Voltronic Power Galleon II 3P User manual

3/3 30K~40K Online UPS
Uninterruptible Power Supply System
Version: 1.0
User Manual

Please comply with all warnings and operating
instructions in this manual strictly. Save this
manual properly and read carefully the following
instructions before installing the unit. Do not
operate this unit before reading through all
safety information and operating instructions
carefully.

Table of Contents
1. SAFETYAND EMC INSTRUCTIONS...........................................................................................................................1
1-1. TRANSPORTATION AND STORAGE ................................................................................................................................... 1
1-2. PREPARATION................................................................................................................................................................ 1
1-3. INSTALLATION ............................................................................................................................................................... 1
1-4. CONNECTION WARNINGS .................................................................................................................................... 2
1-5. OPERATION ................................................................................................................................................................... 3
1-6. STANDARDS................................................................................................................................................................... 3
2. INSTALLATION AND OPERATION .............................................................................................................................4
2-1. UNPACKING AND INSPECTION......................................................................................................................................... 4
2-2. REAR PANEL VIEW......................................................................................................................................................... 4
2-3. SINGLE UPS INSTALLATION ........................................................................................................................................... 6
2-4. UPS INSTALLATION FOR PARALLEL SYSTEM ....................................................................................................................8
2-5. SOFTWARE INSTALLATION.............................................................................................................................................. 8
3. OPERATIONS ................................................................................................................................................................... 9
3-1. BUTTON OPERATION...................................................................................................................................................... 9
3-2. LED INDICATORS AND LCD PANEL................................................................................................................................. 9
3-3. AUDIBLE ALARM .......................................................................................................................................................... 11
3-4. SINGLE UPS OPERATION ............................................................................................................................................. 11
3-5. PARALLEL OPERATION (ONLY FOR THE PARALLEL MODELS)............................................................................................ 14
3-6. ABBREVIATION &MEANING IN LCD DISPLAY................................................................................................................ 15
3-7. LCD SETTING ............................................................................................................................................................. 16
3-8. OPERATING MODE/STATUS DESCRIPTION .................................................................................................................... 21
3-9. FAULT CODE ............................................................................................................................................................... 27
3-10.WARNING INDICATOR ................................................................................................................................................ 27
3-11.WARNING CODE......................................................................................................................................................... 28
4. TROUBLE SHOOTING ................................................................................................................................................. 29
5. STORAGE AND MAINTENANCE............................................................................................................................... 31
5-1. STORAGE .................................................................................................................................................................... 31
5-2. MAINTENANCE............................................................................................................................................................. 31
6. SPECIFICATIONS.......................................................................................................................................................... 32

1
1. Safety and EMC instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using
the unit!
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and
impact.
The UPS must be stored in the room where it is ventilated and dry.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm environment.
The UPS system must be absolutely dry before being installed. Please allow at least two hours for the
UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or nearby heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type
equipment)) to the UPS output sockets or terminal.
Place cables in such a way that no one can step on or trip over them.
Do not block air vents in the housing of UPS. The UPS must be installed in a location with good
ventilation. Ensure enough space on each side for ventilation.
UPS has provided earthed terminal, in the final installed system configuration, equipotential
earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified maintenance personnel.
An appropriate disconnect device as short-circuit backup protection should be provided in the
building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the
UPS in any mode of operation should be provided in the building wiring installation.
Connect the earth before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical laws and
regulations.

2
1-4. Connection Warnings
There is no standard backfeed protection inside, please isolate the UPS before working according to
this circuit. The isolation device must be able to carry the UPS input current.
•This UPS should be connected with TN earthing system
•The power supply for this unit must be three-phase rated in accordance with the equipment nameplate.
It also must be suitably grounded
•Use of this equipment in life support applications where failure of this equipment can reasonably be
expected to cause the failure of the life support equipment or to significantly affect its safety or
effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic
mixture with air, oxygen or nitrous oxide.
•Connect your UPS power module’s grounding terminal to a grounding electrode conductor.
•The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS
is not connected to an AC supply.
Before working on this circuit
-Isolate Uninterruptible Power System (UPS)
-Then check for Hazardous Voltage between all
terminals including the protective earth.
Risk of Voltage Backfeed

3
1-5. Operation
Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any
time since this would cancel the protective earth of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output sockets or
output terminal blocks may be electrically live even if the UPS system is not connected to the building
wiring outlet.
In order to fully disconnect the UPS system, first press the “OFF” button and then disconnect the
mains.
Ensure that no liquid or other foreign objects can enter into the UPS system.
The UPS can be operated by any individuals with no previous experience.
1-6. Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission...............................:IEC/EN 62040-2
Category C3
Radiated Emission..................................:IEC/EN 62040-2
Category C3
*EMS
ESD.........................................................:IEC/EN 61000-4-2
Level 4
RS........................................................ ...:IEC/EN 61000-4-3
Level 3
EFT......................................................... :IEC/EN 61000-4-4
Level 4
SURGE................................................... :IEC/EN 61000-4-5
Level 4
CS........................................................... :IEC/EN 61000-4-6
Level 3
Power-frequency Magnetic field.............. :IEC/EN 61000-4-8
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevent disturbances.

4
2. Installation and Operation
There are two different types of online UPS: standard and long-run models. Please refer to the following
model table.
Model
Type
Model
Type
30K
Standard
model
30KL
Long-run
model
40K
40KL
We also offer optional parallel function for these two types by request. The UPS with parallel function is
called as “Parallel model”. We have described detailed installation and operation of Parallel Model in the
following chapter.
2-1. Unpacking and Inspection
Unpack the package and check the package contents. The shipping package contains:
● One UPS
●One user manual
● One monitoring software CD
●One RS-232 cable (option)
●One USB cable
●One parallel cable (only available for parallel model)
●One share current cable (only available for parallel model)
NOTE: Before installation, please inspect the contents. Be sure that nothing inside the package is damaged
during transportation. Do not turn on the device and notify the carrier and dealer immediately if there is any
damage or shortage of some parts. Please keep the original package in a safe place for future use.
2-2. Rear Panel View
Diagram 1: 30KL Rear Panel Diagram 2: 40KL Rear Panel

5
Diagram 3: 30K Rear Panel Diagram 4: 40K Rear Panel
Diagram 5: 30KL/ 40KL Diagram 6: 30K/40K Input/output
Input/Output Terminal Terminal
1. RS-232 communication port
2. USB communication port
3. Emergency power off function connector (EPO connector)
4. Share current port (only available for parallel model)

6
5. Parallel port (only available for parallel model)
6. Intelligent slot
7. External battery terminal (Only available for long-run model)
8. Line input circuit breaker
9. Maintenance bypass switch (option)
10. Input/Output terminal
11. Output grounding terminal
12. Output terminal: connect to mission-critical loads
13. Line input terminal
14. Input Grounding terminal
2-3. Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and the
following instructions must be executed by professional personnel.
1) Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid
the hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS when its rated current is less
than the UPS’s maximum input current. Otherwise, the receptacle may be burned and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
Wiring spec (AWG)
Input(Ph)
Output(Ph)
Neutral
Battery
Ground
30K
8
8
4
4
30KL
8
8
4
4
4
40K
7
7
4
4
40KL
7
7
4
4
4
NOTE 1: The cable for 30K/30KL should be able to withstand over 63A current. It is recommended to
use AWG 8 or thicker wire for Phase and AWG 4 or thicker wire for Neutral for safety and efficiency.
NOTE 2: The cable for 40K/40KL should be able to withstand over 80A current. It is recommended to
use AWG 7 or thicker wire for Phase and AWG 4 or thicker wire for Neutral for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and
regulations.
5) Remove the cover of the terminal block on the rear panel of UPS. Then connect the wires according to
the following terminal block diagrams: (Connect the earth wire first when making wire connection.
Disconnect the earth wire last when making wire disconnection!)

7
Terminal block wiring diagram
NOTE 1: Make sure that the wires are connected tightly with the terminals.
NOTE 2: Please install the output breaker between the output terminal and the load and the breaker
should be qualified to leakage current protective function if necessary.
6) Put the cover of terminal block back to the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is OFF before installation. The UPS should not be turned on during wiring connection.
●Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the
standard internal battery to the external battery. The battery type and voltage may be different. If
connected together, they maybe cause the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed. If
not, please install it carefully. Switch off the battery breaker before installation.
NOTE: Set the battery pack breaker in “OFF” position and then install the battery pack.
● Pay highly attention to the rated battery voltage marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. Wrong battery
connection may cause permanent damage of the UPS. Make sure the voltage of the battery pack is
correct.
● Pay highly attention to the polarity marked on external battery terminal block, and make sure the correct
battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
● Make sure the protective earth ground wiring is correct. The specification of wire current, color, position,
connection and conductance reliability should be checked carefully.
● Make sure the utility input & output wiring is correct. The specification of wire current, color, position,
connection and conductance reliability should be checked carefully. Make sure the L/N site is correct, not
reverse and short-circuited.

8
2-4. UPS Installation for Parallel System
If the UPS is only available for single operation, you may skip this section to the next.
1) Install and wires the UPSs according to the section 2-3.
2) Connect the output wires of each UPS to an output breaker.
3) Connect all output breakers to a major output breaker which will be directly connected to the loads.
4) Each UPS is connected to an independent battery pack.
5) Refer to the following wiring diagram:
Wiring diagram of parallel system
2-5. Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.

9
3. Operations
3-1. Button Operation
Button
Function
ON/Enter Button
Turn on the UPS: Press and hold the button more than 0.5s until the UPS is on.
Enter Key: Press this button to confirm the selection in setting menu.
OFF/ESC Button
Turn off the UPS: Press and hold the button more than 0.5s until the UPS is off.
Esc key: Press this button to return to last menu in setting menu.
Test/Up Button
Battery test: Press and hold the button more than 0.5s to test the battery while
in AC mode and CVCF* mode.
UP key: Press this button to display next selection in setting menu.
Mute/Down Button
Mute the alarm: Press and hold the button more than 0.5s until the buzzer is
mute. Please refer to section 3-4-9 for details.
Down key: Press this button to display previous selection in setting menu.
Test/Up +
Mute/Down Button
Press and hold the two buttons simultaneously more than 1s to enter/exit the
setting menu.
* CVCF means Constant Voltage and Constant Frequency.
3-2. LED Indicators and LCD Panel
LED Indicators:
There are 4 LEDs on front panel to show the UPS working status:
Mode LED
Bypass
Line
Battery
Fault
UPS On
●
●
●
●
No Output mode
○
○
○
○
Bypass mode
●
○
○
○
AC mode
○
●
○
○
Battery mode
○
○
●
○
CVCF mode
○
●
○
○
Battery Test
●
●
●
○
ECO mode
●
●
○
○
Fault
○
○
○
●
Note: ●means LED is lighting, and ○means LED is faded.
LCD panel
LED indicators

10
LCD Panel:
Display
Function
Backup time information
Indicates the battery discharge time in numbers
H: hours, M: minutes, S: seconds
Fault information
Indicates the warning and fault occurs.
Indicates the fault codes, and the codes are listed in details in section 3-9.
Mute operation
Indicates the UPS alarm is disabled.
Output & Battery voltage information
Indicates the output voltage, frequency or battery voltage.
Vac: output voltage, Vdc: battery voltage, Hz: frequency
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload occurs.
Indicates the load or the output is short circuited.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.

11
Battery information
Indicates the battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates the battery is not connected.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicates the input voltage or frequency or battery voltage.
Vac: Input voltage, Vdc: battery voltage, Hz: input frequency
3-3. Audible Alarm
Description
Buzzer status
Muted
UPS status
Bypass mode
Beeping once every 2 minutes
Yes
Battery mode
Beeping once every 4 seconds
Fault mode
Beeping continuously
Warning
Overload
Beeping twice every second
No
Others
Beeping once every second
Fault
All
Beeping continuously
Yes
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON”position (the
step is only available for long-run model). Then set the line input breaker at “ON”position (for dual
input unit, also set the bypass input breaker at “ON”). In the meanwhile, the fan is running and the
UPS starts power on mode for initialization. Several seconds later, UPS operates in Bypass mode
and supplies power to the loads via the bypass.
NOTE: When UPS is in Bypass mode, the output voltage will directly power from utility after you
switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your
precious devices, you should turn on the UPS. Please refer to next step.
2) Press and hold the “ON” button for 0.5s until the buzzer will beep once to turn on the UPS.
3) A few seconds later, the UPS will enter AC mode. If the utility power is abnormal, the UPS will
operate in Battery mode without interruption.
NOTE: When the UPS is running out of battery, it will shut down automatically in Battery mode. When
the utility power is restored, the UPS will automatically restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the two groups battery are connected correctly as ”+, GND,-”order and the breaker
of the battery pack is at “ON”position (only for long-run model).
2) Press the “ON” button to set up the power supply for the UPS and UPS will enter power on mode.
After initialization UPS will enter No Output mode. Then, press and hold the “ON” button for 0.5s
until the UPS is on and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter Battery mode.

12
3. Connect devices to UPS
After the UPS is turned on, you can connect devices to the UPS.
1) Turn on the UPS first and then switch on the devices one by one. The LCD panel will display total
load level.
2) If it is necessary to connect the UPS to the inductive loads such as a printer, the in-rush current
should be calculated carefully in case that it meets the maximum capacity of the UPS because of
the high power consumption of this kind of load.
3) If the UPS is overload, the buzzer will beep twice every second.
4) When the UPS is overload, please remove some loads immediately. It is recommended to have the
total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload
for system safety.
5) If the overload time exceed acceptable duration listed in spec at AC mode, the UPS will be
automatically transferred to bypass mode. After the overload device is removed, it will return to AC
mode. If the overload time exceeds acceptable duration listed in spec at battery mode, the UPS will
show fault status. At this time, if bypass is enabled, the UPS will power the load via bypass. If
bypass function is disabled or the input power is not within acceptable range of bypass mode, it will
cut off the connection of output directly.
4. Charge the batteries
1) After the UPS is connected to the utility power and turned on in AC mode, the charger will charge
the batteries automatically except in Battery mode, during battery self-test, overload or high
battery voltage duration.
2) Be sure to charge batteries at least 10 hours before operation. Otherwise, the backup time may be
shorter than expected time.
3) Make sure the battery numbers set on the control board (Please refer to the section 3-4-12 for
detailed setting) is consistent to real connection.
5. Battery mode operation
1) When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the
battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery
voltage drops to the alarm level, the buzzer will beep quickly (once every second) to remind users
that the battery is at low level and the UPS will shut down automatically soon. Users could switch
off some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is
no more loads to be switched off at that time, it’s suggested to shut down all loads as soon as
possible to protect the devices or save data. Otherwise, there is a risk of data loss or load failure.
2) In Battery mode, if buzzer sounds annoying, users can press the Mute button to disable the buzzer.
3) The backup time of the long-run model depends on the capacity of external battery.
4) The backup time may vary from different environmental temperature and load type.
5) When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5
hours, UPS will shut down automatically to protect the battery. This battery discharge protection
can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section)
6. Test the batteries
1) If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you can
press the “Test”button to activate battery self-test of the UPS.
2) Users also can set battery self-test through monitoring software.
7. Turn off the UPS with utility power supply in AC mode
1) Turn off the inverter of the UPS by pressing “OFF” button for at least 0.5s, and then the buzzer will
beep once. The UPS will turn into Bypass mode.
NOTE 1: If the UPS is set to enable the bypass output, it will bypass voltage from utility power to
output terminal even though the UPS (inverter) is off.

13
NOTE 2: After turning off the UPS, please be aware that the UPS is working in Bypass mode and
there is a risk of power loss for connected devices.
2) In Bypass mode, output voltage of the UPS is still existing. In order to cut off the output, switch off
the line input breaker (for dual input unit, also switch off the bypass line breaker). A few seconds
later, if there is no display shown on the display panel, UPS is completely off.
8. Turn off the UPS without utility power supply in Battery mode
1) Turn off the UPS by pressing “OFF” button for at least 0.5s until the buzzer will beep once.
2) The power of the output will be cut off. There is no display shown on the display panel.
9. Mute the buzzer
1) To mute the buzzer, please press the “Mute” button for at least 0.5s. If you press it again after the
buzzer is muted, the buzzer will beep again.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
10. Operation in warning status
1) When Fault LED flashes and the buzzer beeps once every second, it means that some problems
occur during UPS operation. Users can get the warning indication from LCD panel. Please check the
trouble shooting table in chapter 4 for details.
2) Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the
details.
11. Operation in Fault mode
1) When Fault LED lights on and the buzzer beeps continuously, it means that there is a fatal error in
the UPS. Users can get the fault code from display panel. Please check the trouble shooting table in
chapter 4 for details.
2) Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try
to turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact
the distributor or service center immediately.
3) For emergency case, please cut off the connection from utility, external battery, and output
immediately to avoid more risk or danger.
12. Operation of changing battery numbers (only 16-pc battery model supported)
1) This operation is only available for professional or qualified technicians.
2) Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance
bypass switch on the rear panel and turn the maintenance switch to “BPS” position first.
3) Switch off the line input breaker (for dual input unit, also switch off the bypass input breaker), and
switch off the battery breaker (only available for long-run model).
4) Remove the cabinet cover, and disconnect battery wire for standard model. Then modify the
jumper of JS4 & JS5 on the control board to set the battery numbers as following table.
Battery Number in series
JS5
JS4
16
0
0
18
0
1
19
1
0
20
1
1
Note: 1 = connect with jumper; 0 = no jumper; x = the pins are for other functions.
5) Modify the battery pack for the setting number carefully. After complete it, put the cover back,
switch on the battery breaker for long-run model.
6) Switch on the line input breaker (for dual input unit, also switch on the bypass input breaker) and
the UPS will enter Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance
switch to “UPS” position and then turn on the UPS.

14
3-5. Parallel Operation (Only for the parallel models)
1. Parallel system initial startup
First of all, please make sure all of the UPSs are parallel models with same configuration.
1) Turn on each UPS to AC mode respectively (Refer to section 3-4(1)). Then, measure the inverter
output voltage of each phase for each UPS with multimeter. If the difference between real output
voltage and setting value is more than 1.5V, please calibrate the voltage by configuring inverter
voltage adjustment (Refer to Program 15, 16 and 17 in section 3-7) in LCD setting. If the difference
remains more than 1.5V after calibration, please contact your local distributor or service center for
help.
2) Calibrate the output voltage measurement by configuring output voltage calibration (Refer to
Program 18, 19, and 20 in section 3-7) in LCD setting to make sure the difference between real
output voltage and detected value of UPS is less than 1V.
3) Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.
4) Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one
with the parallel cable and share current cable, and then screw the cover back.
5) Turn on the parallel system in AC mode:
a) Turn on the line input breaker of each UPS (for dual input, also turn on bypass input breaker).
After all UPSs enter bypass mode, measure the output voltage between two UPSs in the same
phase to make sure the accuracy of phase sequence. If these two voltage differences are near
zero, that means all connections are correct. Otherwise, please check if the wirings are
connected correctly.
b) Turn on the output breaker of each UPS.
c) Turn on each UPS in turns. After a while, the UPSs will enter AC mode synchronously and then,
the parallel system is completed.
6) Turn on the parallel system in Battery mode:
a) Turn on the battery breaker (only available in long-run model) and output breaker of each UPS.
b) Turn on any UPS. A few seconds later, the UPS will enter battery mode.
c) Then, turn on another UPS. A few seconds later, the UPS will enter battery mode and be added
to the parallel system.
d) If the third UPS is in parallel, follow the same procedure in c). Then, the parallel system is
complete.
If more detailed information of parallel operation is needed, please contact supplier or service
center.
2. Add one new unit into the parallel system
1) New unit can be added into the parallel system when whole system is running. You must cut off the
load and shut down the system.
2) Make sure all of the UPS are the parallel models, and follow the wiring. Please refer to section 2-4.
3) Install the new parallel system. Please refer to the section 3-5.
3. Remove one unit from the parallel system
There are two methods to remove one unit from the parallel system:
First Method:
1) Press the “OFF” key twice and each time should last for more than 0.5s. Then, the UPS will enter
bypass mode or no output mode if there is no.
2) Turn off the output breaker of this unit, and then turn off the input breaker of this unit.
3) After it is shut down, you can turn off the battery breaker (for long-run model) and remove the
parallel and share current cables. And then remove the unit from the parallel system.
Second Method:

15
1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
2) Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance
switches from “UPS” to “BPS”. Turn off all the input breakers and battery breakers in parallel system.
3) Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Then, remove it from parallel system.
4) Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode. Set
the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
5) Turn on the remaining UPS according to the previous section.
Warning: (Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all of the maintenance
switches in each unit are at the same position.
● When parallel system is turned on to work-through inverter, please do not operate the maintenance
switch of any unit.
3-6. Abbreviation & Meaning in LCD Display
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ATO
Auto
BAT
Battery
NCF
Normal mode (not CVCF mode)
CF
CVCF mode
SUB
Subtract
ADD
Add
ON
On
OFF
Off
FBD
Not allowed
OPN
Allow
RES
Reserved
N.L
Neutral line loss
CHE
Check
OP.V
Output voltage
PAR
Parallel, 001 means the first UPS
AN
The first phase
BN
The second phase
CN
The third phase
AB
The first line

16
BC
The second line
CA
The third line
HS.H
Hot Standby
3-7. LCD Setting
There are three parameters to set up the UPS. Refer to following diagram.
Parameter 1
Parameter 2 Parameter 3
Programs available list for parameter 1:
Code
Description
Bypass /
No Output mode
AC
mode
ECO
mode
CVCF
mode
Battery
mode
Battery
Test
01
Output voltage
Y*
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
ECO mode enable/disable
Y
06
Voltage range for ECO mode
Y
07
Frequency range for ECO mode
Y
08
Bypass mode setting
Y
Y
09
Maximum battery discharge time
setting
Y
Y
Y
Y
Y
Y
10
Reserved
Reserved for future options
11
Hot Standby Function Setting
Y
12
Neutral loss detection
Y
Y
Y
Y
Y
Y
13
Battery voltage calibration
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter A voltage adjustment
Y
Y
Y
16
Inverter B voltage adjustment
Y
Y
Y
17
Inverter C voltage adjustment
Y
Y
Y
18
Output A voltage calibration
Y
Y
Y
19
Output B voltage calibration
Y
Y
Y
20
Output C voltage calibration
Y
Y
Y
*Y means that this program can be set in this mode.
Note: All parameter settings will be saved only when UPS shuts down normally with internal or external battery
Parameter 1: It’s for program alternatives. Please refer to
the tables below for setting program.
Parameter 2 and parameter 3 are the setting options or
values for each program.
Note: Please select “Up” or “Down” button to change
the programs or parameters.

17
connection. (Normal UPS shutdown means turning off input breaker in bypass/no output mode).
01: Output voltage
Interface
Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208: Presents output voltage is 208Vac
220: Presents output voltage is 220Vac
230: Presents output voltage is 230Vac
240: Presents output voltage is 240Vac
02: Output frequency
Interface
Setting
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three
options in parameter 2:
50.0Hz: The output frequency is set to 50.0Hz.
60.0Hz: The output frequency is set to 60.0Hz.
ATO: If selected, output frequency will be set according to the
latest frequency of normal utility. If it is from 46Hz to 54Hz, the
output frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the
output frequency will be 60.0Hz. ATO is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You
may choose the following two options in parameter 3:
CF: Setting UPS to CVCF mode. If selected, the output frequency
will be fixed at 50Hz or 60Hz according to the setting in parameter
2. The input frequency is from 46Hz to 64Hz.
NCF: Setting UPS to normal mode (not CVCF mode). If selected,
the output frequency will be synchronized with the input
frequency within 46~54 Hz at 50Hz or within 56~64 Hz at 60Hz
according to the setting in parameter 2. If 50 Hz selected in
parameter 2, UPS will transfer to battery mode when input
frequency is not within 46~54 Hz. If 60Hz selected in parameter 2,
UPS will transfer to battery mode when input frequency is not
within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.
03: Voltage range for bypass
Interface
Setting
Parameter 2: Set the acceptable low voltage for bypass. Setting
range is from 176V to 209V and the default value is 176V.
Parameter 3: Set the acceptable high voltage for bypass. Setting
range is from 231V to 276V and the default value is 264V.
Table of contents
Other Voltronic Power UPS manuals

Voltronic Power
Voltronic Power Galleon One 6K User manual

Voltronic Power
Voltronic Power 6K User manual

Voltronic Power
Voltronic Power Nano 400 User manual

Voltronic Power
Voltronic Power Taurus UPS-7.5 User manual

Voltronic Power
Voltronic Power Bonnie 50W User manual

Voltronic Power
Voltronic Power 1K Online UPS For Dual-mains Input User manual

Voltronic Power
Voltronic Power 6K User manual

Voltronic Power
Voltronic Power 6K User manual

Voltronic Power
Voltronic Power Giant 3P/3P User manual

Voltronic Power
Voltronic Power 1K Online UPS For Dual-mains Input User manual