SKV 3400
Level Control Valve
Installation and Operating
Instructions

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
2
CONTENTS
1. SAFETY INFORMATIONS.................................................................................................3
2. DESCRIPTION ...................................................................................................................3
3. TECHNICAL SPECIFICATIONS........................................................................................4
3.1. SKA 3200 Level Control Valve Actuator.......................................................................4
3.2. SKV 3400 Level Control Valve .....................................................................................5
4. INSTALLATION and WIRING............................................................................................6
4.1. Installation ....................................................................................................................6
4.2. Wiring ...........................................................................................................................6
5. COMMISSIONING..............................................................................................................8
6. MAINTENANCE .................................................................................................................8

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
3
1. SAFETY INFORMATIONS
Safety!
Installation, commissioning and maintenance of this controller must be done by a qualified
person.
It is essential to read and understand the “Installation and Maintenance Instructions” of this
controller and other related equipments.
National and local regulations must be taken into consideration.
Warning!
Please make sure to remove the main supply before installation. Otherwise
this may cause damage to the product, personal injuries or even death.
2. DESCRIPTION
SKV 3400 Level Control Valve is used with SKA 3200 Level Control Valve Actuator.
Actuator opens or closes the valve according to signals taken from SK 3400 Modulating
Level Controller.
Figure 1 Modulating Level Control System application

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
4
3. TECHNICAL SPECIFICATIONS
3.1. SKA 3200 Level Control Valve Actuator
Enclosure : IP 65
Maximum ambient temperature : 60 °C
Main supply voltage : 220 V
Frequency : 50 Hz
Maximum power consumption : 26 VA
Weight : 7 kg
Voltage
Force
220 V AC
110 V AC
24 V DC
1,0 kN
SKA 3211
SKA 3212
SKA 3213
2,3 kN
SKA 3221
SKA 3222
SKA 3223
4,5 kN
SKA 3241
SKA 3242
SKA 3243
8,0 kN
SKA 3281
SKA 3282
SKA 3283

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
5
3.2. SKV 3400 Level Control Valve
Maximum operating temperature : 200°C
Maximum operating pressure : 20 bar g
Nominal pressure : PN 25 (ask for other pressure classes)
Valve body : Nodular cast iron
Connection : DN 25-50, Flanged
Weight : 4 kg
Figure 2 SKV 3400 Level Control Valve dimensions
Type
Size
D
(mm)
L
(mm)
B
(mm)
SKV 3425
DN 25
115
160
122
SKV 3432
DN 32
140
180
147
SKV 3440
DN 40
150
200
157
SKV 3450
DN 50
165
230
172

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
6
4. INSTALLATION and WIRING
4.1. Installation
Valve can be installed vertically or
canted maximum 90° left or right. It
must not be installed upside down
(Figure 3).
Pay attention to arrow mark located
on the valve body which shows
direction of water flow.
Figure 3 Installation positions of SKV 3400
Level Control Valve
4.2. Wiring
For wiring, actuator cover must be removed.
To remove it, firstly use an allen key to
remove hand lever (Figure 4). Then pull up
the actuator cover.
Figure 4 Removing actuator cover

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
7
For wiring of data terminals (4, 5) 2x1 mm2screened (shielded) cable and for control
terminals (16, 17, 18) 3x1 mm2normal cable can be used. Valve potentiometer cable
screen (shield) must be only connected to 4th terminal of controller (Figure 5). Valve
potentiometer (actuator) side of the screen must be left unconnected.
Figure 5 SKA 3200 Level Control Valve Actuator wiring diagram
Information
Data terminals (4, 5): Used to transfer valve openness percentage data from valve
potentiometer to controller. Must be used screened (shielded) cable for wiring of data
terminals.
Control Terminals (16, 17, 20): Used to open or close the valve.

SKV 3400 MKK v10.01-EN Vira Valf 2010 ©
8
5. COMMISSIONING
Be sure that all cables are connected to the right terminals.
Before commissioning make sure that valve is fully closed.
6. MAINTENANCE
Warning!
Please make sure to remove the main supply of actuator before displace
the valve. Otherwise this may cause damage to the product, personal
injuries or even death.
When any fault situation occurs or maintenance is necessary, please contact with “Vira Valf
Service Department”.
Vira Heating and Industrial Products Inc. Co.
Metal Is Sanayi Sitesi 11. Blok No: 37-39
Ikitelli / Istanbul / TURKEY
Tel : +90 212 549 57 70
Fax : +90 212 549 48 58
Web : www.viravalf.com
Table of contents
Popular Control Unit manuals by other brands

KIESELMANN
KIESELMANN 6268 Translation of the original operating instruction

Omron
Omron C500-SNT31-V4 Operation manual

Burkert
Burkert 2301 Series quick start

ICP DAS USA
ICP DAS USA iWSN-110X Series quick start

Dungs
Dungs DGAI. 33F/2 Operation and assembly instructions

Cornelius
Cornelius LEOPARD ERV Operator's manual