RS485 4 wire / RS485 2-wire application with echo
One data channel in each direction is available. The RS485
output driver is activated automatically with each transmis-
sion of data, and goes to the high impedance state again
after the end of transmission. The RS485 receiving channel is
always active in this operating mode.
RS485 2 wire application without echo
One data channel in each direction is available. The RS485
output driver is activated automatically with each transmis-
sion of data, and goes to the high impedance state again
after the end of transmission. The RS485 receiving channel is
deactivated when the driver is on, but is switched on when
the driver is in the high impedance state.
Please see the following table for an explanation of the
operating mode DIP switch:
Operating mode SW1 SW2 SW3 SW4 SW5 SW8
RS232 OFF OFF OFF OFF OFF ON
RS422, RS485, 4-wire bus-master OFF OFF OFF ON OFF OFF
RS485, 4-wire/2-wire with echo OFF ON OFF ON OFF OFF
RS485, 2-wire without echo ON ON OFF ON OFF OFF
Termination
For all RS485 operating modes it is essential that the bus
system be terminated with a termination network which
assures a defined rest state in the high-impedance phases
of bus operation. The bus system can be connected to a
termination network by closing switches #6 and #7 on the
interface module: