Vertiv Tech ECM3 Series User manual

ECM3 Series Outdoor Power System
User Manual
Version
V1.1
Revision date
December 31, 2017
BOM
31013576
Vertiv provides customers with technical support. Users may contact the nearest Vertiv local sales
office or service center.
Copyright © 2017 by Vertiv Tech Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Vertiv Tech Co., Ltd.
Address: Block B2, Nanshan I Park, No.1001 Xueyuan Road, Nanshan District, Shenzhen, 518055,
P.R.China
Homepage: www.VertivCo.com
E-mail: overseas.support@vertivco.com

Safety Precautions
To reduce the chance of accident, please read the safety precautions carefully before operation. The ‘Caution,
Notice, Warning, Danger’ in this book do not represent all the safety points to be observed, and are only
supplement to various safety points. Therefore, the installation and operation personnel must be strictly trained
and master the correct operations and all the safety points before operation.
When operating Vertiv products, you must strictly observe the safety rules in the industry, the general safety
points and special safety instructions specified in this book.
Electrical Safety
I. Hazardous voltage
Danger
Danger
Some components of the outdoor power system carry hazardous voltage in operation. Direct contact or indirect contact
through moist objects with these components will result in fatal injury.
Observe safety rules in the industry when installing theAC power system. The installation personnel must be
licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets,
bangles, rings.
When water or moisture is found in the cabinet, just turn off the power immediately. In moist environment,
precautions must be taken to keep moisture out of the power system.
Attach ‘Prohibit’warning label to the switches and buttons that are not permitted to operate during installation.
Danger
Danger
High voltage operation may cause a fire or electric shock. The connection and wiring of AC cables must be in compliance
with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.
Danger
Danger
To avoid electric shock hazard of outdoor environment and outdoor equipment, the non-professionals are prohibited to
operate or maintain the outdoor power system.
II. Tools
Warning
In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.

III. Thunderstorm
Danger
Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.
In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD
Note
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale
ICs. Before touching any plug-in board, PCB or IC chip, wear ESD wrist strap to prevent body static from damaging the
sensitive components. The other end of the ESD wrist strap must be well earthed.
V. Short circuit
Danger
Danger
During operation, never short the positive and negative poles of the DC distribution unit of the system or the non-grounding
pole and the earth. The power system is constant voltage DC power equipment, and short circuit will result in equipment
burning and endanger human safety.
VI. Reverse connection
Warning
Never connect reversely live line and neutral line of the AC input cables, or else the system will be damaged.
Check carefully the polarity of the cable and connection terminal when performing DC live operations.
As the operation space in the DC distribution unit is tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Use insulated tools.
In live operation, keep the arm, wrist and hand tense, so that when the tool in operation slips, the movement of
the human body and tool is reduced to a minimum.
Others
I. Sharp object
Warning
When moving equipment by hand, wear protective gloves to avoid injury by sharp object.

II. Cable connection
Warning
Notice
Note
Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.
III. Binding the signal lines
Warning
Notice
Note
The signal lines should be bound separately from heavy current and high voltage lines, with binding interval of at least
150mm.

Contents
Chapter 1 Overview ............................................................................................................................................................1
1.2 Composition & Configuration ................................................................................................................................1
1.2.1 Power subrack...........................................................................................................................................8
1.2.2 AC Distribution Unit (Optional).................................................................................................................10
1.2.3 DC Distribution Unit (Optional) ................................................................................................................11
1.2.4 Environment Monitoring System (Optional).............................................................................................11
1.2.5 Heating Unit (Optional)............................................................................................................................14
1.3 Technical Parameters.........................................................................................................................................14
1.4 Operating Principles............................................................................................................................................15
1.4.1 Heat Exchanger.......................................................................................................................................15
1.4.2 Air Conditioner.........................................................................................................................................16
1.5 Main Features.....................................................................................................................................................17
1.6 Typical Configurations ........................................................................................................................................18
Chapter 2 Installation ........................................................................................................................................................20
2.1 Safety Regulations..............................................................................................................................................20
2.2 Preparation.........................................................................................................................................................20
2.3 Mechanical Installation........................................................................................................................................22
2.3.1 Disassembling On Site ............................................................................................................................25
2.3.2 Opening And Closing Cabinet Door.........................................................................................................28
2.4 Electrical Installation...........................................................................................................................................29
2.4.1 Installing Power Subrack.........................................................................................................................29
2.4.2 Installing Rectifier ....................................................................................................................................29
2.4.3 Installing Battery......................................................................................................................................30
2.4.4 Connecting Cables ..................................................................................................................................31
2.4.5 Sealing Cable Entry Holes.......................................................................................................................34
2.4.6 Installing Base Cover Plate (Optional).....................................................................................................35
2.5 Installation Check................................................................................................................................................36
Chapter 3 Testing..............................................................................................................................................................37
3.1 Power-on ............................................................................................................................................................37
3.2 System Operation Status Check.........................................................................................................................37
3.3 Final Steps..........................................................................................................................................................38
Chapter 4 Maintenance.....................................................................................................................................................39
4.1 Routine Maintenance..........................................................................................................................................39
4.2 Replacing Parts...................................................................................................................................................40
4.2.1 Replacing Fan .........................................................................................................................................40
4.2.2 Replacing Heater.....................................................................................................................................41
4.2.3 Replacing Heat Exchanger......................................................................................................................42

4.2.4 Replacing Air Conditioner........................................................................................................................42
4.2.5 Replacing LED Lamp...............................................................................................................................43
4.2.6 Replacing Micro Switch ...........................................................................................................................44
Appendix 1 Spare Part List................................................................................................................................................45
Appendix 2 Schematic diagram.........................................................................................................................................46
Appendix 3 Wiring diagram...............................................................................................................................................50
Appendix 4 Glossary.........................................................................................................................................................54

Chapter 1 Overview 1
ECM3 Series Outdoor Power System User Manual
Chapter 1 Overview
ECM3 series integrated outdoor power system (‘power system’for short) has 11 models, see Table 1-1 for details..
The power system is specially used in outdoor to provide outdoor protection and operating environment for power
supplies and communication equipment. The power system is configured with thermal control unit, power subrack
and AC socket for user.
This chapter introduces the composition & configuration, technical parameters, operating principles and main features
of the power system.
Table 1-1 shows the cabinet type and dimensions.
Table 1-1 Cabinet type and dimensions
Cabinet model
Thermal control type
Dimensions (W ×D ×H)
ECM3-E18H-2/1
Heat exchanger
800mm ×800mm ×1800mm
ECM3-E18A-4/1
Air conditioner
800mm ×800mm ×1800mm
ECM3-E18A-4/2
650mm ×650mm ×1800mm
ECM3-P18M-1/1
Heat exchanger + air conditioner
800mm ×800mm ×1800mm
ECM3-B18A-1/1
Air conditioner type battery cabinet
800mm ×800mm ×1800mm
ECM3-B18A-8/2
650mm ×650mm ×1800mm
ECM3-E14H-1/1
Heat exchanger
800mm ×800mm ×1400mm
ECM3-E14A-4/1
Air conditioner
800mm ×800mm ×1400mm
ECM3-E14A-4/2
650mm ×650mm ×1400mm
ECM3-B14A-1/1
Air conditioner type battery cabinet
800mm ×800mm ×1400mm
ECM3-B14A-8/2
650mm ×650mm ×1400mm
1.2 Composition & Configuration
Composition
The power system consists of thermal control unit, power subrack, distribution unit and relevant mechanical parts.
There are three types of thermal control units for use to select: heat exchanger, air conditioner, and heat exchanger +
air conditioner.
Configuration of 1.8m cabinet
1. See Table 1-2 for the configuration of ECM3-E18H-2/1 power system.
Table 1-2 Configuration of ECM3-E18H-2/1 power system
Component
Configuration
Thermal control unit
Heat exchanger
1 set, standard configuration (max. heat exchanging capacity: 190W/K)
Lighting Unit
LED lamp
1 set, standard configuration
Micro switch
Power subrack
NetSure 731 power
subrack
1 set, standard configuration
AC socket (for user)
One 10A single-phase AC socket (standard configuration)
Environment monitoring
FSU
1 set, optional
Temperature & humidity
sensor
Smoke sensor
Water-logging sensor
AC distribution unit
1 set, optional
DC distribution unit
1 ~ 2 sets, optional
Heating unit
2 set, optional, power: 1260W
The structure of ECM3-E18H-2/1 power system is shown in Figure 1-1.

2 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
Heat exchanger
Power subrack
AC distribution unit
DC distribution unit
Reserved space
Heating unit (optional)
Figure 1-1 Structure of ECM3-E18H-2/1 power system
2. The configuration of ECM3-E18A-4/1 is same as that of ECM3-E18A-4/2, see Table 1-3 for details.
Table 1-3 Configuration of ECM3-E18A-4/1 and ECM3-E18A-4/2 power system
Component
Configuration
Thermal control unit
Intelligent outdoor air
conditioner
1 set, cooling capacity: 1500W, no heating function
Emergency ventilation unit
1 set, max. heat exchanging capacity: 1000W (temperature difference
between indoor and outdoor cabinet is 10°C )
Lighting Unit
LED lamp
1 set, standard configuration
Micro switch
Power subrack
NetSure 731 power
subrack
1 set, optional
AC socket (for user)
One 10A single-phase AC
socket
1 set, standard configuration
Environment monitoring
FSU
1 set, optional
Temperature & humidity
sensor
Smoke sensor
Water-logging sensor
AC distribution unit
1 set, optional
DC distribution unit
1 ~ 2 sets, optional

Chapter 1 Overview 3
ECM3 Series Outdoor Power System User Manual
The structure of ECM3-E18A-4/1 power system is same as that of ECM3-E18A-4/2 power system, as shown in
Figure 1-2.
Air conditioner
Power subrack
AC distribution unit
DC distribution unit
Reserved space
Figure 1-2 Structure of ECM3-E18A-4/1 and ECM3-E18A-4/2 power system
3. See Table 1-4 for the configuration of ECM3-P18M-1/1 power system.
Table 1-4 Configuration of ECM3-P18M-1/1 power system
Component
Configuration
Thermal control unit
(equipment
compartment)
Heat exchanger
1 set, max. heat exchanging capacity: 80W/K
Thermal control unit
(battery compartment)
Inteligent outdoor air
conditioner
1set, cooling capacity: 300W; no heating function
Lighting Unit
LED lamp
1 set, standard configuration
Micro switch
Power subrack
NetSure 731 power
subrack
1 set, optional
AC socket (for user)
One 10A single-phase AC
socket
1 set, standard configuration
Environment monitoring
FSU
1 set, optional
Temperature & humidity
sensor
Smoke sensor
Water-logging sensor
AC distribution unit
1 set, optional
DC distribution unit
1 set, optional
Heating unit in equipment compartment
1 set, optional, power: 600W
Note: The battery compartment space is reserved, standardly configured with two groups of battery

4 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
The structure of ECM3-P18M-1/1 power system is shown in Figure 1-3.
Heat exchanger
Power subrack
AC distribution unit
Reserved space
Air conditioner
Battery string
Heating unit (optional)
Figure 1-3 Structure of ECM3-P18M-1/1 power system
4. The configuration of ECM3-B18A-1/1 is same as that of ECM3-B18A-8/2, see Table 1-5 for details.
Table 1-5 Configuration of ECM3-B18A-1/1 and ECM3-B18A-8/2 power system
Component name
Configuration
Thermal control unit in battery
compartment
Intelligent outdoor air
conditioner
1 set, 300W cooling capacity, no heating
function
Lighting unit
LED lamp
1 set, standard configuration
Micro switch
Environment monitoring
Infrared sensor
1 set, optional
Temperature & humidity sensor
Smoke sensor
Water-logging sensor
Note: The battery compartment space is reserved, standardly configured with four groups of battery
The structure of ECM3-B18A-1/1 power system is same as that of ECM3-B18A-8/2 power system, as shown in
Figure 1-4.
Air conditioner
Battery string
Figure 1-4 ECM3-B18A-1/1 and ECM3-B18A-8/2 power system

Chapter 1 Overview 5
ECM3 Series Outdoor Power System User Manual
Configuration of 1.4m cabinet
5. See Table 1-6 for the configuration of ECM3-E14H-1/1 power system.
Table 1-6 Configuration of ECM3-E14H-1/1 power system
Component name
Configuration
Thermal control unit
Heat exchanger
1 set, standard configuration (max. heat exchanging capacity:
80W/K)
Lighting unit
LED lamp
1 set, standard configuration
Micro switch
Power subrack
NetSure 731 power subrack
1 set, optional
AC socket (for user)
One 10A single-phase AC socket
1 set, standard configuration
Environment monitoring
FSU
1 set, optional
Temperature & humidity sensor
Smoke sensor
Water-logging sensor
AC distribution unit
1 set, optional
DC distribution unit
1 set, optional
Heating unit
1 set, optional, power: 600W
The structure of ECM3-E14H-1/1 power system is shown in Figure 1-5.
Heat exchanger
Heating unit
Power subrack
AC distribution unit
DC distribution unit
Reserved space
Figure 1-5 ECM3-E14H-1/1 power system

6 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
6. The configuration of ECM3-E14A-4/1 power system is same as that of ECM3-E14A-4/2 power system, see Table
1-7 for details.
Table 1-7 Configuration of ECM3-E14A-4/1 and ECM3-E14A-4/2 power system
Component name
Configuration
Thermal control unit
Intelligent outdoor air conditioner
1 set, cooling capacity: 1500W, no heating function
Lighting unit
LED lamp
1 set, standard configuration
Micro switch
Power subrack
NetSure 731 power subrack
1 set, optional
AC socket (for user)
One 10A single-phase AC socket
1 set, standard configuration
Environment monitoring
FSU
1 set, optional
Temperature & humidity sensor
Smoke sensor
Water-logging sensor
AC distribution unit
1 set, optional
DC distribution unit
1 set, optional
The structure of ECM3-E14A-4/1 power system is same as that of ECM3-E14A-4/2 power system, as shown in
Figure 1-6.
Air conditoner
Power subrack
AC distribution unit
DC distribution unit
Reserved space
Figure 1-6 ECM3-E14A-4/1 and ECM3-E14A-4/2 power system
7. The configuration of ECM3-B14A-1/1 power system is same as that of ECM3-B14A-8/2 power system, see Table
1-8 for details.
Table 1-8 Configuration of ECM3-B14A-1/1 and ECM3-B14A-8/2 power system
Component name
Configuration
Thermal control unit
Intelligent outdoor air conditioner
1 set, cooling capacity: 300W, no heating function
Lighting unit
LED lamp
1 set, standard configuration
Micro switch
Environment monitoring
Infrared sensor
1 set, optional
Temperature & humidity sensor
Smoke sensor
Water-logging sensor
Note: The battery compartment space is reserved, standardly configured with two groups of battery

Chapter 1 Overview 7
ECM3 Series Outdoor Power System User Manual
The structure of ECM3-B14A-1/1 power system is same as that of ECM3-B14A-8/2 power system, as shown in
Figure 1-7.
Air conditioner
Battery space
Figure 1-7 ECM3-B14A-1/1 and ECM3-B14A-8/2 power system
8. Internal space configuration of power system.
Take 1.8m tri-cabinet three-user power system (configured with 300A power subrack) as an example, the internal
layout of the power system is shown in Figure 1-8.
Cabling space
Tri-cabinet three-user
Battery compartment (9U)
300A Subrack
power (11U)
AC DU(3U)
FSU (1U)
Reserved space (2U)
DC DU (3U)
BBU (2U)
Transmission (2U)
ODF (4U)
DC DU (3U)
BBU (2U)
ODF (4U)
DC DU (3U)
BBU (2U)
ODF (4U)
Fiber storage (1U)
Battery output
Fiber cable
Battery input
DC power
supply
AC input
AC input
Jump fiber
to RRU
Fiber cable
Jump fiber cable
Battery compartment (9U)
Battery compartment (9U)
Battery compartment (9U)
(2U) Cabling space
(2U)
DC power
supply
Cabling space (1U)
Cabling space (2U)
Reserved space (6U)
Transmission (2U)
Fiber storage (1U)
Reserved space (6U)
Cabling space (2U)
Fiber storage (1U)
Transmission (2U)
Reserved space (6U)
Jump fiber
to RRU
Figure 1-8 Internal space layout of 1.8m cabinet power system

8 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
The 1.8m battery cabinet can be configured with four battery strings at most. For integrated cabinet, max. two battery
strings can be configured in the battery compartment, and the equipment compartment can be configured with AC
distribution unit (AC DU for short) and DC distribution unit (DC DU for short) according to your need. For different
configuration, the user equipment space is different, respectively shown in Table 1-9 and Table 1-10.
Table 1-9 Internal space configuration list of 1.8m cabinet
Configuration of battery layers,AC DU and DC DU
User equipment space
Two layers of battery compartment
With AC DU and DC DU
3U ~ 6U
Without AC DU and DC DU
10U ~ 13U
Table 1-10 Internal space configuration list of 1.8m equipment cabinet
Configuration of power subrack, AC DU and DC DU
User equipment space
With power subrack
With AC DU and DC DU
20U ~ 23U
Without AC DU and DC DU
27U ~ 30U
Without power subrack
With DC DU
30U ~ 35U
Without DC DU
40U
Take 1.4m tri-cabinet three-user power system (configured with 300A power subrack) as an example, the internal
layout of the power system is shown in Figure 1-9.
300A Subrack
power (11U)
AC DU (3U)
FSU (1U)
DC DU (3U)
Reserved space (1U)
BBU (2U)
Transmission (2U)
ODF (2U)
DC DU (3U)
BBU (2U)
ODF (2U)
DC DU (3U)
BBU (2U)
ODF (4U)
Fiber storage (1U)
AC input
Fiber cable
Tri-cabinet three-user
Battery compartment (9U)
Battery compartment (9U)
Battery compartment (9U)
DC power
supply
Battery output
Fiber cable
Battery input
Cabling space (2U) Cabling space (2U)
Cabling space (1U)
Cabling space (1U)
Jump fiber
to RRU
AC input
DC power
supply Reserved space (2U)
Transmission (2U)
Fiber storage (1U)
Cabling space (2U)
Reserved space (2U)
Transmission (2U)
Fiber storage (1U) Jump fiber
to RRU
Jump fiber
cable
Figure 1-9 Internal space layout of 1.4m cabinet power system
The 1.4m battery cabinet can be configured with three battery strings at most. For equipment cabinet, the power
subrack, AC distribution unit (AC DU for short) and DC distribution unit (DC DU for short) can be configured according
to your need. For different configuration, the user equipment space is different, as shown in Table 1-11.
Table 1-11 Internal space configuration list of 1.4m equipment cabinet
Configuration of power subrack, AC DU and DC DU
User equipment space
With power subrack
With AC DU and DC DU
10U ~ 13U
Without AC DU and DC DU
17U ~ 20U
Without power subrack
With DC DU
20U ~ 25U
Without DC DU
30U
1.2.1 Power subrack
NetSure 731 A41-S7, Netsure 731 A61-S2 and NetSure 731 A61-S3 subrack power supplies are optional for the
power system. You can choose either one according to the actual power distribution requirement.
The layout of Netsure 731 A61-S2 and NetSure 731 A61-S3 power subrack are generally the same, an B-level SPD
is added to S2 based on the S3 structure, therefore, take Netsure 731 A61-S2 for example, the internal structure of

Chapter 1 Overview 9
ECM3 Series Outdoor Power System User Manual
the power subrack is shown in Figure 1-10. The structure of NetSure 731 A41-S7 power subrack is hown in Figure
1-11.
Non-priority load (user 2)
Battery MCB
Rectifier
C-level SPD B-level SPD
Grounding screw
AC input I AC input II
AC output N
AC output L
Non-priority load (user 1) Non-priority load (user 3)
Non-priority load (user 4)
Priority load (user 1)
Priority load (user 2) Priority load (user 3)
Priority load (user 4)
Figure 1-10 NetSure 731 A61-S2 power subrack
4 route of battery negative MCB
Grounding screw of battery positive pole
Battery MCB Load MCB
Positive grounding terminal of load output
Grounding terminal
3 route of AC output MCB
SPD (C)
AC input MCB I
Rectifier AC input MCB II
Figure 1-11 NetSure 731 A41-S7 power subrack

10 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
The technical parameters of the power subrack are described in Table 1-12.
Table 1-12 Technical parameters of power subrack
Parameter
Configuration
Parameter
Configuration
Controller
Model: M530S
AC distribution
3-phase input
Rectifier
Model: R48-3000e3
Netsure 731 A61-S2 max. configuration: 6;
Netsure 731 A61-S3 max. configuration: 6
Netsure 731 A41-S7 max. configuration: 4
DC distribution
Netsure 731 A61-S2, S3:
Priority load (PL):
User 1 ~ 3: MCB: 25A/1P ×1
User 4: MCB: 10A/1P ×2
Non-priority load (NPL):
User 1 ~ 3
MCB: 125A/1P ×1+16A/1P ×1+6A/1P ×1
User 4: MCB: 63A/1P ×1
Netsure 731 A41-S7:
Priority load (PL):
MCB: 25A/1P ×3+10A/1P ×2
Non-priority load (NPL):
MCB: 32A/1P ×8 + 16A/1P ×2 + 6A/1P ×1
AC input MCB
Netsure 731 A61-S2,S3: 63A/4P ×2;
Netsure 731 A41-S7: 63A/2P ×2
AC output MCB
Netsure 731 A61-S2,S3: 5 ×16A/1P, 4 ×
10A/1P
Netsure 731 A41-S7: 2 ×16A/1P, 1 ×
10A/1P
Battery MCB
4 ×125A/1P
AC SPD
1 piece (Netsure 731 A61-S2: B + C SPD)
DC SPD
1 piece
Controller mode
after BLVD
Netsure 731 A61-S2,S3: Controller power on
mode;
Netsure 731 A41-S7: Controller power off
mode
Refer to NetSure 731 A61 Subrack Power System User Manual and NetSure 731 A41 Subrack Power System User
Manual for the detailed technical parameters and configurations of the power subrack.
1.2.2 AC Distribution Unit (Optional)
The power system supports a three-phase or single-phase AC distribution unit (respectively see Figure 1-12 and
Figure 1-13), and can work with the power subrack. You may choose to configure as required.
Figure 1-12 Three-phase AC distribution unit
Figure 1-13 Single-phase AC distribution unit

Chapter 1 Overview 11
ECM3 Series Outdoor Power System User Manual
AC distribution parameters and configurations are respectively given in Table 1-13 and Table 1-14.
Table 1-13 Three-phase AC distribution parameters and configurations
Category
Parameter name
Technical parameter
AC distribution
Three-phase
Input system
TN or TT system, double-route three-phase five wire
Rated input voltage
Without an air conditioner: 346Vac ~ 433Vac
With an air conditioner: 380Vac ~ 398Vac (±10%)
Rated input current
50A (Max.)
Input MCB
2 ×63A/4P (manualy switch, with mechanical mutual interlock)
AC SPD
60kA (Max.)
AC output
2 ×16A/1P, 2 ×10A/1P
Table 1-14 Single-phase AC distribution parameters and configurations
Category
Parameter name
Technical parameter
AC distribution
Single-phase
Input system
TN or TT system, double-route single-phase three wire
Rated input voltage
Without an air conditioner: 200Vac ~ 250Vac
With an air conditioner: 220Vac ~ 230Vac (±10%)
Rated input current
95A (Max.)
Input MCB
2 ×125A/2P (manualy switch, with mechanical mutual interlock)
AC SPD
60kA (Max.)
AC output
5 ×16A/1P, 4 ×10A/1P
1.2.3 DC Distribution Unit (Optional)
The power system supports a DC distribution unit (see Figure 1-14), and can work with the power subrack. You may
choose to configure as required.
Figure 1-14 DC distribution unit
DC distribution parameters and configurations are given in Table 1-15.
Table 1-15 DC distribution parameters and configurations
Category
Parameter name
Technical parameter
DC distribution
Rated input voltage
53.5V
Priority load
Total current ≤50A
16A/1P × 4, 10A/1P × 2
Non-priority load
Total current ≤ 100A
32A/1P × 12, 6A/1P × 1
1.2.4 Environment Monitoring System (Optional)
The power system provides the FSU intelligent monitoring equipment, which controls environment parameter
acquisition such as micro switch (optional), temperature and humidity (optional), smoke (optional), water-logging
(optional), infrared (optional). In addition, it provides multiple routes of dry contact alarm port for user monitoring.
Table 1-16 describes the definition of relevant ports.

12 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
Table 1-16 Ports silkprint and description
Silkprint
Description
PE terminal
POWER 36-60VDC
Power input port, power input range: 36Vdc ~ 60Vdc
CONSOLE
Console port
12V
Output terminal of 12Vdc auxiliary power
AGND
Ground terminal of 12Vdc auxiliary power
V1+, V1M, V1-
V2+, V2M, V2-
Total battery string voltage port. V1+, V2+: positive battery terminal; V1M, V2M: battery middle
points; V1-, V2-: negative battery terminal
CH1 ~ CH8
AI1 ~ AI8, can be set to voltage, DC current or digital signal input channel
REL1 ~ REL4
Output common terminal of relays 1, 2, 3, 4
NO1 ~ NO4
Normally open node of relays 1, 2, 3, 4, can be set to normally closed node through internal
jumpers
DI1 ~ DI12
DI port, can be voltage or digital signal input channel
DI13 ~ DI16
Water detection input
COM1 ~ COM9
Serial ports 1 ~ 9, supporting RS485 communication mode
COM10
Serial ports 10, supporting RS232 communication mode
CONSOLE
Port standard: RS232; baud rate:115200bps, N, 8, 1; non-isolation
Micro SD
Micro SD card slot, max. 32G Micro SD card can be inserted into the slot to expand the storage
space of the monitoring equipment
USB
USB port, for connecting modem
LAN1/2/3/4
10M/100M self-adaptive Ethernet port
The FSU acquires power monitoring information through RS485 port, and uploads information of components such
as heat exchanger and air conditioner through internal RS485 port. The FSU universally processes and transmits the
information to user monitoring system through Ethernet remote communication port. The appearance and port
position of the FSU are shown in Figure 1-15.
GND
Power port
Console port
Battery string
voltage input port
DI port
Relay output
Smoke
Serial ports 1 ~ 10
USB port
SD card slot
Ethernet ports 1 ~ 4
Waterlogging
AI port
Figure 1-15 ECCUP appearance and port positions
For detailed technical parameters and configuration of FSU, please refer to FSU-2808IM Monitoring Equipment
Installation And Commissioning Manual.
Sensor Introduction
Micro switch
Each cabinet door can be configured with a micro switch. When the door is open, the system will generate a door
open alarm. The appearance of the micro switch is shown in Figure 1-16.
Figure 1-16 Appearance of micro switch

Chapter 1 Overview 13
ECM3 Series Outdoor Power System User Manual
Temperature & humidity sensor
A temperature & humidity sensor can be configured to each cabinet for detecting the temperature and humidity of
internal cabinet, and providing temperature basis for the system running control. The appearance of the temperature
& humidity sensor is shown in Figure 1-17.
Figure 1-17 Appearance of temperature & humidity sensor
Smoke sensor
A smoke sensor can be selected for each cabinet. When an unexpected failure occurred in the system cabinet and
producing smoke whose concentration reaches the sensor setting, the system will generate a smoke alarm. The
appearance of the smoke sensor is shown in Figure 1-18.
Figure 1-18 Appearance of smoke sensor
Water-logging sensor
The system provides a water-logging sensor as an option, which can only be configured in the main cabinet. When
the cabinet water level reaches the submerged position of that sensor, an water-logging alarm will be generated. The
appearance of the water-logging sensor is shown in Figure 1-19.
Figure 1-19 Appearance of water-logging sensor
Infrared sensor
The system provides an infrared sensor as an option, which can only be configured in the battery cabinet. The
appearance of the infrared sensor is shown in Figure 1-20.
Figure 1-20 Appearance of infrared sensor

14 Chapter 1 Overview
ECM3 Series Outdoor Power System User Manual
1.2.5 Heating Unit (Optional)
The power system can be configured with a heating unit; its appearance is shown in Figure 1-21.
Figure 1-21 Appearance of heating unit
The heating unit consists of the Positive Temperature Coefficient (PTC) heater, fan, temperature relay, fuse and
installation cover. It uses a built-in fan to release the heat produced by the heater to the cabinet, while the heater
starts or stops automatically according to the cabinet temperature.
1.3 Technical Parameters
The technical parameters of the power system are listed in Table 1-17.
Table 1-17 Technical parameters of the power system
Parameter
Specifications
Environment
parameter
Temperature
Operating temperature
Without heating:-10°C ~ +45°C
With heating: -40°C ~ +45°C
Storage temperature
-40°C ~ +70°C
Relative
humidity
Operating relative
humidity
5%RH ~ 95%RH (40°C ±2°C )
Storage relative
humidity
≤ 95%RH (40°C no condensation)
Altitude
≤2000m (derating is necessary above 2,000m; The maximum
working temperature decreases 1°C when the altitude increases
every 200m)
Solar radiation
1120W/m2
Application environment
Over-voltage level: II; pollution level: 2
Noise
≤60dB (at a distance of 1.5m)
Protection level
IP45
Mechanical
parameter
Dimensions
(H ×W ×D)
Single
cabinet
ECM3-18
1800mm ×800mm ×800mm
1800mm ×650mm ×650mm
ECM3-14
1400mm ×800mm ×800mm
1400mm ×650mm ×650mm
Mechanical
parameter
Dimensions
(H ×W ×D)
Battery
compartment
ECM3-18
Independent battery compart:
Four layers in total: 355mm ×780mm ×580mm/layer (1800mm ×
800mm ×800mm);
355mm ×630mm ×560mm/layer (1800mm ×650mm ×650mm)
Battery compartment (equipment + battery):
Two layers in total: 330mm ×780mm ×580mm/layer (1800mm ×
800mm ×800mm)
Table of contents
Other Vertiv Tech Power Supply manuals