manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Vertiv
  6. •
  7. Rack & Stand
  8. •
  9. Vertiv MPX PRC User manual

Vertiv MPX PRC User manual

Other Vertiv Rack & Stand manuals

Vertiv VE Series User manual

Vertiv

Vertiv VE Series User manual

Vertiv Knurr DCM User manual

Vertiv

Vertiv Knurr DCM User manual

Vertiv SmartAisle 12-21HE/U User manual

Vertiv

Vertiv SmartAisle 12-21HE/U User manual

Vertiv eSure 60017372 User manual

Vertiv

Vertiv eSure 60017372 User manual

Vertiv 24BA1200-23 User manual

Vertiv

Vertiv 24BA1200-23 User manual

Vertiv NetSure 48BA1200-19 User manual

Vertiv

Vertiv NetSure 48BA1200-19 User manual

Vertiv SmartAisle-SwitchTube 19 Core 320mm 7-12HE/U User manual

Vertiv

Vertiv SmartAisle-SwitchTube 19 Core 320mm 7-12HE/U User manual

Vertiv DCF 48U Installation and maintenance instructions

Vertiv

Vertiv DCF 48U Installation and maintenance instructions

Vertiv DCE E42611 User manual

Vertiv

Vertiv DCE E42611 User manual

Vertiv VP8641 User manual

Vertiv

Vertiv VP8641 User manual

Vertiv KMMLED156 User manual

Vertiv

Vertiv KMMLED156 User manual

Vertiv SmartAisle 03.029.214 Series User manual

Vertiv

Vertiv SmartAisle 03.029.214 Series User manual

Vertiv Smaract User manual

Vertiv

Vertiv Smaract User manual

Vertiv Knurr Miracel 2 User manual

Vertiv

Vertiv Knurr Miracel 2 User manual

Vertiv Knurr PowerTrans2 User manual

Vertiv

Vertiv Knurr PowerTrans2 User manual

Vertiv RMPSU User manual

Vertiv

Vertiv RMPSU User manual

Vertiv KMMLED156 Installation and maintenance instructions

Vertiv

Vertiv KMMLED156 Installation and maintenance instructions

Vertiv Knurr DCM Heavy Duty Rack User manual

Vertiv

Vertiv Knurr DCM Heavy Duty Rack User manual

Vertiv MPE User manual

Vertiv

Vertiv MPE User manual

Vertiv Knurr DCM User manual

Vertiv

Vertiv Knurr DCM User manual

Vertiv NetSure 48BA1200-23 User manual

Vertiv

Vertiv NetSure 48BA1200-23 User manual

Vertiv MPH2 User manual

Vertiv

Vertiv MPH2 User manual

Vertiv Avocent User manual

Vertiv

Vertiv Avocent User manual

Popular Rack & Stand manuals by other brands

Dynex DX-MP3MT Quick setup guide

Dynex

Dynex DX-MP3MT Quick setup guide

Konig & Meyer 24185 manual

Konig & Meyer

Konig & Meyer 24185 manual

ECG LD 326501 instruction manual

ECG

ECG LD 326501 instruction manual

Philips SB7S19S/00 quick start guide

Philips

Philips SB7S19S/00 quick start guide

Woodline KIT-250 lb instructions

Woodline

Woodline KIT-250 lb instructions

ricoo S1222 installation instructions

ricoo

ricoo S1222 installation instructions

Kanto P301 user manual

Kanto

Kanto P301 user manual

VidaBox VB MNT FFS2 installation guide

VidaBox

VidaBox VB MNT FFS2 installation guide

PROEL PLWIN60C user manual

PROEL

PROEL PLWIN60C user manual

AllMounts PLB-43S instruction manual

AllMounts

AllMounts PLB-43S instruction manual

VMP VH-001 instruction sheet

VMP

VMP VH-001 instruction sheet

Nederman SYSTEM 920/400 instruction manual

Nederman

Nederman SYSTEM 920/400 instruction manual

Glasdon ORBIS POST MOUNTING KIT installation guide

Glasdon

Glasdon ORBIS POST MOUNTING KIT installation guide

Songmics LGR105 manual

Songmics

Songmics LGR105 manual

Grape GM401 user manual

Grape

Grape GM401 user manual

FourStarGroup 11225296 manual

FourStarGroup

FourStarGroup 11225296 manual

CHIEF FLR100 installation instructions

CHIEF

CHIEF FLR100 installation instructions

FEC XDCAM EX PMW-EX30 manual

FEC

FEC XDCAM EX PMW-EX30 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

SL-20839_REV1
590-1625-501A
1
MPX™ PRC
Quick Installation Guide
Before assembling and installing a
Liebert® MPX™, read and understand all
warnings and cautions in the Liebert®
MPX™ User Manual - Global Applications
which can be downloaded at www.
VertivCo.com.
Vertiv strongly recommends that the
MPX power entry module (PEM) be
installed by an individual who is properly
trained and qualified to perform electrical
work.
WARNING: The Liebert MPX contains
high voltage that can cause serious
personal injury or death. The unit must be
installed in a restricted-access location.
NOTE: If you need support for your MPX
power rail chassis (PRC), contact a Vertiv
representative. The MPX PRC contains no
user-serviceable parts. Never work alone.
De-energize the input power and discon-
nect power connections to all equipment
in the rack before installing a Liebert MPX
or connecting input power to the unit.
ASSEMBLY
Tools Required
• Phillips® (Tip Size 2) screwdriver
• 5 mm Allen wrench
To assemble and install the MPX
PRC:
1. Attaching an MPX PRC to the
cabinet
For 78.84 in (2000 mm) racks, attach
two mounting brackets to the side
horizontal sections A1 for each MPX
PRC using an Allen wrench. For
86.61 in (2200 mm) racks, attach
two mounting brackets to a vertical
section A2.
NOTE: L-shaped brackets are used
exclusively with Knurr® Miracel™ racks.
L- or Z-shaped brackets can be used
for racks from other manufacturers.
2. Placing the mounting buttons
Insert spring nuts into the rear of
the MPX PRC. Tighten the screws
through the mounting buttons and
into the spring nuts using a Phillips®
(
Tip Size 2
) screwdriver.
Z-shaped bracket L-shaped bracket
MPX PRC Bracket Vertical Install (L-shaped Bracket Shown)
Typical rack upright
1
2
VertivCo.com |Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2016 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or
registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
2
MPX™ PRC
Quick Installation Guide
SL-20839_REV1
590-1625-501A
3. Securing the MPX™ PRC
Insert mounting buttons through the
bracket cutout and slide it down into
the slot to secure it.
4. Connecting the grounding
cable (optional)
WARNING: Do not connect input
power to the MPX PEM until the
Liebert MPX is fully assembled and
mounted in place. As soon as input
power is connected to the MPX PEM,
the contacts on the underside are live
with hazardous voltage and the MPX
PRC carries live hazardous voltage.
Insert a spring nut into the rack frame
near the grounding point. Attach a
ground wire to the rack with a screw,
washer and lock washer, securing
the screw to the rack’s frame with
the spring nut. Use a second field-
supplied screw, washer and lock
washer to secure the ground wire to
the MPX PRC at the connection point
marked with an earth-ground symbol.
NOTE: For instructions on how to
install an MPX PEM and an MPX
branch receptacle module (BRM)
onto the MPX PRC, see the MPX™
PEM Quick Installation Guide and
the MPX BRM™ Quick Installation
Guide. For product details, see
the
Liebert® MPX™ User Manual -
Global Applications
which can be
downloaded at www.VertivCo.com.
4
Typical rack upright
3