Vertiv Liebert CRV CCD25 User manual

Liebert® CRV CCD25 and CCD35
User Manual (Original Instructions)
50 Hz, Condenser

Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-emea/support/ for additional assistance.
The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

TABLE OF CONTENTS
1 Important Safety Instructions 1
2 Nomenclature and Components 3
2.1 Model Number Nomenclature 3
2.2 Main Components 4
2.2.1 Fan 4
2.2.2 Heat Exchanger 4
2.2.3 Low Ambient Kit 4
2.3 Accessories 5
2.4 Dimensions and Weights 6
2.5 Operation Environment 7
2.6 Storage Environment 7
3 Pre-installation Preparation 9
3.1 Moving the Unit 10
3.2 Unpacking the Unit 10
4 Installation 11
4.1 Installation Notes 11
4.2 Installing the Unit 11
4.2.1 Vertical Airflow Installation 11
4.2.2 Horizontal Airflow Installation 15
4.3 Installing the Low Ambient Kit 19
4.4 Connecting Pipelines 19
4.5 Connecting Power Cables and Communications Cable 20
4.5.1 Connecting Power Cable for Condenser 20
4.5.2 Connecting Power Cable for the Low Ambient Kit 24
4.5.3 Connecting Communications Cable for Condenser 26
4.6 Charging Refrigerant and Adding Lubricating Oil 27
5 Maintenance and Troubleshooting 29
5.1 Maintenance 30
5.1.1 Refrigeration System 30
5.1.2 Heat Exchanger 30
5.1.3 Fan 30
5.2 Troubleshooting 30
6 Appendices 33
Appendix A: Conformity to EU Directives 33
Appendix B: Technical Support and Contacts 34
iii
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

iv
This page intentionally left blank
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

1 Important Safety Instructions
NOTE: Before moving, installing or servicing this unit, please read the Safety Instructions sheet provided as a
separate document shipped with the unit.
NOTE: The Vertiv™ Liebert® CRV CCD25 and CCD35 condensers are for outdoor use only.
1 Important Safety Instructions 1
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

1 Important Safety Instructions
2
This page intentionally left blank
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

2 Nomenclature and Components
2.1 Model Number Nomenclature
The following tables describe the model number for Vertiv™ Liebert® CRV CCD25 and CCD35 condensers.
Model Number
1 2 3 4 5 6 7 8 9 10 11
C C D 2 5 4 H - 0 0 A
Table 2.1 CCD25 Model Number Example
Digit Variable Description of Variable
1
CCD Liebert® CRV condenser2
3
4
25, 35 Model number
5
6 4 400 V, 3-phase, 50 Hz, CE
7 H High ambient temperature (-5 °C to 52 °C (23 °F to 125.6 °F))
8 - Separator
9 0 R410A refrigerant
10 0 Free digit
11 A Revision
Table 2.2 CCD25 and CCD35 Model Number Digit Definitions
2 Nomenclature and Components 3
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

2.2 Main Components
2.2.1 Fan
The EC axial fan uses low-noise fan blades and a high-performance three-phase motor.
2.2.2 Heat Exchanger
The finned-tube heat exchanger provides high heat-dissipating efficiency and is convenient for maintenance.
2.2.3 Low Ambient Kit
The low ambient kit consists of a receiver with four heater belts, a head pressure valve, a safety valve, a check valve, and a
pressure switch. The kit is designed to maintain proper operating pressure in outdoor temperature down to -35 °C (-31 °F).
The low ambient kit is an optional component and is field-installed.
Figure 2.1 Diagram of Condenser with Low Ambient Kit
Item Description Item Description
1 Condenser 7 Liquid pipe
2 Discharge pipe 8 Receiver
3 Refrigerant flow direction 9 Check valve
4 Outdoor environment 10 Head pressure valve
5 Indoor environment 11 Safety valve
6 Evaporator 12 Pressure switch
Receiver
The receiver stores refrigerant to help fulfill the needs for low temperature load in winter and high temperature load in
summer. There are three connection ports in the receiver to connect refrigerant inlet pipe, refrigerant outlet pipe, and safety
valve. Two sight glasses are also installed on the receiver to observe the refrigerant level in the receiver conveniently.
2 Nomenclature and Components
4
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Head Pressure Valve
The head pressure valve is a three-way modulating valve that responds to discharge pressure. When the discharge pressure
falls below a certain value, the discharge port is opened and the discharge gas bypasses the condenser. When the discharge
pressure is high, the discharge port is closed and there is full liquid flow to the condenser.
During the soldering process, care must be taken not to overheat and damage the valve.
Figure 2.2 Structure Diagram of Head Pressure Valve
Item Description
1 Connected with discharge pipe
2 Connected with condenser
3 Connected with receiver
Heater Belt
The receiver is equipped with four heater belts which consume a total power of 300 Watts. The heater belt is controlled by
the pressure of refrigerant in the receiver. When the pressure is lower than 1.4 MPa (203.1 psig), the heater belt will start
heating. When the pressure is higher than 1.9 MPa (275.6 psig), the heater belt will stop heating.
Pressure Switch
Pressure switch controls the heater belt. When the refrigerant pressure in the receiver is lower than 1.4 MPa (203.1 psig), the
pressure switch will be closed and the heater belt will start working. When the refrigerant pressure in the receiver is higher
than 1.9 MPa (275.6 psig), the pressure switch will be opened and the heater belt will stop working.
Check Valve
Check valve is installed between the head pressure valve and the receiver on the liquid line, to prevent the refrigerant from
flowing back to the condenser. The arrow on the valve indicates the direction of the flow and it should point towards the
receiver.
2.3 Accessories
The accessories provided with the condenser are listed in the table below.
2 Nomenclature and Components 5
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Component Quantity
Leg for condenser 4
M6 x 16 Phillips hex head screw 20
User manual 1
EU declaration of conformity 1
Table 2.3 Accessories of the Condenser
The accessories provided with the low ambient kit are listed in the table below.
Component Quantity
Cable gland 1
EU declaration of conformity 1
Table 2.4 Accessories of the Low Ambient Kit
2.4 Dimensions and Weights
Condenser Model
Unit Dimensions (W x D x H)
mm (in.) without legs, with
fan
Shipping Dimensions (W x D
x H) mm (in.) Net Weight kg (lb)
Shipping Weight kg
(lb)
CCD25
1562 × 830 × 1272
(61.5 x 32.7 x 50.1)
1651 × 916 × 1486
(65 x 36.1 x 58.5)
120 (264.6) 195 (429.9)
CCD35
2362 × 830 × 1272
(93 x 32.7 x 50.1)
2451 × 916 × 1486
(96.5 x 36.1 x 58.5)
175 (385.8) 273 (601.9)
Low ambient kit
1270 × 280 × 554
(50 x 11 x 21.8)
1356 × 666 × 430
(53.4 x 26.2 x 16.9)
34 (75.0) 62 (136.7)
Table 2.5 Dimensions and Weights of Condenser
2 Nomenclature and Components
6
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

2.5 Operation Environment
Item Requirements
Installation
position
The maximum equivalent pipe length between the indoor unit and the condenser is 120 m (393.7 ft)
Vertical difference: -8 m (-26.2 ft) ≤ ΔH ≤ 30 m (98.4 ft)
Installation
mode
Standard condenser: horizontal airflow installation and vertical airflow installation
Condenser with low ambient kit: vertical airflow installation
Ambient
temperature
Standard condenser: -20 °C to 48 °C (-4 °F to 118 °F) . Unit remains operational up to 52 °C (125.6 °F) with reduced capacity
Condenser with low ambient kit: -35 °C to 48 °C (-31 °F to 118 °F)
Ambient
humidity Outdoor: 5% RH to 95% RH
Operation
power AC 400V 3Ph+N+PE 50Hz. The voltage tolerance is 10%
Altitude ≤ 1000 m (3280.8 ft). Derating is required if the altitude exceeds 1000 m (3280.8 ft)
Protection
level IPX4
Note:
•The value of vertical difference is positive if the condenser is installed higher than the indoor unit; otherwise the value is negative
•If the altitude is higher than 1000 m (3280.8 ft), please contact Vertiv™
Table 2.6 Operation Environment
NOTE: When the condenser is used with a low ambient kit, the condenser must be installed in vertical airflow
direction.
2.6 Storage Environment
Item Requirements
Storage
environment Store the unit in its original factory packaging, in a clean indoor environment with good ventilation and with no dust
Ambient
temperature -40 °C to +70 °C (-40 °F to 158 °F)
Ambient
humidity 5% RH to 95% RH
Storage time The total storage time should not exceed 6 months. Otherwise, contact VertivTM to check that the unit is in good condition
Table 2.7 Storage Environment
2 Nomenclature and Components 7
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

2 Nomenclature and Components
8
This page intentionally left blank
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

3 Pre-installation Preparation
WARNING! Risk of improper moving. Can cause serious injury or death. Building and equipment damage may
also result. Use only lifting equipment that is rated for the unit weight by an OSHA-certified rating
organization. The center of gravity varies depending on the unit size and selected options. The slings must
be equally spaced on either side of the center of gravity.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, or remove packaging from the unit in preparation for unit installation.
NOTICE
Risk of improper lifting. Can cause equipment damage. Make sure that the spreader bars are wider than the
unit. If the spreader bars are too short, the slings may crush the unit.
NOTICE
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures
and contact damage.
Upon arrival of the unit and before unpacking:
•Verify that the labeled equipment matches the bill of lading.
•Carefully inspect all items for visible or concealed damage.
•Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv™ or to your sales
representative.
3 Pre-installation Preparation 9
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

3.1 Moving the Unit
It is recommended to use mechanical transport equipment such as forklift or crane when unloading and transferring the
condenser closest to the installation site.
When a forklift is used, insert the tines of the forklift in the direction as shown in the figure below.
Figure 3.1 Inserting the Forklift in this Direction
3.2 Unpacking the Unit
Unpacking the Condenser
1. Pull straight the hooks on the top and side wooden panels using a claw hammer.
2. Remove the top and side wooden panels and foam from the condenser. Do not remove the protection
cardboard of the fins until the condenser is in its installation position.
Unpacking the Low Ambient Kit
1. Pull straight the hooks on the top and side wooden panels using a claw hammer.
2. Remove the top and side wooden panels from the low ambient kit. Loosen the clamp that secures the kit to the
bracket and then remove the kit.
3 Pre-installation Preparation
10
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

4 Installation
4.1 Installation Notes
•Vertiv™ Liebert® CRV CRV CCD25 and CCD35 condensers are used with Vertiv™ Liebert® CRV CRD25 and
CRD35 row-based cooling units. Read Vertiv™ Liebert® CRV CRD25 and CRD35 Row-Based Cooling Units User
Manual before installing and using the CCD25 and CCD35 condensers.
•Do not install the unit in the environment with noise restrictions.
•Do not place the unit close to vapors, hot gases, and waste gases.
•Install the unit in a clean place and keep it away from dusts and foreign objects.
•When the ambient temperature is lower than - 20 °C (-4 °F ), the low ambient kit needs to be used. The low
ambient kit can only be used on the outdoor unit that has been installed in vertically upward direction.
4.2 Installing the Unit
4.2.1 Vertical Airflow Installation
Mount the condenser on suitable support in accordance with local codes. Secure the stands to the mounting surface using a
field supplied bolt in each of the two 12 mm (0.47 in.) holes in each stand.
NOTE: A 4000 mm (157.5 in.) clearance is required above the condenser air outlet.
Figure 4.1 Dimensions of Condenser for Vertical Airflow Installation (CCD25)
4 Installation 11
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Item Description Item Description
1 1562 mm (61.5 in.) 4 906 mm (35.7 in.)
2 1246 mm (49.1 in.) 5 1272 mm (50.1 in.)
3 454 mm (17.9 in.)
Figure 4.2 Dimensions of Condenser for Vertical Airflow Installation (CCD35)
Item Description Item Description
1 2362 mm (93.0 in.) 4 906 mm (35.7 in.)
2 1246 mm (49.1 in.) 5 1272 mm (50.1 in.)
3 454 mm (17.9 in.)
Figure 4.3 Dimensions of Condenser Stand for Vertical Airflow Installation (CCD25)
4 Installation
12
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Item Description Item Description
1 1325.6 mm (52.2 in.) 4 75 mm (3.0 in.)
2 1120 mm (44.1 in.) 5 75 mm (3.0 in.)
3Ob-round: 12 mm x 20 mm (0.47 in.
x 0.79 in.)
Figure 4.4 Dimensions of Condenser Stand for Vertical Airflow Installation (CCD35)
Item Description Item Description
1 2126 mm (83.7 in.) 4 75 mm (3.0 in.)
2 1120 mm (44.1 in.) 5 75 mm (3.0 in.)
3Ob-round: 12 mm x 20 mm (0.47 in.
x 0.79 in.)
4 Installation 13
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Figure 4.5 Vertical Airflow Installation Space Requirements (CCD25)
Item Description
1 Minimum: 915 mm (36 in.)
2 Minimum: 1200 mm (47.2 in.)
4 Installation
14
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Figure 4.6 Vertical Airflow Installation Space Requirements (CCD35)
Item Description
1 Minimum: 915 mm (36 in.)
2 Minimum: 1200 mm (47.2 in.)
4.2.2 Horizontal Airflow Installation
Mount the condenser on suitable other support in accordance with local codes. Secure the unit to the mounting surface
using a field supplied bolt in each of the four 10 mm (0.39 in.) holes in sheet metal.
4 Installation 15
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual

Figure 4.7 Dimensions of Condenser for Horizontal Airflow Installation (CCD25)
Item Description Item Description
1 1562 mm (61.5 in.) 3 1272 mm (50.1 in.)
2 830 mm(32.7 in.)
Figure 4.8 Dimensions of Condenser for Horizontal Airflow Installation (CCD35)
4 Installation
16
Vertiv™ Liebert® CRV CCD25 and CCD35 CondensersUser Manual
This manual suits for next models
1
Table of contents
Other Vertiv Heat Pump manuals
Popular Heat Pump manuals by other brands

Daikin
Daikin RQYQ140-180PY1 Service manual

BSVILLAGE
BSVILLAGE Hayward Micro Installation instructions manual

Nibe
Nibe AG-WT10 series Installer manual

Johnson Controls
Johnson Controls UC installation manual

Daikin
Daikin Altherma R Hybrid Installer's reference guide

Econar
Econar GeoSource Ultra GW Series Installation and operating instructions