Waterite V3175-01 User manual

0
Advanced Water
Conditioners
featuring
the Custom Control F2CC
Valve
OWNER’S
MANUAL
FOR ALL FUSION² F SERIES AND FCA SERIES WATER CONDITIONERS
THIS MANUAL IS TO BE LEFT WITH THE OWNER OF THE EQUIPMENT FOR REFERENCE
PURPOSES AND TECHNICAL GUIDANCE. IT IS STRONGLY RECOMMENDED THAT
QUALIFIED DEALER SERVICE PERSONNEL BE CONTACTED IN THE EVENT OF AN UNKNOWN
INTERRUPTION OF SERVICE OR APPARENT PRODUCT MALFUNCTION. AN ANNUAL
PREVENTATIVE MAINTENANCE INSPECTION BY A WATER PROFESSIONAL IS
RECOMMENDED TO ENSURE TROUBLE-FREE AND CONTINUOUS OPERATION.
www.waterite.com
Waterite
,
Inc. ■ Winnipeg, MB Canada
R2

1
TABLE OF CONTENTS
Preinstallation instructions for dealer
Inside front cover
Specifications
2
Cycle sequence settings
3
Softener System Setup (programming)
4-6
Bypass valve description & diagrams
7
Installation
8-9
Installer settings
Hardness, Override, Regen Time & Time of Day
10
Normal operating & error displays, power loss
11
Low salt warning & resetting it
12
Start- up instructions
13
Replacement parts & valve repair
Front Cover, Drive Assembly and Piston
14
Injector assembly & refill port assembly
15
Drain line 3/4" assembly & flow controls
16
Drain line 1" assembly & flow controls
17
Water meter & bypass valve
18
Installation fitting assemblies & service wrench
19
Control valve servicing
20-24
Troubleshooting procedures
25-26
PREINSTALLATION INSTRUCTIONS
This unit has a control valve which enables the setting of not only the length of each regeneration cycle but also the order
in which cycles (steps of regeneration) occur. The following pages instruct how to set the treatment unit’s sequence of
cycles, cycle times, salt dose, exchange capacity, and gallon capacity/regeneration time. A salt warning option may also
be included.
THE DEALER...
1. Read this page, GENERAL INSTRUCTIONS, INSTALLER SETTINGS, NORMAL OPERATING DISPLAYS, and
LOW SALT WARNING.
2. Complete the CYCLE SEQUENCE SETTINGS.
3. Complete the SOFTENER SYSTEM SETUP.
a. Cycle Times
b. Choose Softener or Filter
c. Set Salt Dose
d. Set Capacity
e. Set How Gallon Capacity Will be Calculated
f. Set Regeneration Time Option
g. Select or Turn Off Low Salt Warning
THE INSTALLER...
1. Read Bypass Valve page.
2. Read GENERAL INSTRUCTIONS, NORMAL OPERATING DISPLAYS, and RESETTING LOW SALT WARNING
(if applicable).
3. Be sure CYCLE SEQUENCE SETTINGS and SOFTENER SYSTEM SETUP are done before leaving for
installation.
4. Follow INSTALLATION INSTRUCTIONS, INSTALLER SETTINGS, TIME OF DAY, and RESETTING SALT

AMOUNT (if applicable).
5. Follow START UP INSTRUCTIONS.
CONTROL VALVE SPECIFICATIONS
SERVICE FLOW RATE & PRESSURE LOSS
(valve only, including bypass valve, but not
including mineral, etc.)
27 gpm (102.2 lpm) @ 15 psi (103 kPa)
P
BACKWASH FLOW RATE & PRESSURE LOSS
(whole conditioner...including bypass valve) 27 gpm (102.2 lpm) @ 25 psi (172 kPa) P
MINIMUM & MAXIMUM OPERATING
PRESSURE 20 psi (138 kPa) - 125 psi ( 862 kPa)
MINIMUM & MAXIMUM OPERATING
TEMPERATURE 40∞F (4∞C) -110∞F (38∞C)
CURRENT DRAW & VOLTAGE 0.5 amperes 110 volts
REGENERANT TANK REFILL RATE 0.5 gpm (1.9 lpm)
INLET / OUTLET FITTING TYPES
(a) 1" NPT elbow
(b) 3/4" & 1" PVC solvent weld socket
(c) 1" straight brass sweat fitting
(d) 3/4" straight brass sweat fitting
DISTRIBUTOR TUBE 1.05" O.D. (3/4" U.S. PVC Pipe Size)
TANK THREAD 2Ω" - 8 NPSM
PC BOARD MEMORY
Non-volatile EEPROM
(electrically erasable programmable read
only memory)
COMPATIBLE REGENERANTS
sodium chloride, potassium chloride, potassium
permanganate, sodium hydroxide, hydrochloric
acid
COMPATIBLE CHEMICALS sodium bisulfite, sodium hydrosulfite,
chlorine, chloramines
GENERAL INSTRUCTIONS
During operation, the normal user displays such as time of day, gallons or days remaining before regeneration (optional),
and salt warning (optional), are shown. Each of these can be viewed by pressing NEXT to scroll through them. When
moving through any displays or programming, if no buttons are pressed within five minutes, the display returns to normal
operating displays. Any changes made prior to the five minute time out are incorporated.
To quickly exit any Programming, Installer Settings, etc., press SET CLOCK. Any changes made prior to the exit are
incorporated.
If desired, two regenerations within 24 hours are possible with a return to the pre-set program. To do a double regeneration
if the control valve is factory set to “NORMAL” or “NORMAL + on 0” (see Step 9S under SOFTENER SYSTEM SETUP):
1. Press the “REGEN” button once. REGEN TODAY will flash on the display.
2. Press and hold the “REGEN” button for three seconds until a regeneration begins.

Once the valve has completed the immediate regeneration, the valve will regenerate one more time at the pre-set
regeneration time.

3
CYCLE SEQUENCE
CYCLE SEQUENCE instructions allows the setting of the order of
the cycle. There are 9 cycles which can be arranged in any order.
Later in this book the INSTALLER SETTINGS allow the setting of
how long cycles will last.
END must be used as the last cycle option. The SERVICE cycle should only be used in brine prefill applications.
If using upflow brine verify that the valve is configured as follows:
1. upflow piston is installed; and
2. injector is located in up hole and injector plug is in down hole.
The following is an example of how to set a valve so that when regeneration is initiated BACKWASH occurs first,
dn
BRINE occurs second, RINSE occurs third, and FILL occurs fourth.
STEP 1CS
STEP 2CS
STEP 3CS
STEP 4CS
STEP 5CS
STEP 6CS
Step 1CS – Press NEXT and simultaneously for 3 seconds until SOFTENING or
FILTERING appears on the display and release. If SOFTENING doesn’t appear, use the
orbutton to display it. Then press NEXT and again for 3 seconds and release. If
screen in Step 2CS does not appear in 5 seconds the lock on the valve is activated. To
unlock press,NEXT , and SET CLOCK in sequence, then press NEXT and
simultaneously for 3 seconds and release.
Then press NEXT and again for 3 seconds and release.
Step 2CS – Press the or , buttons until BACKWASH
appears. Press NEXT to go to Step 3CS.
Press REGEN if you need to return to the previous step.
Step 3CS - Press the or buttons until dn BRINE
appears. Press NEXT to go to Step 4CS.
Press REGEN if you need to return to the previous step.
Step 4CS - Press the or buttons until RINSE
appears. Press NEXT to go to Step 5CS.
Press REGEN if you need to return to the previous step.
Step 5CS - Press the or buttons until FILL
appears. Press NEXT to go to Step 6CS.
Press REGEN if you need to return to the previous step.
Step 6CS - Press the or buttons until END
appears. Press NEXT to exit CYCLE SEQUENCE.
Press REGEN if you need to return to the previous step.
CYCLE OPTIONS
BACKWASH
DN BRINE
FILL
END
RINSE UP BRINE
SOFTENING OR
FILTERING

4
CYCLE SETTING LIMITS
CYCLE OPTIONS
UNITS
LOWER/UPPER LIMIT
DEFAULT
Backwash
minutes 1 to 1200
8
Rinse (fast rinse)
6
dn Brine (brine and slow rinse)
60
UP Brine (brine and slow rinse)
60
Fill (regenerant tank refill)
Lbs.
0.1 to 120.0
60
Service
minutes
1 to 1200
240
SOFTENER SYSTEM SETUP
In SOFTENER SYSTEM SETUP you choose the duration for the cycles selected in CYCLE SEQUENCE and specify
other operating parameters for the system. The upper and lower limits of the allowable values for the cycles are as
follows:
Since no time is associated with the END cycle,
the END cycle will not appear in the SOFTENER
SYSTEM SETUP sequence.
Note: Fill is in pounds of salt.
Step 1S – Press NEXT and simultaneously for 3 seconds and release. If screen in Step 2S
does not appear in 5 seconds the lock on the valve is activated. To unlock press , NEXT,
, and SET CLOCK in sequence, then press NEXT and simultaneously for 3 seconds
and release.
Step 2S – Choose SOFTENING using theor button. Press NEXT to go to Step 3S.
Press REGEN if you want to exit SOFTENER SYSTEM SETUP.
Step 3S – Select the time for the first cycle (which in this example is BACKWASH) using
theor button.
Press NEXT to go to Step 4S.
Press REGEN if you need to return to previous step.
Step 4S – Select the time for the second cycle (which in this example is dn BRINE) using
theor button.
Press NEXT to go to Step 5S.
Press REGEN if you need to return to previous step.
NOTE: The display will flash between cycle number and time, and brine direction (dn or
UP).
Step 5S – Select the time for the third cycle (which in this example is RINSE) using the or
button.
Press NEXT to go to Step 6S.
Press REGEN if you need to return to the previous step.
Step 6S – Select the Lbs. for the fourth cycle (which in this example is FILL) using the or
button. Press NEXT to go to Step 7S. Press REGEN if you need to return to the previous step.
Step 7S – Set Grains Capacity using theor button. The ion exchange capacity is in
grains of hardness as calcium carbonate for the system based on the pounds of salt that will
be used. Calculate the pounds of salt using the fill time previously selected. The allowable
grains capacity range varies from 5000 to 200,000 grains. The increment in- crease is 500 for
the range from 5000 to 30,000, 1000 for the range of 30,000 to 100,000, and 2000 for the
range of 100,000 to 200,000. Grains capacity is affected by the fill time. The grains capacity
for the selected fill time should be confirmed by testing. The capacity and hardness levels
entered are used to automatically calculate reserve capacity when gallon capacity is set to
AUTO. Press NEXT to go to Step 8S.
Press REGEN if you need to return to previous step.

5
SOFTENER SYSTEM SETUP - continued
Step 8S – Set Gallons Capacity using the button. If value is set to:
• “AUTO” ...the gallon capacity will be automatically calculated and reserve capacity will be
automatically estimated.
• “oFF”...the regeneration will be based on the day override set
(see Installer Settings Step 3I).
• a specific number (allowable range 20 to 50,000)...the regeneration initiation will be based
on the value specified. The settable increment is 20 for the range 20 to 1000, 50 for the range
of 1000 to 10,000 and 100 for the range of 10,000 to 50,000.
If “oFF” or a specific number is used, hardness display will not be allowed to be set in Installer
Displays Step 2I. Press NEXT to go to Step 9S. Press REGEN if you need to return to the
previous step.
Step 9S – Set Regeneration Time Options using the button. If value is set to:
• “NORMAL”...the regeneration will occur at the preset time.
• “on O”...the regeneration will occur immediately when the gallons capacity reaches 0 (zero).
• “NORMAL + on 0”...the regeneration will occur at one of the following:
— the preset time when the gallons capacity falls below the reserve or the specified number
of days between regenerations is reached whichever comes first; or,
— immediately after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
Press NEXT to go to Step 10S. Press REGEN if you need to return to the previous step.
Step 10S – Set Low Salt Warning using button. If the value is set to:
• “oFF”...no low salt level warning will appear for the user.
•aspecific value...“FILL SALT” will flash on the display when the calculated remaining
pounds of salt falls below that level. Allowable values range from
10 to 400 pounds in 10 pound increments.
Press NEXT to exit SOFTENER SYSTEM SETUP. Press REGEN
if you need to return to the previous step.

6
SOFTENER SET UP DETAIL TABLE
This table is to be used as a guide or shortcut to the settings made in Step 3I, 8S, and 9S. For quick programming use the
recommended settings shown in row 3 below in bold italic type.
Gallons
Capacity
Regeneration
Time Option
Day
Override
Result
AUTO NORMAL oFF
Reserve capacity automatically estimated.
Regeneration occurs when gallons capacity falls below the reserve
capacity at the time.
AUTO NORMAL Any number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen. Set Time when gallons
capacity falls below capacity...or the specified number of days
between regenerations is reached.
Any
number
NORMAL oFF
Reserve capacity not automatically estimated. Regeneration occurs at
the next Regen. or when gallons capacity reaches 0
oFF NORMAL Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen. Set Time when the specified
number of da regenerations is reached.
Any
number NORMAL Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen. Set Time when gallons
capacity reaches 0 number of days between regenerations is
reached
AUTO On O oFF
Reserve capacity automatically estimated.
Regeneration occurs immediately when gallons capacity reaches 0.
Time of regeneration is not allowed to be set because regeneration
will always occur when gallons capacity reaches 0.
Any
number On O oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when gallons capacity reaches 0.
Time of regeneration is not allowed to be set because regeneration
will always occur.
AUTO NORMAL on O oFF
Reserve capacity automatically estimated.
Regeneration occurs when gallons capacity falls below the
reserve capacity at the Time or regeneration occurs immediately
after 10 minutes of no water usage when reaches 0.
AUTO NORMAL on O Any number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons
capacity falls below capacity or the specified number of days
between regenerations is reached, or re immediately after 10 minutes
of no water usage when gallon capacity reaches 0.
Any
number NORMAL on O Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the
specified number of day regenerations is reached, or regeneration
occurs immediately after 10 minutes of when gallon capacity
reaches 0.

7
BYPASS VALVE
The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or
maintenance. The 1" full flow bypass valve incorporates four positions including a diagnostic position that allows a service technician to have pressure
to test a system while providing untreated bypass water to the building.
The bypass body and rotors are glass filled Noryl and the nuts and caps are glass filled polypropylene. All seals are self-lubricating EPDM
to help prevent valve seizing after long periods of non-use. Internal o-rings can easily be replaced if service is required.
The bypass consists of two interchangeable plug valves that are operated independently by red arrow shaped handles. The handles identify the
direction of flow. The plug valves enable the bypass valve to operate in four positions.
1. Normal Operation Position: The inlet and outlet handles point in the direction of flow indicated by the engraved arrows on the control
valve. Water flows through the control valve for normal operation of a water softener or filter. During the regeneration cycle this position
provides regeneration water to the unit, while also providing untreated water to the distribution system. (See Figure 1)
2. Bypass Position: The inlet and outlet handles point to the center of the bypass.
The system is isolated from the water pressure in the plumbing system.
Untreated water is supplied to the building. (See Figure 2)
3. Diagnostic Position: The inlet handle points toward the control valve and the outlet handle points to the center of bypass valve.
Untreated supply water is allowed to flow to the system and to the building, while not allowing water to exit from the system to the
building (See Figure 3).
This allows the service technician to draw brine and perform other tests without the test water going to the building.
NOTE: The system must be rinsed before returning the bypass valve to the normal position.
4. Shut Off Position: The inlet handle points to the center of the bypass valve and the outlet handle points away from the control valve.
The water is shut off to the building. The water treatment system will depressurize upon opening a tap in the building. A negative
pressure in the building combined with the softener being in regeneration could cause a siphoning of brine into the building. If water is
available on the outlet side of the softener or filter it is an indication of water bypassing the system (i.e. a plumbing cross-connection
somewhere in the building). (See Figure 4)
NORMAL OPERATION BYPASS OPERATION
“TREATED” WATER
EXITS
SUPPLY WATER
ENTERS
SUPPLY WATER
EXITS
SUPPLY WATER
ENTERS
Figure 1 Figure 2
DIAGNOSTIC MODE SHUT OFF MODE
SUPPLY WATER
EXITS
SUPPLY WATER
ENTERS
NO WATER
EXITS
SUPPLY WATER IS SHUT OFF
FROM THE HOUSE AND THE VALVE
Figure 3
Figure 4

8
INSTALLATION
GENERAL INSTALLATION & SERVICE WARNINGS
The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments but are not
designed to support the weight of a system or the plumbing.
Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicone lubricant may be used on
black o-rings, but is not necessary. Avoid any type of lubricants, including silicone, on red or clear lip seals.
Do not use pipe dope or other sealants on threads. Teflon tape must be used on the threads of the 1" NPT elbow, its
NPT connection, and on the threads for the drain line connection. Teflon tape is not used on the nut connections or caps
because o-ring seals are used. The nuts and caps are designed to be unscrewed or tightened by hand or with the special
plastic Service Wrench, #V3193. If necessary a pliers can be used to unscrew the nut or cap. Do not use a pipe wrench
to tighten nuts or caps.
Do not place screwdriver in slots on caps and/or tap with a hammer.
SITE REQUIREMENTS
• Water Pressure, 20-125 psi (138-862 kPa)
• Water temperature, 40° -110° F (4° - 38° C)
• The tanks should be on a firm level surface
• Electrical: Use a 115/120V, 60Hz uninterrupted outlet.
• Current draw is 0.5 amperes
• A 15 ft power cord is furnished.
• The plug-in transformer is for dry locations only.
• Batteries are not used.
1. The distance between the drain and the water conditioner should be as short as possible.
2. Since salt must be periodically added to the brine tank, it should be located where it is easily accessible.
3. Do not install any water conditioner with less than 10 feet (3m) of piping between its outlet and the inlet of a water
heater. Water heaters sometimes overheat to the extent that they will transmit heat or backflow from their inlet back to the
water conditioner control. Hot water can severely damage the conditioner. Allowing the 10 foot (3m) distance will permit
most heat to dissipate before reaching the water conditioner. A more positive way of insuring against backflow is to install
a high temperature check valve. The heater should also have a properly rated temperature and pressure relief valve.
Also, be certain that local codes are not violated.
4. Do not locate unit where it or its connections (including the drain and overflow lines) will ever be subjected to room
temperatures under 34° F (49° C).
5. The use of resin cleaners in an unvented enclosure is not recommended.
SERIAL NUMBER: Record the serial number on the installer’s and customer’s records.
Top View

9
INSTALLATION
INLET/OUTLET PLUMBING: Connect to a supply line downstream of outdoor spigots. Install an inlet shutoff valve and
plumb to the unit’s bypass valve inlet located at the right rear as you face the unit. There are a variety of installation fittings
available. They are listed under Installation Fitting Assemblies. When assembling the installation fitting package (inlet and
outlet), connect the fitting to the plumbing system first and then attach the nut, split ring and o-ring. Heat from soldering or
solvent cements may damage the nut, split ring or o-ring. Solder joints should be cool and solvent cements should be set
before installing the nut, split ring and o-ring. Avoid getting solder flux, primer, and solvent cement on any part of the o-
rings, split rings, bypass valve or control valve. If the building’s electrical system is grounded to the plumbing, install a
copper grounding strap from the inlet to the outlet pipe. Plumbing must be done in accordance with all applicable local
codes.
DRAIN LINE: First, be sure that the drain can handle the backwash rate of the system. Solder joints near the drain must be
done prior to connecting the drain line flow control fitting. Leave at least 6" between the drain line flow control fitting and
solder joints. Failure to do this could cause interior damage to the flow control. Install a˚" I.D. flexible plastic tube to the
Drain Line Assembly or discard the tubing nut and use the ∫" NPT fitting for rigid pipe. If the backwash rate is greater than 7
gpm, use a ∫" drain line. Where the drain line is elevated but empties into a drain below the level of the control valve, form a
7" (18 cm) loop at the discharge end of the line so that the bottom of the loop is level with the drain connection on the
control valve. This will provide an adequate anti-siphon trap. Where the drain empties into an overhead sewer line, a sink-
type trap must be used. Run drain tube to its discharge point in accordance with plumbing code. Pay special attention to
codes for air gaps and anti-siphon devices.
IMPORTANT:
Never insert a drain line directly into a drain, sewer line, or trap. Always allow an air gap between the drain
line and the wastewater to prevent the possibility of sewage being back-siphoned into the conditioner.
BRINE TANK CONNECTION: Install a 3/8" O.D. polyethylene tube from the Refill Elbow to the Brine Valve in the brine tank.
OVERFLOW LINE CONNECTION:
AN OVERFLOW DRAIN LINE IS RECOMMENDED WHERE A BRINE OVERFLOW COULD DAMAGE FURNISH- INGS
OR THE BUILDING STRUCTURE.
Your softener is equipped with a brine tank safety float which greatly reduces the chance of an accidental brine overflow. In
the event of a malfunction, however, an OVERFLOW LINE CONNECTION will direct the “overflow” to the drain instead of
spilling on the floor where it could cause considerable damage. This fitting should be on the side of the cabinet or the brine
tank.
To connect overflow fitting, locate hole in side of brine tank. Insert overflow fitting into tank and tighten with plastic thumb
nut and gasket from the inside. Attach a length of ˚" (1.3 cm) I.D. tubing (not supplied) to fitting and run to drain. Do not
elevate overflow line higher than 3" (7.6 cm) below bottom of overflow fitting. Do not “tie” this tube into the drain line of the
control valve. Overflow line must be a direct, separate line from overflow fitting to drain, sewer, or tub. Allow an air gap as
per the drain line instructions.
IMPORTANT:
Never insert a drain line directly into a drain, sewer line, or trap. Always allow an air gap between the drain
line and the wastewater to prevent the possibility of sewage being back-siphoned into the conditioner.

10
INSTALLER SETTINGS
NOTE: What follows assumes that AUTO is set for regeneration mode in Step 8S,
meaning gallons are automatically calculated.
STEP 1I - Press NEXT and simultaneously for 3 seconds.
STEP 2I – Hardness: Set the amount of hardness in grains per gallon (default 20) using
the or buttons. The allowable range is from 1 to 150 in 1 grain increments. Note:
Increase the grains per gallon if soluble iron is present. This display will show “–nA–” if
“FILTER” is selected or if “AUTO” is not selected previously. Press NEXT to go to step
3I. Press REGEN if you want to exit.
STEP 3I – Day Override: When gallon capacity is set to off, this sets the number of days
between regenerations. When gallon capacity is factory set to AUTO or to any number,
this sets the maximum number of days between regenerations. If this is set to “oFF”,
regeneration initiation is based solely on gallons used. If any number is set (allowable
range from 1 to 28), a regeneration initiation will be called for on that day even if
sufficient number of gallons were not used to call for regeneration. Set Day Override
using or buttons (14 recommended):
• set number of days between regeneration (1 to 28, default 14); or
• set to “oFF”.
Press NEXT to go to step 4I. Press REGEN if you need to return to previous step.
STEP 4I – Next Regeneration Time (hour): Set the hour of day for regeneration using
or buttons. AM/PM toggles after 12.
The default time is 2:00 a.m. (recommended).
This display will show “REGEN on 0 GAL” if immediate regeneration was factory set.
Press NEXT to go to step 5I. Press REGEN if you need to return to previous step.
STEP 5I – Next Regeneration Time (minutes): Set the minutes using or buttons.
This display will not be shown if “on 0” is selected in step 9S.
Press NEXT to exit Installer Settings. Press REGEN to return to previous step.
To initiate a manual regeneration immediately, press and hold the “REGEN” button for
three seconds. The system will begin to regenerate immediately. The control may be
manually stepped through the regeneration cycles by pressing “REGEN”.
P 2U
SET TIME OF DAY
TIME OF DAY
Time of day should only need to be set after extended power outages or when daylight saving
time begins or ends. If an extended power outage occurs, the time of day will flash on and off
indicating that the time should be reset.
STEP 1U – Press SET CLOCK.
STEP 2U - Current Time (hour): Set the hour of the day using or buttons. AM/PM toggles
after 12. Press NEXT to go to step 3U.
NEXT to exit Set Clock. Press REGEN to return to previous step.

12
GENERAL OPERATION
NORMAL OPERATING DISPLAYS
When the system is operating one of three displays will be shown.
Pressing NEXT will alternate between the displays. One of the
displays is the current time of day. Depending the system
configuration, the second display is one of the following: days
remaining or gallons remaining. Days remaining is the number of days
left before the system goes through a regeneration cycle. Capacity
remaining is the number of gallons that will be treated before the
system goes through a regeneration cycle. The third display is an
option and, if used, will show the number of pounds of salt remaining
in the brine tank. The user can scroll between the displays as desired
using NEXT.
If the system has called for a regeneration that will occur at the
preset time of regeneration, the words REGEN TODAY will appear on
the display.
When water is being treated (i.e. water is flowing through the
system) the word “Softening” or “Filtering” flashes on the display.
REGENERATION MODE
Typically a system is set to regenerate at a time of low water usage. If there is a demand
for water when the system is regenerating, untreated water will be delivered.
When the system begins to regenerate, the display will change to include information
about the step of the regeneration process and the time remaining for that step to be
completed. The system runs through the steps automatically and will reset itself to provide
treated water when the regeneration has been completed.
MANUAL REGENERATION
Sometimes there is a need to regenerate before the control valve calls for it, usually
referred to as manual regeneration. This is needed when a period of heavy water usage is
anticipated or when the system has been operated without salt.
•To initiate a manual regeneration at the preset delayed regeneration
time, press and release “REGEN”. The words “REGEN TODAY” will
flash on the display to indicate that the system will regenerate at the
preset delayed regeneration time.
•If you pressed the “REGEN” button in error, pressing the button again,
will cancel the command. Note: If the regeneration time is factory set
to “on 0” there is no set delayed regeneration time so “REGEN
TODAY” will not activate if “REGEN” button is pressed.
•To initiate a manual regeneration immediately, press and hold the
“REGEN” button for three seconds. The system will begin to
regenerate immediately. The command cannot be cancelled.
POWER LOSS
POWER LOSS & ERROR DISPLAY
If the power goes out for less than two hours, the system will automatically reset
itself. If an extended power outage occurs, the time of day will flash on and off
which indicates the time of day should be reset.
The system will remember the rest.
ERROR MESSAGE
If the word “ERROR” and a number are alternately flashing on the display record
the number and contact the dealer or manufacturer for help. This indicates that
the control valve was not able to function properly.

13
LOW SALT WARNING (optional)
Salt Remaining or Adding Salt
If the Low Salt Warning option was factory installed the
following screens will be viewed in the User Display.
Note: The salt used per regeneration setting was set in
increments of 0.1 pounds, but the LBS REMAINING
screen will round up or down to the closest whole
number.
Once the salt remaining has gone below the set point, the display will automatically flash “Salt Fill”.
RESETTING THE SALT AMOUNT AFTER ADDING
When adding salt to the brine tank (if the salt remaining option is used) the following steps must be completed:
Step 1US – Press the NEXT button until SALT appears in the display.
It does not matter if the SALT display alternates with the LBS REMAINING display.
Step 2US – Press SET CLOCK.
Step 3US – Set LBS REMAINING: Use the or button to adjust the pounds remaining
in the brine tank.
NOTE: Estimate the pounds of salt in the brine tank and add it to the amount of salt added
to the brine tank. The example at the left would indicate 200 lbs. of salt being added to a
brine tank that has 40 lbs. remaining.
Step 4US – Press SET CLOCK to exit Adding Salt. The control is now in one of its three
normal operating displays. Press NEXT to view GAL CAPACITY REMAINING or TIME OF
DAY.

14
START UP INSTRUCTIONS
•After installation is completed rotate the bypass handles to the bypass position (see bypass valve
diagram page).
•Turn on water and check for leaks.
•Fully open a cold water faucet.
•Allow water to run until clear to rid pipes of debris which may have occurred during installation.
•The system is now ready for filling with water and for testing.
1. With the bypass valve in the bypass position, manually pour enough water into the brine tank to reach the top of the air
check valve.
2. Press and hold the REGEN button until the motor starts. Release button. Wait until the display reads “BACK- WASH”
and the remaining time is counting down. Unplug transformer to prevent valve from moving to the next cycle.
3. Open the inlet handle of the bypass valve very slightly allowing water to fill the tank slowly in order to expel air.
CAUTION: If water flows too rapidly there will be a loss of media.
4. When the water is flowing steadily to the drain without the presence of air, restore power and momentarily press the
REGEN button to advance the control to the “BRINE” position.
5. Fully open the inlet bypass valve handle (bypass is now in the diagnostic position).
Check to verify that water is being drawn from brine tank. There should be a slow flow to the drain.
Allow two minutes for the media bed to settle.
6. Momentarily press REGEN again until the display reads “2 BACKWASH” and the “time remaining” numbers are
counting down. The “2” flashes.
7. Momentarily press REGEN again until the display reads “RINSE”. Unplug transformer. There should be a rapid flow to
the drain. Allow to run until steady, clear, and without air.
Restore power.
8. Set bypass valve handles to the normal operating position
9. Momentarily press REGEN again until the display reads “FILL”.
Allow the brine tank to fill automatically.
It will fill with the proper volume of water for the first regeneration after the unit will automatically return to the service
position. If not filling automatically, press REGEN to advance the valve to service.
10. While the brine tank is filling, load it with water softener salt.

15
Front Cover and Drive Assembly
Item No.
Part No.
Description
Qty.
1
V3175CC-01
Front cover assy., CC
1
2
V3107-1
Motor
1
3
V3106-01
Drive bracket & spring clip
1
4
V3108CC
PC board, CC
1
5
V3110
Drive gear, 12x36
3
6
V3109
Drive gear cover
1
2-6
V3002CC
Drive assy., CC
-
not shown
V3186
Transformer, 110V-12V
1
5
3
Piston Assembly
Item No.
Part No.
Description
Qty.
1
V3005
Spacer stack assy.
1
2
V3004
Drive cap assy.
1
3
V3135
O-ring 228
1
4a
V3011
Piston assy, downflow
1
4b
V3011-01
Piston assy., upflow
1
5
V3174
Regenerant piston
1
6
V3180
O-ring 337
1
*Item 5 is NOT used with backwash-only filters
REPLACEMENT PARTS

Injector assembly with Cap, Plug, Screen and O-Ring
Item No.
Part No.
Description
Qty.
1
V3176
Injector cap
1
2
V3152
O-ring 135
1
3
V3177
Injector screen
1
4
V3010-1Z
Injector assy. plug
1
5
V3010-1A
A injector assy., BLACK
1
V3010-1B
B injector assy., BROWN
V3010-1C
C injector assy., VIOLET
V3010-1D
D injector assy., RED
V3010-1E
E injector assy., WHITE
V3010-1F
F injector assy., BLUE
V3010-1G
G injector assy., YELLOW
V3010-1H
H injector assy., GREEN
V3010-1I
I injector assy., ORANGE
V3010-1J
J injector assy., DARK BLUE
V3010-1K
K injector assy., DARK GREEN
not shown
V3170
O-ring 011 (lower)
*
not shown
V3171
O-ring 013 (upper)
*
* The injector plug and the injector each use one lower and one upper o-
ring
Note: For a backwash-only filter, item 3 is used in both holes.
REPLACEMENT PARTS
Refill Port Assembly
Item
No.
Part No. Description Qty.
1 V319501 Refill port plug assy.
Req’d for
backwash-
only filters
2
H4615
Elbow locking clip
1
3+4+5 V414401
Brine Refill Elbow
Assembly 3/8
1
4
JCPG6BLK
Nut, 3/8
1
5
H4613
Elbow cap, 3/8
1
6
V3163
O-ring 019
1
7 V316501*
Refill flow control
retainer assy.
1
8 V3182
Refill flow control
(specify size)
1
Not
show
n
H4650 Elbow ½” w/ nut and
insert Optional
*Assembly includes refill flow control (specify size)

17
REPLACEMENT
PARTS
Drain Line Assembly, ¾”
Item No.
Part No.
Description
Qty.
1
H4615
Locking clip, elbow
1
2
PHP10TS8BULK
Inset, 5/8” tube
Optional
3
V3192
Nut, ¾” drain elbow
Optional
4
V315801
Drain elbow assy., ¾” NPT
1
5
V3163
O-ring 019
1
6
V315901
DLFC Retainer assy.
1
7
V3162007
0.7 DLFC for ¾” elbow
One
DLFC
must be
used if
¾” fitting
is used.
V3162010
1.0 DLFC for ¾” elbow
V3162013
1.3 DLFC for ¾” elbow
V3162017
1.7 DLFC for ¾” elbow
V3162022
2.2 DLFC for ¾” elbow
V3162027
2.7 DLFC for ¾” elbow
V3162032
3.2 DLFC for ¾” elbow
V3162042
4.2 DLFC for ¾” elbow
V3162053
5.3 DLFC for ¾” elbow
Items 2 and 3, nut and insert, are only used with 5/8” I.D. by ½” O.D.
polytubing. For other piping materials the ¾” NPT is used.

Drain Line Assembly, 1"
Item No.
Part No.
Description
Qty.
1
H4615
Locking clip, elbow
1
2
V3008-02
Drain fitting, 1" straight
1
3*
V3166
Drain fitting body, 1"
1
4*
V3167
Drain fitting adapter, 1"
1
5*
V3163
O-ring 019
1
6*
V3150
Split ring
1
7*
V3151
Nut, 1" QC
1
8*
V3105
O-ring 215
1
9
V3190-065
6.5 gpm DLFC for 1" fitting
One DLFC
must be
used if
1" fitting
is used.
V3190-075
7.5 gpm DLFC for 1" fitting
V3190-090
9.0 gpm DLFC for 1" fitting
V3190-110
11.0 gpm DLFC for 1" fitting
V3190-130
13.0 gpm DLFC for 1" fitting
V3190-170
17.0 gpm DLFC for 1" fitting
V3190-200
20.0 gpm DLFC for 1" fitting
V3190-250
25.0 gpm DLFC for 1" fitting
*Items 3-8 can be ordered as No. V3008-02, Drain fitting assy., 1" straight.
REPLACEMENT
PARTS

Bypass Valve
Item No.
Part No.
Description
Qty.
1
V3151
Nut, 1" Quick Connect
2
2
V3150
Split ring
2
3
V3105
O-ring 215
2
4
V3145
Bypass rotor, 1"
2
5
V3146
Bypass cap
2
6
V3147
Bypass handle
2
7
V3148
Bypass rotor seal retainer
2
8
V3152
O-ring 135
2
9
V3155
O-ring 112
2
10
V3156
O-ring 214
2
90∞ Vertical elbow adapter assy. for bypass valve
( not shown )
Part No. V319101
Part No.
Description
Qty.
V3151
Nut, 1" quick connect
2
V3150
Split ring
2
V3105
O-ring 215
2
REPLACEMENT PARTS
.
Water and Meter Plug
Item No.
Part No.
Description
Qty.
1
V3151
Nut, 1" QC
1
2
V3003
Meter assy., includes Items 3 and 4
1
3
V311801
Turbine assy.
1
4
V3105
O-ring 215
1
5
V300301
Meter plug assy.
1
This manual suits for next models
2
Table of contents
Other Waterite Water Dispenser manuals
Popular Water Dispenser manuals by other brands

Emerson
Emerson in sink erator HC1100 Quick installation guide

ITV ICE MAKERS
ITV ICE MAKERS RAIN 120 Installation, use and maintenance handbook

Pentair
Pentair PCFE40P12 owner's manual

SENTRY II
SENTRY II 962SM Series Operation and maintenance manual

InSinkErator
InSinkErator F-HC3300C installation manual

Olympia Water Systems
Olympia Water Systems OROS-50 Installation instructions & owner's manual