RXAC-2M Quick Start Guide
Customer Support: support@voltserver.com | 888-622-8658, Option 1
VoltServer Inc. | www.voltserver.com | contact@voltserver.com
Rev B 5 of 8
WARNING!
VoltServer RX Receiver inputs are intended to be
powered by VoltServer TX Transmitter products
only. Ensure that only VoltServer TX Transmitter
products are used as sources of power for this RX
Receiver unit.
WARNING!
The minimum wire gauge for use with VoltServer
GEN2 Transmitters is 18AWG copper conductors.
Mutual conductor capacitance shall be no more that
40pF per foot or 164 pF per meter.
WARNING!
The voltage rating of the transmission wiring
between VoltServer TX Transmitter and RX
Receiver(s) must be a minimum of 300Vrms.
The surface of this unit may become
hot while running. Shut down the unit
and allow to cool before servicing.
This symbol indicates the main earth
ground terminal for the device. See
“Grounding” section.
Do not open the unit. There are no eld
serviceable parts inside the unit. Risk of
high touch current under single fault
conditions. Up to 34mA may be present.
Symbols
NOTE
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and (2) this device must accept any interference
received, including interference that may cause
undesired operation.
Warranty Statement
With the exception of the fan module, there are no
serviceable parts within the RXAC-2M. Opening or
modifying the unit will void the warranty.
Accessories (Sold Separately)
KITCBL-RXAC-C19: Power Cable, C14 to C19, Heavy
Duty, 15A, 250V, 14AWG, 6ft, Black
KITCBL-RXAC-C15: Power Cable, C14 to C15, Heavy
Duty, 15A, 250V, 14AWG, 6ft, Black
KITCBL-RXAC-C15-Y: Power Cable, C14 to two (2)
C15, Heavy Duty, 15A, 250V, 14AWG, 2.3ft, Black
RXAC-FAN-MODULE: Replacement fan module for
RXAC-2M
RXAC-SHELF: 2U, 19" Rack-mount Shelf, Holds 2
RXAC-2M Receivers
Servicing the Fan
If the RXAC-2M is displaying an eight red LED fault code,
which indicates a hardware failure, the modular fan may
need servicing. Conrm fan failure by feeling for a lack
of pressure coming from the fan grate. Contact
VoltServer customer support to make them aware of the
fault and request a replacement fan module.
Replacement fan module: SKU-FAN-MODULE
RXAC-SHELF
RXAC-SHELF populated with 2x RXAC-M