Tab. no. 3a) Thermal - technical parameters of G 42 boiler equipped with SINGLE STAGE or
DOUBLE STAGE GAS VALVE and designated for NATURAL GAS combustion
(thermal power 34,16 MJ.m
-3
, gas temperature 15 °C and bar. air pressure 1013,25 mbar)
Rated heat output maximum kW 8 17 26 34 41 49
Rated heat output minimum kW - 12 18 27 35 42
Rated heat input maximum kW 8,84 18,78 28,02 37,20 44,85 53,18
Rated heat input minimum kW - 13,18 19,66 29,8 38,34 45,90
Gas volume flow rate at maximum heat output m
.h-1 0,932 1,980 2,953 3,920 4,727 5,605
Gas volume flow rate at minimum heat output m
.hod
- 1,390 2,072 3,141 4,041 4,837
Gas volume flow rate at maximum heat output dm
.min
15,53 33,0 49,22 65,33 78,78 93,42
Gas volume flow rate at minimum heat output dm
.min
- 23,17 34,53 52,35 67,35 80,62
Efficiency at maximum heat output % 90,5 – 93
Efficiency at minimum heat output % 90,5 – 91,5
No
category 2
Combustion products temperature in smoke
flue at maximum heat output °C 90 – 120
Combustion products temperature in smoke
flue at minimum heat output °C 80 – 90
Real volume of dry combustion products at
maximum heat output m
3
.m
-3
17,80 23,33 19,23 23,89 20,66 18,25
Real volume of dry combustion products at
minimum heat output m
3
.m
-3
- 25,09 27,52 28,67 23,65 25,09
Connecting gas overpressure mbar 20
Gas overpressure on burner nozzles at
maximum heat output mbar
13,7 13,2 15,8 14,2 14,7 14,3
Gas overpressure on burner nozzles at
minimum heat output mbar
- 6,8 7,8 8,9 10,8 10,6
Number of cool. sticks on a tube pc 2 3 3 3 3 3
Number of nozzles pc 1 2 3 4 5 6
Nozzles diameter mm 2,4 2,52 2,52 2,52 2,45 2,45
Connecting gas overpressure mbar 13
Gas overpressure on burner nozzles at
maximum heat output mbar
10 10 11 11 11,7 11,5
Gas overpressure on burner nozzles at
minimum heat output mbar
4,6 4,7 4,8 6,8 8,8 8,6
Number of cool. sticks on a tube pc 2 3 3 3 3 3
Number of nozzles pc 1 2 3 4 5 6
Nozzles diameter mm 2,7 2,7 2,7 2,7 2,7 2,7
Note: At a single stage valve the heat output is pre-set by the manufacturer to the maximum.
Tab. no. 3b) Thermal - technical parameters of G 42 boiler equipped with SINGLE STAGE GAS
VALVE and designated for PROPANE combustion
(thermal power 87,75 MJ.m
-3
, gas temperature 15 °C a bar. air pressure 1013,25 mbar)
Rated heat output kW 7 14 21 26 33 40
Rated heat input kW 7,73 15,21 22,82 28,32 35,90 43,79
Fuel volume rated flow m
.h-1 0,317 0,624 0,936 1,162 1,473 1,796
Fuel volume rated flow dm
.min
5,28 10,40 15,60 19,37 24,55 29,93
Boiler efficiency % 90,5 – 92
No
category 2
Combustion products temperature in smoke
flue °C 90 – 110
Real volume of dry combustion products m
.m
46,42 59,5 95,87 67,3 58,55 56,15
Connecting fuel overpressure mbar 30
Gas overpressure on burner nozzles mbar
27,5 28,5 28 27 27,5 27,5
Number of cool. sticks on a tube pc 2 3 2 3 3 3
Number of nozzles pc 1 2 3 4 5 6
Nozzles diameter mm 1,55 1,55 1,5 1,5 1,5 1,5