Voltaire NOMINAL 300 CFM User manual

www.voltairesys.com
Phone: (407) 378–7482
2900 W. Orange Ave. Ste. 100
Apopka, FL 32703
VoltAire Systems, LLC VoltAire Doc. # DA0322A
Published: June 13, 2023
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
FOR PRESSURIZATION MODULE (WITH PLENUM FOR W18-W36 AIR
CONDITIONER MODELS)
NOMINAL 300 & 450 CFM FOR
BARD W18 THROUGH W36 UNITS
115VAC & 208/230VAC Models
* A more recentrevision may be available at www.voltairesys.com or the QR Code in the top right corner of every page.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 2 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
TABLE OF CONTENTS
1. Important Information to Review Prior to Installation, Operation and Maintenance........................................................Page 3
2. Parts Shipped Loose and Tools Required/Materials Provided by the Installer................................................................Page 3
3. Product Description ..........................................................................................................................................................Page 4
4. Important Application Notes..............................................................................................................................................Page 4
5. General Product Data .......................................................................................................................................................Page 5
6. Installation Instructions......................................................................................................................................................Page 7
7. Startup and Maintenance Instructions............................................................................................................................Page 12
8. Troubleshooting Guide....................................................................................................................................................Page 12
9. Wiring Diagram (No External Controls or Damper)........................................................................................................Page 14
Wiring Diagram (Option A – with Shutdown Control).....................................................................................................Page 15
Wiring Diagram (Option B – with Damper and Shutdown Control)................................................................................Page 16
Wiring Diagram (Option C - with HVAC Interlock Control).............................................................................................Page 17
Wiring Diagram (Option D – with Damper, HVAC Interlock and Shutdown Controls)...................................................Page 18
10. Warranty..........................................................................................................................................................................Page 19

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 3 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
1. IMPORTANT INFORMATION TO REVIEW PRIOR TO INSTALLATION,
OPERATION AND MAINTENANCE
READ THE ENTIRE MANUAL PRIOR TO INSTALLING, OPERATING AND MAINTAINING the VoltAire Systems
Pressurization Module. Do not install or perform maintenance on the equipment if you do not understand all of the
instructions. Contact VoltAire Systems at (407) 378-7482 with any questions or concerns.
The pressurization module should be fully inspected on initial delivery. Open the packaging completely at the time of
initial delivery and verify there is no hidden or concealed damage. Shipping damage, including concealed damage, is
not covered under warranty. Reject the shipment if any damageis found.
WARNING: IMPROPER INSTALLATION AND OPERATION MAY CAUSE PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE. The pressurization module shall only be installed andserviced by a certified professional in
strict accordance with the requirements within this manual,in accordance with all local/state/federal codes, and per
industry standards. Remove power from the unit during maintenanceand installation, as linevoltage may be dangerous,
hazardous and lethal.
In the event of a conflict, code requirements shall take precedence over the instructions provided within this manual. The
installer shall be aware of allcode requirements and shall comply fully.
Use care when transporting and lifting the pressurization module.
WARNING: WEAR PROPER PERSONAL PROTECTION EQUIPMENT, INCLUDING BUT NOT LIMITED TO SAFETY
GLASSES, GOGGLES, AND GLOVES. EDGES MAY BE SHARP.
A field provided disconnect must be provided by the installer with the power supply circuit serving thepressurization
module. The installer shall size the electrical wire and disconnect in accordance with all applicable codes. Verify wire
terminals and voltageprior to starting the pressurization module, otherwise you may damage the electrical components.
These instructions should be retained by the owner and/or with the unit.
2. PARTS SHIPPED LOOSE AND TOOLS/MATERIALS PROVIDED BY THE
INSTALLER
Materials shipped loose in addition to this manual are as follows:
a) Ship Loose Kit
DESCRIPTION PART NUMBER
Pressurization Module Ship Loose Kit D0Z0007VAA
Pressurization Module Plenum Ship Loose Kit D0Z0008VAA
b) Bard Economizer Exhaust Modification Kit (Optional, Sold Separately)
DESCRIPTION PART NUMBER
W18-W24 Economizer Exhaust Mod
Field Kit
(
Bard Models W18-W24
)
W18-W24ECONMODKIT
W30-W36 Economizer Exhaust Mod
Field Kit (Bard Models W18-W24) W30-W36ECONMODKIT

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 4 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
Required Tools and Materials provided by Installer:
a. Electrical service wire and disconnect, and
associated electric tools
b. Exterior rated silicone or other exterior sealant
c. Foil sealing tape
d. Flathead and phillips head driver/bit
e. 5/16” Hex head drill bit
f. Jigsaw / Reciprocating saw
g. Personal Protection Equipment
3. PRODUCT DESCRIPTION
VoltAire Systems pressurization modules are designed to be mounted on Bard HVAC Units, sizes 1.5 to 3 tons
(W18 through W36), to provide fan powered pressurization air through the Bard unit and into the building, providing
positive pressure to the building after pre-conditioning the outside air with the Bard unit. The amount of
pressurization air required is a function ofthe building/room size and tightness/sealing. The pressurization module
provides a pre-filter/mist eliminator and 2” MERV 8Filter to provide filtration. The pressurization module fan speed
is manually adjusted utilizing the potentiometer. It is important to note that the units must be ordered for either a
right hand or left hand mounting orientation.
It is highly recommended that Bard units paired with the VoltAire Systems Pressurization Module be supplied with
independent humidity control for any sites where ambient humidity may be higher than the desired building interior
humidity.
4. IMPORTANT APPLICATION NOTES
HVAC independent humidity control highly recommended for mild to high humid environments due to fresh air
pressurization.
Positive pressurization requires a well-sealed building/room envelope. Take extraordinary means to ensure
envelope sealing.
If HVAC units are equipped with economizers, special accommodations may be required to the HVAC unit as
building/room pressure will be affected by economizer operation.
Consider outdoor air load in HVAC sizing calculations to ensure proper heating, cooling, and
dehumidification for outside air provided by the pressurization module.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 5 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
5. GENERAL PRODUCT DATA
FIGURE 1: PRESSURIZATION MODULE MODEL NOMENCLATURE
FIGURE 2: PRESSURIZATION MODULE PLENUM MODEL NOMENCLATURE

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 6 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
FIGURE 3: PRODUCT CONFIGURATIONS (LEFT OR RIGHT)
FRONT OF BARD UNIT WITH RIGHT HAND SIDE PRESSURIZATION MODULE (WITH PLENUM)
FIGURE 4: GENERAL CONFIGURATION AND AIRFLOW
FIGURE 5: DIMENSIONS

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 7 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
6. INSTALLATION INSTRUCTIONS
WARNING: REVIEW THIS MANUAL COMPLETELY PRIOR TO BEGINNING INSTALLATION OR SERVICE.
FAILURE TO DO SO MAY RESULT IN IMPROPER OPERATION, UNIT DAMAGE, AND/OR PERSONAL/BODILY
HARM. PRESSURIZATION MODULES MUST ONLY BE INSTALLED BY PROPERLY TRAINED AND
EXPERIENCED TECHNICIANS.
The Pressurization Module is designed to use a Plenum adapter tofit on Bard HVAC models W18 to W36. The Plenum
requires a 10 by 10 inch cutout to be made on the side panel. Two pre-existing screws are used to assist with hanging
the Plenum. After the Plenum is hung, 8 self-tapping screws will be used to fix theplenum in place. The main
Pressurization Module may then be affixed to the Plenum.
Installation steps are as follows and note that your distributor might have completed some or all of the steps.
1. Prepare the Bard side panel for removal of the 10” x10” cutout. The cutout is located below the filter
assembly in the approximate location shown. Mark the cut out area and using a tape measure and visual
inspection, verify that the cutout will not conflict with any internal piping and/or components. Be cautious of
cutting blade depth. After the material is removed from the cutout, deburr and clean the cutout as necessary
ensuring the side panel is clean of any metal shavings, dust, and/or debris.
WARNING! After marking the cutout
opening location, check the interior of the
HVAC unit within the cutout area footprint to
verify there are no copper pipes, wires, and
other HVAC unit components that will be
damaged by the cutting blade.
Bard Side Panel Shown
FIGURE 6: CUTOUT AREA
2. Using foil tape (field supplied), tape the metal edge and internal insulation to provide a clean edge as shown

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 8 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
below.
FIGURE 7: PLENUM OPENING WITH TAPED EDGES
3. Install the Plenum gasket kit as shown in Figure 8 below. The figure shows the gasket area. Note that the
15.625-inch lengthpiece runs across the top of the unit.
FIGURE 8: PLENUM GASKET AREA
4. After installation of the Plenum gasket kit, utilize the pre-existing screws on the Bard side panel and the
marked holes on the Plenum, mount the Plenum onto the Bard unit. The approximate location of the Bard
screws are shown in Figure 9. Note that these screws hold the filter rack bracket in place on the Bard unit and
the filter rack may need to be re-located back in place duringinstallation. Your plenum gasket side should
mount against the Bard side panel. Before fully securing the two screws, ensure the plenum is level.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 9 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
FIGURE 9: PLENUM ALIGNMENT SCREWS
5. After hanging the plenum, install the 8 provided self-tapping screws in the location shown in Figure 10.
FIGURE 10: PLENUM MOUNTING LOCATIONS
6. Using field-supplied sealant, apply a bead along the top seam (and side seams if possible) between the
Plenum and the Bard unit.
7. Install the Pressurization Module gasket kit utilizing Figure 11 as reference. The figure shows the gasket area.
Note that the 18-inch length runs across the top of the unit.
FIGURE 11: PRESSURIZATION MODULE MOUNTING SURFACE
MOUNTS TO PLENUM

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 10 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
8. Install the Pressurization Module on the Plenum using the 6 provided screws in the shipped loose kit. The six
screw holes can be found on the mounting flanges the Pressurization Module as shown in Figure 12.
FIGURE 12: PRESSURIZATION MODULE SIDE VIEW
(OPPOSITE SIDE OF MOUNTING SURFACE)
9. Remove the top access panel from the pressurization module. (Refer to General Configuration and Airflow)
10. Using field-supplied sealant, apply a bead along the top and around the sides of the mounting bracket where
the Pressurization Module and the Plenum meet.
11. Using the field supplied electrical service with disconnect, pass through the Pressurization Module electrical
entries and land the wires at the terminal block, including a ground wire to the ground terminal, as shown in
Figure 13. Wire size may be #12 to #16 AWG, sized by installer per code, using the torque driver to provide
4.5 in-lb torque.
FIGURE 13: ELECTRICAL ENTRY LANDING
12. The Pressurization Module may come with a selection of features depending on the model number.
Determine which features are included with the unit by referring to the model number to the nomenclature
from Figure 1 on page 5. Then refer tothe respective wiring diagrams found on pages 14-18 in this manual
for further clarification.
For Pressurization Modules with an HVAC interlock, remove the factory jumper from the interlock relay and
provide 24VAC external power to the interlock contacts.
For Pressurization Modules with fire/smoke shutdown, remove the factory jumper from the shutdown terminal
block and replace with field supplied dry contacts.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 11 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
The field contacts should be closed to command the Pressurization Module to operate and the contacts
should open for interlock off or fire/smoke shutdown. If supplied with a low leakage damper, the damper will
automatically shut when the Pressurization Module is turned off by the interlock or fire/smoke damper.
If the unit is ordered without an interlock or fire/smoke shutdown option not used, ensure that the hole entry
remains plugged.
13. Verify all wires and landing points for high voltage and interlock/fire-shutdown are tight and secure any loose
wires with a wire tie to prevent the wires from rubbing or touching the fan. Ensure that any wires are free from
entanglement with the damper actuator.
14. Place top access panel and secure with screws.
15. If the unit has an economizer and if a field economizer exhaust modification kit is provided, install the
economizer mod kit as follows, prior to installing the Bard unit on the building if the return air opening is not
accessible from inside the unit. If the return air opening is accessible from inside the unit, this modification
and field adjustment can occur after the Bard unit is installed on the building by accessing the economizer
through the wall return opening (prior to the return grille installation).
a. Power the economizer blade open to expose
the economizer exhaust opening. This will
require the unit is powered with damper
opening via running the economizer Damper
Open test. Reference Bard HVAC manual as
necessary.
b. Remove the factory economizer seal blade
on the sides of the opening (rear to remain).
c. The economizer modification kit is provided
with two pieces of metal, the first is the
bracket to be installed with screws on the
down flange as shown. The second piece
installs on top of the bracket and has set
screws. The set screws can be adjusted to
vary the amount of economizer exhaust
opening. Install new gasket (provided with
field kit) on the sides as shown.
d. Once installed, the Damper Open test mode
can be terminated and the damper blade will
return to fully closed position and the
installation of the economizer exhaust
modification kit is complete.
16. The unit is now fully installed andready for operation, with Startup Instructions on the following pages.
FIGURE 14: ECONOMIZER BRACKET
INSTALLATION

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 12 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
7. STARTUP INSTRUCTIONS
The Pressurization Module is designed to provide continuous airflow for positive pressure in the building. As such, the
fan will run continuously whenever power is applied to the unit, unless the interlock or fire/smoke shutdown option is
ordered. The amountof pressurization air requiredis heavily dependent upon how well the building/room is sealed.
If a building or room pressurization monitoring station is provided (sold separately), the installer can adjust the speed of
the Pressurization Module(s) to reach the desired pressurization. The speed control can be accessed by removing the
speed control panel found above the filter access panel. Utilize a small flat head screw driver to adjust the
potentiometer. Turning the potentiometer to the right increases the fan speed and adjusting to the left lowers the fan
speed.
If the Pressurization Module was ordered with an interlock or fire shutdown, ensure that the interlock is wired to the
appropriate system (wall mount AC or fire/life-safety system). Open contacts will de-energize the pressurization module
and close the damper (if ordered/provided), closed contacts will provide continuous run and open the damper (if
applicable). Test the shutdown/interlock to verify proper operation.
The Module is provided with a nominal ½” mist eliminator and a nominal 2” x 12” x 16” MERV 8 filter. These filters are
accessible by removing the access panel. It is recommended that the filters be checked monthly with the mist eliminator
being cleaned and the 2” MERV 8 being replaced, as necessary.
8. TROUBLESHOOTING GUIDE
WARNING: ELECTRICAL SHOCK HAZARD. DISCONNECT POWER FOR SERVICING. FAILURE TO DO SO
COULD RESULT IN ELECTRICAL SHOCK OR DEATH.
CAUTION: SERVICE AND TROUBLESHOOTING SHOULD ONLY BE CONDUCTED BY CERTIFIED TECHNICIANS.
TECHNICIANS SHALL FOLLOW ALL INDUSTRY STANDARDS FOR SAFETY. THE COMPONENTS IN THE UNIT
ARE STANDARD INDUSTRY COMPONENTS, AND TOGETHER WITH THE INFORMATION PROVIDED WITHIN
THIS MANUAL, THE TECHNICIAN SHALL USE STANDARD ELECTRICAL TOUBLESHOOTING, DIAGNOSIS AND
REPAIR PROCEDURES. PLEASE NOTE THAT UNIT MAY CONTAIN CUT HAZARDS/SHARP EDGES AND
GLOVES SHALL BE USED TO AVOID SHARP EDGES AND INJURY, TOEGHER WITH SAFETY GLASSES.
IMPORTANT: REVIEW THE MANUAL IN ITS ENTIRETY PRIOR TO SERVICING OR MAINTAINING THE
EQUIPMENT.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 13 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
The following troubleshooting table provides some problems that may be experienced with startup and/or maintenance
of the pressurization module. Please review this chart to diagnose the problem and repair/adjust, as needed.
PROBLEM POTENTIAL CAUSE SOLUTION
The
pressurization fan
does not operate
or operates too
slow to pressurize
the building/room
No power Check power source voltage and verify the disconnect is turned on.
5 amp fuse blown Turn the disconnect OFF, remove the top access panel and remove the fuse from
the fuse holder to verifycontinuity. If the fuse is open replace it and restart as
described within this manual.
Dirty filter Air flow will be reduced as the filter becomes dirty. Remove the filter through the
filter access panel. Check the filter and replace if dirty.
Loose wiresor terminal
connections Turn the disconnect OFF, remove the top access panel and verify all wires are
landed on terminals and tightened properly.
Fan is not operating
Turn the disconnect OFF, remove the top access panel and turn the disconnect ON
to visually inspect if the fanis operating. Check the capacitance of the fan
capacitor. If the above items have all been checked and verified AND the fan is not
rotating, replace the fan capacitor and/or fan.
If provided with interlock or
fire shutdown, external dry
contacts are not functional
Verify that the external dry contacts for shutdown and the 24VAC supply for the
interlock are operating properly and closed during normal operation; The dry
contacts must be closed for normaloperation.
The fan isrunning slow Access the speed controller through the speed control accesspanel. Make sure
this is turned to the right to increase speed.
The
Pressurization
Module will not
pressurize the
building
Building / room air leakage Check all doors, windows, and other building components to ensure they are well
sealed; buildings requiring positive pressure may require additional sealing,
including but not limited to gasket on all doors.
Verify sufficient
pressurization capacity
The level of pressurization will determine the amount of pressurization air required.
Verify the building has sufficient pressurization air capacity. Although all
buildings/rooms vary, there are rules of thumb used to determine the amount of
pressurization air required. Common rules of thumb are (i) 0.25 CFM/Surface area
(floor, walls, ceiling), and (ii) 1 CFM/SF of floor area for building pressurized to +/-
0.1” W.C.
Economizer Exhaust
Adjustment
If the Bard unit has an economizer and the pressurization module was provided
with the economizer exhaust modification kit and the building pressure loss is only
occurring during economizer mode, adjust the plate on the economizer modification
kit to reduce the opening on the economizer exhaust.
FOR ADDITIONAL TECHNICAL SUPPORT, PLEASECONTACT VOLTAIRE SYSTEMS AT (407) 378-7482.

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 14 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
8. WIRING DIAGRAMS

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 15 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 16 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 17 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 18 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 19 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
10. WARRANTY
VOLTAIRE SYSTEMS THERMAL UNITS NON-TRANSFERABLE
STANDARD LIMITED WARRANTY, DISCLAIMERS, AND LIMITATIONS OF LIABILITY
(Applies to All Heat Exchangers, Pressurization Units/Modules,
Fan Units, and Air Conditioners)
The VoltAire Systems, LLC ("VoltAire") Non-Transferable Limited Warranty (“Limited Warranty”) is applicable for 12
months following the shipment of the product to the original purchaser ("Purchaser") defined as the "Warranty
Period". VoltAire warrants to the original purchaser during the Warranty Period that all materials and workmanship
are free of defects of quality and operation that would impair the usefulness of the original air conditioner, fan unit,
pressurization unit or heat exchanger (collectively herein referred to as "Product") duringthe Warranty Period. This
Limited Warranty is for all components of the Product, except filters, when installed and operated under the following
conditions:
A. In strict accordance with the Product's Installation and Operation Manual, as may be revised from time to
time with the latest version available at www.voltairesys.com.
B. Maximum voltage variation no greater than plus or minus 10% of nameplate nominal rating.
C. Maximum frequency variation no greater than plus or minus 3 Hz. of nameplate nominal rating.
D. Must not exceed minimum and maximum stated temperatures on the nameplate.
E. Not to exceed (BTU/Hr.) rating, including any heat sink, as indicated on the nameplate.
F. Installed per all local, State and Federal legal requirements.
G. The unit must not be restarted for a period of five (5) minutes after intentional oraccidental shut-off of a
compressor. (This does not apply to heatexchanger or filter fan.)
The Limited Warranty is void and not applicable if:
A. The Product is installed improperly
B. The Product is not maintained properly, including prolonged operation with dirty filters or coils
C. The Product is modified, abused and/or tampered
D. The Product is applied in an incorrect manner, including operation within a corrosive atmosphere (including
but not limited to coastal applications)
E. The Product is used with the incorrect refrigerant (air conditioners)
F. The Product is damaged and/or inoperable due to accidents or events beyond the reasonable control of
VoltAire and Acts of God
G. The Product is repaired with parts not provided by VoltAire
H. The Product is installed and operated outside the United States, Mexico, and/or Canada.
Damage during freight is not included with this Limited Warranty. The Purchaser must insure the Product is installed
by a competent, professional, qualified contractor, following all local, state, and national legal requirements and
industry standards. The Purchaser must provide adequate maintenance (e.g.filter changes, coil cleanings).
The Limited Warranty covers the Product for the Purchaser only during the Warranty Period, and the Limited
Warranty does not include any labor,freight, and/or consequential damages or loss. Upon Notification by the
Purchaser, VoltAire solely reserves the right to either, as Purchaser’s sole remedy:
Ship replacementparts to the Purchaser for the Purchaser's infield replacement of the part. Infield
replacement will require the Purchaserto provide a purchase order to VoltAire for thestandard cost of the

Pressurization Module with
Plenum Installation, Operation
and Maintenance Manual
VoltAire Systems, LLC
Specifications are subject to change without notice
Page 20 of 20
VoltAire Doc. # DA0322A
Published: June 13, 2023
part and after infield replacement return the original part to VoltAire with freight cost by Purchaser. Within
fourteen (14) days of receipt of the returned part VoltAire will review and analyze the returned part. If the
part is found to be defective by VoltAire a credit will be issued to the Purchaser. Parts returned to VoltAire
and found not to be defective will result in no credit applied to Purchaser's account and the Purchaser will be
required to pay for the replacement part.
Or, request the return of the Product for evaluation. Return of the Product must be preceded by the
issuance of a VoltAire Return Merchandise Authorization (RMA). The RMA will require that shipping costs
be paid by the Purchaser to returnthe Product to VoltAire. Within fourteen (14)days of receipt of the
returned Product VoltAire will review and analyze the Product. If the Product is determined by VoltAire to be
defective, VoltAire may repair orreplace the Product,and will ship the Product to the Purchaser for the
Purchaser's installation in the field with no labor costs reimbursed by VoltAire. If the Product is determined
by VoltAire to NOT be defective, the Purchaser will be notified and a Purchase Order must be issued in the
amount required for the Product to be packaged andreturned to the Purchaser.
DISCLAIMERS AND LIMITATIONS OF LIABILITY:
THIS LIMITED WARRANTY CONSTITUTES THE ENTIRE WARRANTY FOR THE VOLTAIRE PRODUCT AND IS
IN LIEU OF ALL OTHER WARRANTIES, EXPRESS AND IMPLIED, INCLUDING ANY WARRANTY OF
MERCHANTABILITY AND WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. THERE ARE NO
WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
VOLTAIRE IS NOT RESPONSIBLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY NATURE
WHATSOEVER, INCLUDING, BUT NOT LIMITED TO, LOST PROFITS, ATTORNEYS FEES, AND LOSS OF USE
DAMAGES.
VOLTAIRE EXCLUDES ALL LIABILITY FOR OR ARISING FROM ANY NEGLIGENCE ON ITS PART OR ON THE
PART OF ANY OF ITS EMPLOYEES, AGENTS, OR REPRESENTATIVES IN RESPECT TO THE MANUFACTURE
OR SUPPLYOF GOODS, INCLUDING THE PRODUCT, OR THE PROVISION OF SERVICES RELATING TO THE
GOODS, INCLUDING THE PRODUCT.
THIS LIMITED WARRANTY, DISCLAIMER, AND LIMITATION OF LIABILITY SHALL SUPERSEDE ANY TERMS OF
PURCHASE PROVIDED BY THE PURCHASER AT THE TIME OF THE PURCHASE, AND THE LIMITATION OF
LIABILITY SHALL SURVIVE FROM THE DATE OF THE PURCHASE TO THE DATE OF DISCONTINUED USE.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL
DAMAGES,SO THE ABOVE LIMITATION OF CONSEQUENTIAL DAMAGES MAY NOT APPLY.
This manual suits for next models
1
Table of contents
Popular Control Unit manuals by other brands

ABB
ABB LD 800HSE manual

Siemens
Siemens VVI46 /2 Series Mounting instructions

Pilz
Pilz PSSu K S 16DO 0.5 operating manual

Miranda
Miranda NV5100MC Master Control Reference manual

Hydro Instruments
Hydro Instruments PRV-71H Series Operation and maintenance manual

Balluff
Balluff BIS V-6111 series Technical Description, User's Guide