VES ABM 315/4-1 User manual

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08702 404340 Fax: 08702 404550 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
AIRBEAM Wall Extract Units
Installation, Operation and Maintenance Manual
ORIGINAL INSTRUCTIONS
!
Contents Page
1Introduction 1
2 Receipt of Goods 1
3 Installation 1
4 Wiring 2
5 Maintenance 3
1 Introduction
The AIRBEAM series is a range of extract wall units, with a
duty range of between 0.11 and 1.2m³/s. The range offers an
unobtrusive design, with a number of outlet/housing options.
Standard operating temperature of the unit is -20 to +50°C
and the fans are rated at IP54.
For further technical details regarding dimensions and
weights contact VES on 08702 404340, quoting the sales
order (SO) number and the unit type as found on the unit
nameplate or visit www.ves.co.uk.
2 Receipt of Goods
Immediately upon receipt of goods check for possible
damage in transit paying particular attention to fan impeller.
Prior to installation please check to ensure smooth rotation
of the impeller after transit. Also check to ensure that any
ancillary items are included. These will normally be
supplied fitted or in the case of small items taped to the
unit.
In the event of any damage having occurred or if any item is
found missing, it is essential to inform VES Andover Ltd.
within 3 working days of delivery quoting sales order (SO)
number and the unit type as found on the unit nameplate.
After this period we will be unable to accept any claim for
damaged or missing goods.
Fig. 1 Unit arrangement
Top: Louvre unit
Bottom: Cowl unit
3 Installation
The entire system must be considered for safety purposes
and it is the responsibility of the installer to ensure that all of
the equipment is installed in compliance with the
manufacturer’s recommendations, with due regard to the
current HEALTH AND SAFTEY AT WORK ACT and conforms
to all relevant statutory regulations. Where a unit is installed
so that a failure of components could result in injury to
personnel, precautions should be taken to prevent such an
injury.
IMPORTANT
Only experienced fitters should undertake this work. Take
necessary safety precautions when working in elevated positions
The AIRBEAM unit is specifically designed for wall mounting,
in the vertical plane only. A hole must be cut in the wall to
the following dimensions prior to installation; note the
difference in opening size between louvre and cowl housings
see fig 2. Trim the wall opening as required to make good.
1
VES Ref: ID660
Issue C
May 2015
Louvre unit
Remove the front louvre from the wall sleeve. To ease
installation, the fan should also be removed by removing the
fan fixing bolts, ensuring after installation the fan plate is
reattached in the correct position. Insert the unit in the
opening from the outside of the ventilated area, taking care
to avoid damaging the external finish (reducing the unit’s
resistance to corrosion).
External
Louvre
Axial fan,plate and
guard assembly
External
Cowl
Case, backdraught
flaps & fan plate
assembly
Backdraught
flap/plate
!
IMPORTANT
It is the responsibilty of the installer to ensure that the unit is
installed in a manner which will not result in injury or damage
to either the unit or property.
When selecting the location for your Airbeam, it is critical to
ensure there are no immediate obstructions to the airflow as
this will cause a loss of performance.
These products contain rotating parts and electrical
connections which can be a danger and could cause injury,
although unlikely as all fans are fitted with motor side guards.
The axial fans utilised in the Airbeam range also generate
noise; it is advised that if activities have to be conducted in
close proximity to the working units the noise level should be
taken into account.
Taking the previously mentioned points into consideration, it
is advised that this unit should installed out of normal reach
of personnel.
Fig. 2 Approximate unit weights & opening dims
Lined hole
size (mm) Weight (kg) Lined hole
size (mm) Weight (kg)
315 505 x 505 21 340 x 340 12
355 505 x 505 25 395 x 395 15
400 595 x 595 23 450 x 450 12
450 595 x 595 28 495 x 495 16
500 675 x 675 33 575 x 575 19
560 745 x 745 39 635 x 635 25
630 835 x 835 42 710 x 710 25
Unit
Louvre Cowl

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08702 404340 Fax: 08702 404550 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
AIRBEAM Wall Extract Units
Installation, Operation and Maintenance Manual
ORIGINAL INSTRUCTIONS
4 Wiring
AIRBEAM series contain an axial plate fan, acting as an
extract unit.
All electrical connections must be carried out in accordance
with the current edition of the I.E.E REGULATIONS and only
competent electricians should be allowed to affect any
electrical work to our units.
IMPORTANT
Do not connect any unit to an electrical supply voltage
outside of that indicated on the motor nameplate.
A local isolator must be fitted and mains cables should be
suitably sized and terminated as shown in fig 6 & 7.
Electrical details are shown in fig 5. Make the connection in
the fan terminal box using the gland provided.
2
!
3 Installation continued
Push the unit all the way home until the external flange lies
flush with the wall. Match drill fixing holes into the wall
through the fixing holes in the casing. Relocate the front
louvre on the casing and fix to the wall using appropriate
fixings (supplied by others) through both plates together
using the holes provided. A bead of sealant can be run
around the join between the flange and wall to ensure full
weatherproofing as required see fig 3. It is the installer’s
responsibility to determine the type of fixing to be used, and
whether any extra support is required.
Cowl unit
Seperate the two plates which make-up the external part of
the unit. Taking care to ensure that the cutout on the unit
matches up with the opening in the wall, mark out the
location of the fixing holes on the wall. Match drill the fixings
holes on the wall. Carefully put the two plates together, offer
up to the wall opening and secure into place through both
plates, using appropriate fixings (supplied by others). A bead
of sealant can now be run around the join between the edge
of the plate and the wall to ensure weatherproofing as
required.
To fit the fan plate, remove the fan from the packaging. Offer
the fan up to the inside wall, again ensuring that it is central
to the wall opening, match drill fixing holes in the wall. Attach
the fan rigidly to the mounting surface, using appropriate
fixings (supplied by others). Should this surface be uneven it
will be necessary to pack between the fan plate and the wall
to prevent any distortion to the bellmouth causing the
impeller to foul. It is the installer’s responsibility to
determine the type of fixing to be used, and whether any
extra support is required.
B
Fig. 4 Cowl unit detail B
Fig.5 Electrical Details
Sealant
Wall fixing
(supplied
by others)
Removable
cowl
Backdraught
flaps
Wall
Fig. 3 Louvre unit detail A
Sealant
Wall fixing
(supplied
by others)
Removable
louvre
Backdraught
flaps
Wall
A
ABM 315 / 4 - 1 1400 0.14 0.67 -
ABM 355 / 4 - 1 1400 0.16 0.76 -
ABM 355 / 6 - 1 900 0.10 0.44 -
ABM 400 / 4 - 1 1400 0.25 1.06 -
ABM 400 / 6 - 1 900 0.12 0.54 -
ABM 450 / 4 - 1 1400 0.45 1.96 -
ABM 450 / 6 - 1 900 0.17 0.74 -
ABM 450 / 8 - 1 700 0.12 0.68 -
ABM 500 / 4 - 1 1400 0.72 3.29 -
ABM 500 / 6 - 1 900 0.29 1.40 -
ABM 500 / 8 - 1 700 0.15 0.75 -
ABM 560 / 4 - 1 1400 0.90 3.67 -
ABM 560 / 4 - 3 1400 1.03 - 1.83
ABM 560 / 6 - 1 900 0.40 1.83 -
ABM 560 / 8 - 1 700 0.24 1.34 -
ABM 630 / 4 - 3 1400 1.23 - 2.13
ABM 630 / 6 - 1 900 0.54 2.40 -
ABM 630 / 6 - 3 900 0.53 - 1.10
ABM 630 / 8 - 1 700 0.28 1.47 -
FLC
400V
Model Fan speed
RPM
Motor size
kW
FLC
230V
Consideration must also be given by the installer for
adequate illumination of the unit location in order for safe
maintenance.
IMPORTANT
When replacing the external louvre or cowl care should be
taken to ensure that the fixings are securely tightened.
!
Axial plate
fan
Axial plate
fan

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NF
Tel: 08702 404340 Fax: 08702 404550 E-mail: vesltd@ves.co.uk Web: www.ves.co.uk
AIRBEAM Wall Extract Units
Installation, Operation and Maintenance Manual
ORIGINAL INSTRUCTIONS
Therm
TOTO L1 L2 L3 E
Violet
Violet
Orange
Brown
Red
Blue
Grey
Black
Grn/Ylw
!
!
!
3
Standard motor wiring arrangement
Fig.7 400V 3Ph 50Hz
Note: A trial connection of the three phase (3Ph) supply should
be made to check that the fan rotates in the correct direction as
indicated on the fan. If the rotation is incorrect, interchange any
two phases of the incoming supply at the terminal block.
3 Wiring continued
Standard motor wiring arrangement
Fig.8 230V 1Ph 50Hz
N L E
Cap
Brown
White
Black
Grn/Ylw
Therm
Aux
Main
Grey
Orange
Orange
IMPORTANT
Before attempting to carry out any work on our units, the unit
MUST BE COMPLETELY ISOLATED
from its
electrical supply.
Ensure a minimum of two minutes after electrical
disconnection before commencing work. This will allow any
moving part to come to a rest, all accompanying
documentation including warning labels on the unit must be
referenced
WARNING
When used in conjunction wih an Inverter for speed control, a
minimum of 5 minutes should be given to allow for the
capacitors to discharge before starting work
Care should also be taken whilst cleaning the unit in the
event that wind or air movement should cause the fan to
freewheel.
Annual checks
Check inside the unit for an accumulation of dust, grease
etc. If the fan impeller is heavily soiled, clean out carefully
(ensure the unit is properly isolated). Failure to do this
periodically could lead to a loss of performance or the fan to
become out of balance, leading to bearing failure. Check the
drainage holes (cowl unit only) are clear of debris and
service as required. Clean the external louvre/cowl to ensure
that performance is maintained. Inspect the backdraught
shutters for signs of damage (cracks or bending).
IMPORTANT
When removing the louvre/cowl please note that these
fixings secure the units into position and by removing these
the unit may be released from the wall. This is particularly
important with the cowl unit as the backdraught plate would
be unsupported.
PLEASE ENSURE THAT THIS DOCUMENT IS
PASSED ON TO THE END USER.
We reserve the right to alter the specifcation without notice
When enquiring after or ordering spares contact VES
Customer Services Department, quoting the sales order
(SO) number and unit type as found on the unit nameplate.
Telephone 08702 40 43 40
Fax 08702 40 45 50
!
5 Maintenance
In general, this series of units require very little maintenance.
All fan and motor bearings are supplied fully greased,
lubricated and sealed for life. In the unlikely event of
component failure, spares are available from stock at VES
Andover Ltd.
!
IMPORTANT
When used in conjunction with a speed controller refer to
the appropriate controller wiring diagram
IMPORTANT
When used in conjunction with a SC310SD speed controller
additional wiring connections will be required - refer to the
appropriate controller wiring diagram or document ID
Ref:678 for further details*.