INPUT SIGNAL
• Use shielded wire for signal wiring where high level
noise is generated or when the wiring distance is long.
• Control with a 1 to 5 V input signal becomes an input
resistance 250 . Provide a voltage that can safely
20mA or more than.
DC POWER SUPPLY
• Battery or full wave rectification can be used.
• Consider an inrush current of motor.
(It is 1.5 to 3 times of consumed current.)
• When using a DC voltage, be selected the wire
thickness by the wiring distance.
• Do not use power supply that require more than
1 second with rise and fall time.
INPUT SIGNAL AND OPERATION MODE
The input signal and operation mode are set as
follows. (Factory shipped)
Input signal 4 to 20 mA or 1 to 5 V
Operation mode Mode A
Operation SHUT by decreased signal.
OPEN by increased signal.
OPERATION
TESTING
• Make sure that power supply voltage is correct. Also
check operating position, wiring, speed and signals.
• During trial operation, check that valve movement and
output signal are correct.
CONFIRM THE OPERATING CONDITION
• Adjust fluid condition, controller setting, sensor etc. so
that stable control is achieved.
• When used in an unstable control state, the life of the
actuator and the valve will be shortened.
• The desired control state is stable at the target value.
Adjust the PID setting value of the controller when
overshooting the target value greatly, when not
converging for a long time or hunting operation. Also,
when the time delay is large, please consider the
sensor position.
DUTY CYCLE (PDX)
Confirm that the operation frequency is within the
specified duty cycle.
Use beyond the load time rate range will affect
product life. Also, it may cause burnout.
Duty cycle is a value that regulates the opening /
closing frequency of the actuator.
The meaning of 50 % 30 minutes for Duty cycle is
that 15 minutes (50 % of 30 minutes) operation is
possible. The calculated value obtained by dividing
15 minutes by the operation time is the number of
times of operation within 30 minutes.
ATTENTION
• Do not change an unnecessary dip switch.
• Keep power supplied for built-in space heater to
prevent condensation inside actuator.
• Do not touch the moving parts of actuator in
operation.
• Never put anything on the actuator or make it into a
foothold.
MANUAL OPERATION
PRECAUTIONS
• Be sure to turn off the power before manual operation.
• Operate manually with reference to the opening
degree label. Do not turn beyond the fully open / fully
closed position. Operation failure may occur during
automatic operation.
THE WAY OF OPERATION
PDX / PHX PDX / PHX (06K)
Manual operation can be possible by pulling down
manual clutch knob. Set the knob to manual
position and operate the joint by using an
adjustable wrench in the SHUT/OPEN direction.
When it becomes in the position besides the range
of operation in the case of manual operation, it may
stopped automatic moving.
In case the manual clutch knob is not easy to pull
down, try moving joint or manual shaft to the
opposite direction by wrench. For automatic
operation, reset the knob to automatic position.
Be sure to confirm that knob is reset completely.
Before automatic operation, be sure to remove
wrench.
MAINTENANCE
• To prevent electric shock, be sure to turn off the power
when removing the actuator cover.
• Do the routine maintenance at least once in half a
year.
Inspection items
• Confirm operation of opening and closing.
• Confirm that an actuator is not hot excessively.
• Confirm existence of abnormal noise and
vibration during operation.
• Confirm whether screws are loose or not.
• Confirm that water or condensation no remains
in the actuator.