Vision BP650 User manual


BUDGET PRO series 650-2200VA - UPS www.visionups.com
2
INDEX
1. Introduction ……………….………………...…………………………......................................... 2
2. Safety instructions …………..………………………………………………………………….….. 2
3. Specifications ……………………………………………………………….…..……….…………. 3
4. System description …..……..…………………………………………………………..….…..….. 4
4.1. Front panel ……………..……………………………………………………………………… 4
4.2. Back panel …………………………...………………………………………………………… 4
5. Installation & operation ……………….…..…………………………………………………….…. 5
5.1. Unpacking and control ……………………………………………………………………….. 5
5.2. Charging before first use …………………………………………………………………….. 5
5.3. Placement ……………………...……………………………………………………………… 5
5.4. Connection …………………………..……….................................................................... 5
5.5. Turn On/Off ………..………………………………………………………………………….. 5
5.6. Cold start in battery mode …………….……………………………………………………... 5
6. Trouble shooting …………...….………………...………………………………………………… 6
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
1. INTRODUCTION
This UPS is specially designed for personal computers with multi-functions. Its light weight and compact design fits perfectly
into limited workspaces. The UPS-input is equipped with automatic voltage regulation (boost and buck AVR) to stabilize
input voltage range. It has also a built-in cold start function, which enables the UPS for start-up without mains supply.
Although it’s a small UPS, it disposes the main features listed below:
control by microprocessor guarantees a high reliability;
equipped with automatic voltage regulation (boost and buck AVR);
green power function for energy saving;
cold start function;
automatic restart while mains supply recovery;
compact size, light weight;
provides mains supply overload protection.
2. SAFETY INSTRUCTIONS
This UPS uses voltages that may be dangerous. Do not attempt to disassemble the unit; it contains no user
serviceable parts. Repairs should only be executed by plant service.
The battery voltage is 12Vdc. These are internal, sealed, maintenance-free, 6 cells lead-acid batteries.
The UPS must be connected to a mains socket with circuit-breaker. Connect the appliance only to a mains socket
with grounding.
In case of an emergency, press the OFF-button and pull the mains plug for interrupting completely the power
supply to the UPS.
Do not let attain any liquids or foreign objects into the UPS appliance; that’s why no beverage or other liquid-
containing vessels should be placed on or near the appliance.
This unit is intended for installation in a controlled environment (temperature and humidity). Do not install it in
locations with standing or flowing water or excessive humidity.
Do not plug the input cable of the UPS in its own output.
Do not connect multiple plugs or surge protections to the UPS unit.

BUDGET PRO series 650-2200VA - UPS www.visionups.com
3
Only connect computer-related elements to the UPS unit.
DO NOT CONNECT medical applications or life-support equipment.
DO NOT CONNECT AS WELL laser printer, labelling machines, copy machines, generators, vacuum cleaners, drain
pumps, microwave ovens or other larger electric appliances to the output connectors. The electricity consumption
would cause an overload and possibly even the damage of the UPS.
To reduce the risk of overheating: do not cover or block the vent of the UPS unit, do not expose the appliance to
direct sunlight, do not install it near heat emitting appliances such as space heaters or furnaces/ovens.
Pull the mains plug out of the socket before cleaning. Do not use liquid or spray detergents.
Do not expose the batteries to fire because they may explode.
Do not open and/or damage the batteries on their outside: released electrolyte (lead-acid-accumulator) is harmful
to skin and eyes. It may be toxic.
A battery holds the risk of electric shocks and short circuits. The following precautions should be considered when
working with batteries:
1) Remove watches, rings or other metal objects from your hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and rubber boots.
4) Do not deposit tools and/or metal parts on the battery.
5) Disconnect the appliance from the mains each time you are connecting or disconnecting the battery terminals.
The maintenance of the batteries should be executed by battery-knowledgeable personnel. Observe the
recommended and necessary precautions. Keep unauthorised personnel away from the batteries.
When the batteries are replaced, utilize the same quantity and type of sealed lead-acid battery. The ambient
temperature may not exceed 40°C. For maintaining the battery lifetime, we advise an ambient operating
temperature of 20°C to 25°C.
Ensure during the installation of the appliance, that the sum of the residual current of the UPS and of the
connected load does not exceed 3.5mA.
Caution of electric shocks. Even when the unit is disconnected from the mains, dangerous voltages could be
achieved via power supply from the battery. For that raison, interrupt the battery on its plus and minus poles
when maintenance and servicing activities are necessary and undertaken.
The mains socket outlet that supplies the UPS shall be installed near the UPS unit and shall be easily accessible.
3. SPECIFICATIONS
LED Model
BP650
BP850
BP1100
BP1300
BP1600
BP2200
& LCD Model
BP650D
BP850D
BP1100D
BP1300D
BP1600D
BP2200D
Capacity
650VA
850VA
1100VA
1300VA
1600VA
2200VA
Input
Voltage
220 / 230 / 240 Vac
Voltage range
162-290 Vac
Frequency range
60/50 Hz (automatic recognition)
Output
Voltage in battery mode
230 Vac ±10% (no block sinus)
Frequency in battery mode
50/60 Hz ±1%
Transfer time
typically : 2 à 6 ms
Batteries
Recharge time
6-8 hours to reach 90% of capacity
Number and type of battery
1 x 12V7Ah
1 x 12V9Ah
2 x 12V7Ah
2 x 12V7Ah
2 x 12V9Ah
2 x 12V9Ah
LED Indicator
Mains mode (AC)
green LED lighting
Battery-Modus
green and orange LED lighting
Protection
Overvoltage / overload
surge protection
Audible alarm
Battery mode
sounding every 10s
Weak autonomy
sounding every 1s
Overload
sounding every 0.5s
Replace batteries
sounding every 2s
Fault
continuously sounding
Size ratio
Dimensions –mm (W x D x H)
101 x 298 x 142
149.3 x 338 x 162
158 x 380 x 198
Net weight –kg
4.25
4.9
7.8
8
11.1
11.5

BUDGET PRO series 650-2200VA - UPS www.visionups.com
4
Operating environment
Ambient temperature
0°C à 40°C
Operating humidity
< 90% without condensation
4. SYSTEM DESCRIPTION
4.1. Front panel
① Mains power switch
②LED Indicators:
Mains mode:
The green LED is lighting (650-1300VA). The left green LED is lighting & the 1st to 4th green LED are gradually
lighting and in line with the load level (1600-2200VA).
Battery mode:
The yellow LED is flashing (650-1300VA). The left green LED is flashing & the 1st to 4th green LED are gradually
lighting and in line with the autonomy level (1600-2200VA).
Fault mode:
The red LED is lighting.
③LCD
4.2. Back panel
①Input mains power supply
② Output receptacles
③USB & RJ11 data communication
④USB & RS232 data communication
⑤RJ45
⑥Circuit breaker

BUDGET PRO series 650-2200VA - UPS www.visionups.com
5
5. INSTALLATION & OPERATION
5.1. Unpacking and control
Remove the packaging from the UPS and inspect it for eventual transport damage. If any damage is discovered, repack the
unit and send it back to the seller.
5.2. Charging before first use
Tis unit was sent ex-factory with its internal battery fully charged; anyhow it can discharge during the transportation. That’s
why it has to be charged before first use. Turn on the UPS, plug it into an appropriate power
supply and allow the UPS to charge totally by leaving it plugged in for at least 6 hours with no
load (no electrical devices such as computers, monitors, etc.) connected.
5.3. Placement
Install the UPS unit in a protected environment that provides adequate ventilation around the unit and that’s free from
excessive dust, corrosive vapours and conducting polluting substances. Do not operate your UPS in an environment where
the ambient temperature or humidity is high.
Furthermore, maintain a minimum distance of 20 cm between UPS unit and a monitor for avoiding harmful interference.
5.4. Connection
Plug the UPS into a 2-pole grounded mains socket (phase and neutral). Afterwards, connect by means of the delivered cable
one computer or computer-related device to each connection jack on the back side of the UPS.
5.5. Turn On/Off
To turn the UPS on, press the power switch. To turn the UPS off, press the power switch again.
5.6. Cold start in battery mode
All UPS appliances are equipped with a cold start function in battery mode. To start the UPS when mains power is not
available, simply press the power switch.

BUDGET PRO series 650-2200VA - UPS www.visionups.com
6
6. TROUBLE SHOOTING
Symptom
Possible cause
Solution
No LED indication on the
front panel display.
1. The battery is weak.
2. Battery fault.
3. The power switch is not pressed.
1. Charge the battery during 8 hours.
2. Replace the battery with a new one of
same type.
3. Press the power switch (again).
Alarm buzzer beeps
continuously when mains
supply is normal.
Overload of the UPS.
Verify if the connected load is in accordance
with the denoted performance (see
specifications).
When the power failures,
back-up time is shorten.
1. Overload of the UPS.
2. The battery voltage is too low.
3. Battery fault because of too high
operating temperature, or because of
malfunction of the battery.
1. Remove some non-critical loads.
2. Charge the battery during 8 hours or more.
3. Replace the battery with a new one of
same type.
Mains power is normal, but
the yellow LED is flashing.
The Power cord is loose.
Reconnect the power cord properly and
firmly.
If any abnormal situations occur that are not listed above, please contact immediately the client service.
▪▪ ▪ ▪ ▪ ▪
This manual suits for next models
11
Table of contents