Amperage Range 0.75 to 50 A continuous*
Insulation Class 600 VAC RMS (UL)
Frequency Range 50/60 Hz
Temperature Range -15° to 60°C (5°to 140°F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% typical
Status Output N.O. 0.2 A@120 VAC, polarity sensitive
O-State Resistance 1 MΩ
On-State Resistance 20 Ω
Terminal Block Max. Wire Size 14 AWG
Terminal Block Torque (nom.) 4 in-lbs (0.45 N-m)
Agency Approvals UL508 E150462
The product design provides for basic insulation only.
* When operating at 50 Hz, low threshold may be 0.9 A.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
WIRING EXAMPLE
H809 TM 809
DIMENSIONS
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the device at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections and relay between the sensor and the controller
(solid-state contact).
4. Route the conductor through the sensor’s center window and slip the assembly
into the mounting bracket.
5. Secure enclosure and reconnect power.
6. Calibrate sensor with load running normally.
 0.7"
(18 mm)
0.4”x 0.2”
Slot (x2)
2.8"
(71 mm)
1.7
(43 mm)
2.3"
(58 mm)
1.1"
(27 mm)
0.9"
(23 mm)
Removable/Adjustable Mounting Bracket
Motor
Fan or Pump
DDC CONTROLLER
DI
-
+
CONTACTOR
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com
TM
INSTALLATION GUIDE
H809
OPERATION
The H809 is a current-sensitive switching device that monitors current (amperage)
in the conductor passing through it. A change in amperage in the monitored
conducter that crosses the switch threshold plus the hysteresis value will cause the
resistance of the status output to change state, similar to the action of a mechanical
switch. The setpoint is adjustable through the action of a 20-turn potentiometer
(see CALIBRATION section). The status output is suitable for connection to building
controllers or other appropriate data acquisition equipment operating at up to 120
volts. The H809 requires no external power supply to generate its output.
TROUBLESHOOTING
Problem Solution
No Reading at
Controller
• Check sensor calibration (see above)
• Check for control power at sensor (<120 VDC)
• Check for amperage in monitored conductor (>0.75 A)
• Verify correct polarity
Setpoint screw has
no stops
• The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be most
sensitive. Repeat calibration above.
Both LEDs are lit Unit is out of calibration.Turn screw 20 turns CCW and recalibrate.
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
H68xx-5A CT
150A
300A:5A
2.5A
> 50 A (Sensor max.)
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
A. To monitor under-current (belt loss, coupling shear, status)
A
OK!
!
1. Turn setpoint screw
clockwise until Status
Open LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status Closed LED just
turns ON.
3. Turn the screw an
additional 1/4 turn
counter-clockwise for
operational margin.
B. To monitor over-current (mechanical problems, seized impeller)
3. Turn the setpoint
screw an additional
1/4 turn clockwise for
operational margin.
1. Turn setpoint screw
counter-clockwise until
Status Closed LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status Open LED just
turns ON.
OK!
STATUS
A
OK!
!
OK!
STATUS
1/4
Setpoint
+
+
1/4
Setpoint
Before beginning calibration, establish normal load conditions.
OK!
A
OK!
Then choose either A or B below.
< 0.75 A (Sensor Min.)
0.5A
4x
CALIBRATION
Setpoint
Status
Open
STOP
Setpoint Status
Closed
STOP
Setpoint Status
Closed
STOP
Setpoint
Status
Open
STOP
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com

This manual suits for next models

1

Other Veris Industries Relay manuals

Veris Industries Hawkeye 906 User manual

Veris Industries

Veris Industries Hawkeye 906 User manual

Veris Industries Hawkeye 740 User manual

Veris Industries

Veris Industries Hawkeye 740 User manual

Veris Industries Hawkeye 740 User manual

Veris Industries

Veris Industries Hawkeye 740 User manual

Veris Industries Hawkeye 806 User manual

Veris Industries

Veris Industries Hawkeye 806 User manual

Veris Industries Hawkeye 735 User manual

Veris Industries

Veris Industries Hawkeye 735 User manual

Veris Industries Hawkey 739 User manual

Veris Industries

Veris Industries Hawkey 739 User manual

Popular Relay manuals by other brands

Mikro DIN310 user manual

Mikro

Mikro DIN310 user manual

DAITEM SH701AX installation manual

DAITEM

DAITEM SH701AX installation manual

Basler BE1-67N instruction manual

Basler

Basler BE1-67N instruction manual

F&F BIS-410 manual

F&F

F&F BIS-410 manual

Panasonic LD Relays (ALD) Specifications

Panasonic

Panasonic LD Relays (ALD) Specifications

Omron G2RV -  1 datasheet

Omron

Omron G2RV - 1 datasheet

Circutor RGU-10 RAL manual

Circutor

Circutor RGU-10 RAL manual

ABB Relion 611 Series installation manual

ABB

ABB Relion 611 Series installation manual

Siemens 7UG0583-1CU20 operating instructions

Siemens

Siemens 7UG0583-1CU20 operating instructions

Circutor CBS-4C manual

Circutor

Circutor CBS-4C manual

Vitals Rs 50k Manual For Technical Use

Vitals

Vitals Rs 50k Manual For Technical Use

Crouzet HSV manual

Crouzet

Crouzet HSV manual

CARLO GAVAZZI BTM-T15-PLUS installation guide

CARLO GAVAZZI

CARLO GAVAZZI BTM-T15-PLUS installation guide

F&F BIS-411B-LED quick start guide

F&F

F&F BIS-411B-LED quick start guide

Honeywell RP470A installation instructions

Honeywell

Honeywell RP470A installation instructions

GE IFC53M instructions

GE

GE IFC53M instructions

ABB CT-AHS Safety instruction

ABB

ABB CT-AHS Safety instruction

Omron K2CM Series manual

Omron

Omron K2CM Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.