E5EN E5EN
Specifications
JRATINGS
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC, 50/60 Hz/24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 9 VA 5 VA/4 W
Sensor input Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum resistance thermometer: Pt100, JPt100
Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C
Voltage input: 0 to 50 mV
Control output Relay output SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations
Voltage output 12 VDC +15%/–20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
Current output 4 to 20 mA DC, load: 600 Ωmax., resolution: approx. 2,600
Alarm output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations
Control method PID or ON/OFF control
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and single-lighting indicator
Character height: PV: 14.0 mm; SV: 9.5 mm
Ambient operating temperature –10_C to 55_C (14°F to 131°F) with no condensation or icing
Storage temperature –25_C to 65_C (–13°F to 149°F) with no condensation or icing
Ambient humidity 25% to 85% RH
JCHARACTERISTICS
Indication accuracy Thermocouple: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max. (See Note)
Platinum resistance thermometer: ±0.5% of indicated value or ±1_C, whichever greater, ±1 digit max.
Analog input: ±0.5% FS±1 digit max.
CT input: ±5% FS±1 digit max.
Hysteresis 0.1 to 999.9 EU (in units of 0.1 EU)
Proportional band (P) 0.1 to 999.9 EU (in units of 0.1 EU)
Integral time (I) 0 to 3999 s (in units of 1 s)
Derivative time (D) 0 to 3999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Sampling period 500 ms
Insulation resistance 20 MΩmin. at 500 VDC
Dielectric strength 2000 VAC, 50 or 60 Hz for 1 min between different charging terminals
Vibration resistance 10 to 55 Hz, 10 m/s2for 2 hours each in X, Y and Z directions
Shock resistance 300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2)
Weight Approx. 310 g; mounting bracket: Approx. 100 g
Protective structure Front panel: NEMA 4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00
Memory protection EEPROM non-volatile memory (number of writes: 100,000)
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U
and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or
less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
(This table continues on the next page.)