Weidmuller UR20-4DI-4DO-PN-FSOE User manual

Remote I/O system u-remote
IP20 modules for functional safety
Manual (Original)
Letʼs connect.

1 About this documentation 3
1.1 Symbols and notes 3
1.2 Complete documentation 3
2 Safety 5
2.1 General safety notice 5
2.2 Intended use 6
2.3 Use in a potentially explosive atmosphere 6
2.4 Notes on functional safety 6
2.5 Legal notice 7
3 System description of safe I/O modules 9
3.1 Sample design 9
3.2 Transition diagramm 10
3.3 Current-/voltage characteristics of the fail safe digital inputs 10
3.4 Registration of safe I/O modules on the safety control 11
3.5 Safety address 11
3.6 Operation with and without test pulses 12
3.7 Processing time 12
4 System description of safe power-feed modules 15
4.1 Sample design 16
4.2 Transition diagramm 17
4.3 Modules switchable by PF-O-xDI-SIL 18
4.4 Conguration 18
4.5 Switch-off delay time 18
4.6 Operation with and without test pulses 19
5 Detailed descriptions of safe modules 21
5.1 General technical data 21
5.2 Data width dependent on the coupler used 22
5.3 Digital in- and output module UR20-4DI-4DO-PN-FSOE,
UR20-4DI-4DO-PN-FSOE-V2 24
5.4 Digital input module UR20-8DI-PN-FSOE, UR20-8DI-PN-FSOE-V2 32
5.5 Digital in- and output module UR20-4DI-4DO-PN-FSPS,
UR20-4DI-4DO-PN-FSPS-V2 39
5.6 Digital input module UR20-8DI-PN-FSPS, UR20-8DI-PN-FSPS-V2 47
5.7 Safe power-feed module UR20-PF-O-1DI-SIL 54
5.8 Safe power-feed module UR20-PF-O-2DI-SIL 59
5.9 Safe power-feed module UR20-PF-O-2DI-DELAY-SIL 64
6 Installation and replacement 71
7 Example applications 73
7.1 Example applications for safe I/O modules 73
7.2 Dual-channel emergency stop monitoring 76
7.3 Dual-channel light curtain monitoring (AOPD type 4)
and emergency stop monitoring 77
7.4 Dual-channel emergency stop and cable-pull switch monitoring 78
7.5 Dual-channel safety door monitoring with automatic reset
and emergency stop 79
7.6 Safety mat 80
7.7 Dual-channel two-hand monitoring with automatic start 81
7.8 Dual-channel safety door monitoring with magnetic switch,
automatic reset and emergency stop 82
7.9 Dual-channel safety door monitoring, spring-operated interlock
with manual reset and emergencystop 83
7.10 Dual-channel safety door monitoring, magnetically operated interlock
with manual reset and emergency stop 84
7.11 Dual-channel safety door monitoring with proximity sensors,
automatic reset and emergency stop 85
7.12 Dual-channel safety door monitoring, spring-operated interlock,
controlled shutdown with manual reset and emergency stop 86
7.13 Dual-channel safety door monitoring with automatic reset
and controlled shutdown and emergency stop 87
7.14 Cascading 88
8 LED displays and troubleshooting 89
8.1 Safe I/O modules 89
8.2 Safe power-feed modules 91
9 Accessories and replacement parts 93
9.1 Accessories 93
9.2 Replacement parts 93
Attachment
Checklist for the use of u-remote safety modules A-2
EC Declaration of Conformity A-5
TÜV Certicates A-27
Content
21484600000/04/06.2017u-remote IP20 modules for functional safety manual
Manufacturer
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
32758 Detmold, Germany
T +49 5231 14-0
F +49 5231 14-292083
info@weidmueller.com
www.weidmueller.com
Document No. 1484600000
Revision 04/June 2017

1 About this documentation | Symbols and notes
3u-remote IP20 modules for functional safety manual1484600000/04/06.2017
1 About this documentation
1.1 Symbols and notes
The safety notices in this documentation are designed
according to the severity of the danger.
DANGER
Imminent risk to life!
Notes with the signal word “Danger” warn
you of situations which will result in serious
injury or death if you do not follow the in-
structions given in this manual.
WARNING
Possible danger to life!
Notes with the signal word “Warning” warn
you of situations which may result in serious
injury or death if you do not follow the in-
structions given in this manual.
CAUTION
Risk of injury!
Notes with the signal word “Caution” warn
you of situations which may result in injury
if you do not follow the instructions given in
this manual.
ATTENTION
Material damage!
Notes with the signal word “Attention” warn you of hazards
which may result in material damage.
Text next to this arrow are notes which are
not relevant to safety, but provide important
information about proper and effective work
procedures.
The situation-dependent safety notices may contain the fol-
lowing warning symbols:
Symbol Meaning
Warning against hazardous electrical
voltage
Warning against explosive atmospheres
Warning against electrostatically charged
components
Warning against automatic startup
Instruction: observe the documentation
▶All instructions can be identified by the black triangle
next to the text.
–Lists are marked with a tick.
1.2 Complete documentation
This manual contains product-specic
information and notes about the use of
u-remote safe modules. It supplements
but doesnot replace the u-remote manual
(document no 1432790000).
All manuals are available to download on the
Weidmüller website.

1 About this documentation | Complete documentation
41484600000/04/06.2017u-remote IP20 modules for functional safety manual

2 Safety | General safety notice
5u-remote IP20 modules for functional safety manual1484600000/04/06.2017
This section includes general safety instructions for handling
the u-remote system. Specic safety instructions for specic
tasks and situations are given at the appropriate places in
the documentation.
2.1 General safety notice
Work on the u-remote products may only be performed by
qualied electricians with the support of trained persons.
As a result of their professional training and experience, an
electrician is qualied to perform the necessary work and
identify any potential risks.
Before any work is carried out on the products (installa-
tion, maintenance, retrotting), the power supply must be
switched off and secured against being switched on again.
Work may be carried out with safety extra-low voltage.
When working during continued operations, the safety
equipments and devices must not be made ineffective.
If a malfunction on a u-remote product cannot be xed after
following the recommended measures (see the chapter8),
the product in question must be sent back to Weidmüller.
Weidmüller assumes no liability If the base or electronic
module has been tampered with!
Electrostatic discharge
u-remote products can be damaged or destroyed by electro-
static discharge. When handling the products, the neces-
sary safety measures against electrostatic discharge (ESD)
according to IEC 61340-5-1 and IEC 61340-5-2 must be
observed.
All devices are supplied in ESD-protected packaging. The
packing and unpacking as well as the installation and disas-
sembly of a device may only be carried out by qualied per-
sonnel and in accordance with the ESD information.
Open equipment
u-remote products are open equipment that may only be in-
stalled and operated in lockable housings, cabinets or electri-
cal operations rooms. Only trained and authorised personnel
may access the equipment.
For applications requiring functional safety, the surrounding
housing must meet at least IP54.
The standards and guidelines applicable for the assembly
of switch cabinets and the arrangement of data and supply
lines must be complied with.
Fusing
If safe I/O modules or safe power-feed modules are installed
within a u-remote station, a SELV/PELV power supply has to
be applied to ensure the safety functions.
The operator must set up the equipment so that it is protect-
ed against overloading. The upstream fuse must be designed
such that it does not exceed the maximum load current. The
maximum permissible load current of the u-remote compo-
nents can be found in the technical data.
To meet UL-specications in accordance with UL248-14,
a UL-certied automatic fuse (e.g. ABB Type S201-B16)
or a 8A fuse with a medium time-lag (e.g. ESKA Part No.
522.226) must be used.
All connections of the u-remote components are protected
against voltage pulses and overcurrent in accordance with
IEC61131-2, ZoneB. The operator has to decide whether
additional overvoltage protection according to IEC62305
is required. Voltages that exceed +/-30V may cause the de-
struction of couplers and modules.
A feed-in power supply with secure isolation must be used.
Earthing (functional earth FE)
Each u-remote I/O module is tted with an FE spring on the
underside which creates an electrical connection to the DIN
rail. In order to establish a secure connection, the assembly
must be carried out carefully in accordance with the instruc-
tions (see chapter 7 of the u-remote manual). The module is
earthed by connecting the DIN rail to the protective earth via
the earth terminal.
Shielding
Shielded lines are to be connected with shielded plugs and
xed on a shield bus in compliance with the relevant stan-
dard (see u-remote manual, chapter8).
2 Safety

2 Safety | Intended use
61484600000/04/06.2017u-remote IP20 modules for functional safety manual
2.2 Intended use
The products of the u-remote series are intended for use in
industrial automation. A u-remote station with bus coupler
and connected modules is intended for the decentralised
control of systems or sub-systems. All modules of a station
are integrated into a eldbus structure and connected to the
superordinate control unit via the eldbus coupler.
The u-remote safe I/O modules (UR20-*FS*) as well as the
safe power-feed modules (PF-O-xDI-SIL) are intended for
connecting equipment providing functional safety. Therefore
safe I/O modules must be operated via a safety control.
The u-remote products conform to protection class IP20 (in
accordance with DIN EN 60529), they can be used in poten-
tially explosive atmospheres rated as Zone 2 (as per Directive
2014/34/EU).
The observance of the supplied documentation is part of the
intended use. The products described in this manual may
only be used for the intended applications and only in con-
nection with certied third-party devices or components.
2.3 Use in a potentially explosive atmosphere
If u-remote products are used in potentially explosive atmos-
pheres, the following notes are also applicable:
–Staff involved in assembly, installation and operation must
be qualified to perform safe work on electrical systems
protected against potentially explosive atmospheres.
–For applications in potentially explosive atmospheres, the
requirements according to IEC60079-15 must be
observed.
–The housing enclosing must be ATEX/IECEx certified
meeting the requirements of protection class IP54, acces-
sible only by use of a tool.
–The housing enclosing must meet the requirements of
explosion protection type Exn or Exe.
–Sensors and actuators that are located in Zone 2 or in a
safe zone can be connected to the u-remote station.
–Devices are for use in an area of not more than pollution
degree 2 in accordance with EN60664-1.
–Provision shall be made to prevent the rated voltage from
being exceeded by transient disturbances of more than
140 % of the rated voltage.
–When the temperature under rated conditions exceeds
70 °C at the conductor or conduit entry point, or 80 °C at
the contact, the temperature specification of the selected
cable shall be in compliance with the actual measured
temperature values.
–A visual inspection of the u-remote station is to be per-
formed once per year.
2.4 Notes on functional safety
Safety Integrity Level (SIL)
The safety requirements necessary for the safety functions
of an application are determined in a risk analysis. Here, the
probability of the safety functions failing is important. In an
operating mode with a high rate of demand or continuous
demand, the probability of dangerous failure per hour (PFH)
must be taken into consideration, whereas in an operating
mode with a lower rate of demand, the probability of danger-
ous failure on demand (PFD) must be taken into consider-
ation. According to IEC61508 and IEC62061, the safety
requirements are graded by the failure limit values as follows:
Safety requirements by failure limit values
PFD PFH
SIL3 < 10-3 < 10-7
SIL2 ≥ 10-3 to < 10-2 ≥ 10-7 to < 10-6
SIL1 ≥ 10-2 to < 10-1 ≥ 10-6 to < 10-5
Performance level (PL)
According to ENISO13849-1, the degree to which a safety
function contributes to risk minimisation is dened as the
performance level. A distinction is made between the ve
levels PLa to PLe with an increasing contribution to risk min-
imisation.
Safety categories
Safety categories according to ENISO13849-1 describe a
minimum level of applicable safety and to what extent moni-
toring is required.
Category B: The safety-related components of machine
controls and/or their safety equipment as well as their
components must be designed, selected, assembled and
combined to the state of the art such they can withstand the
expected conditions.
Category 1: The requirements of Category B must be met.
Use of proven safety-related components.
Category 2: The requirements of Category B must be met
with the use of proven safety principles. The safety functions
must be veried by the machine controls at suitable intervals
(depending on the application and the type of machine).
Category 3: The requirements of Category B must be met
with the use of proven safety principles. Controls must be de-
signed so that a single failure in the control system does not
lead to a loss of safety function(s), and whenever reasonably
practicable, the single failure shall be detected with suitable
means which meet the state of the art.
Category 4: The requirements of Category B must be met
along with the use of proven safety principles. Controls must

2 Safety | Legal notice
7u-remote IP20 modules for functional safety manual1484600000/04/06.2017
be designed so that a single failure in the control system
does not lead to a loss of safety function(s), and whenever
reasonably practicable, a single failure is detected during or
prior to the next demand upon the safety function, or if this
is not possible, an accumulation of faults does not lead to
the loss of the safety function(s).
Requirements on sensors / signal generators
The sensors / signal generators being connected must meet
the following requirements:
–Only signal generators that are suited for the respective
required safety level may be used.
–Positively opening control switches must be used in
accordance with IEC60947-5-1 (designated with this
symbol: ).
–Only use components that have been proven in operation.
–Depending on the established risk level, switches (e.g. for
position monitoring) may have to have a redundant
design.
–Depending on the required safety level, control devices
may have to have a redundant design. In this regard,
make sure to take into account the applicable C stan-
dards.
2.5 Legal notice
The u-remote series products are CE-compliant in accor-
dance with Directive 2014/30/EU (EMC Directive) and
Directive 2014/35/EU (Low Voltage Directive). They also
meet the requirements of the ATEX Directive 2014/34/EU.

81484600000/04/06.2017u-remote IP20 modules for functional safety manual

3 System description of safe I/O modules | Sample design
9u-remote IP20 modules for functional safety manual1484600000/04/06.2017
This chapter contains product-specic informa-
tion and notes about the use of safe I/O mod-
ules. Please also observe the system description
in the u-remote manual (document number
1432790000).
The u-remote system provides safe I/O modules for both
safety protocols Safety over EtherCAT1) (Fail safe over
EtherCAT, FSOE) and PROFIsafe. Attached to a safety control
they enable the selective switching off of plant devices.
The 4DI-4DO type as well as the 8DI type is available for
each safety protocol. Each type is also available as type2
variant (V2):
UR20-4DI-4DO-PN-FSOE, UR20-4DI-4DO-PN-FSOE-V2
UR20-8DI-PN-FSOE, UR20-8DI-PN-FSOE-V2
UR20-4DI-4DO-PN-FSPS, UR20-4DI-4DO-PN-FSPS-V2
UR20-8DI-PN-FSPS, UR20-8DI-PN-FSPS-V2
Both variants are identical in design, they only differ in the
rmware and therefore in the parameters (see module de-
scriptions in Chapter5). The V2 modules enable to connect
antivalent switching safety devices.
The V1 modules cannot be upgraded using the
V2 rmware!
Single channel architectures (1oo1) as well as dual channel
architectures (1oo2) can be realised with the safe inputs and
outputs, also mixed operation is possible. In case of failure of
the safety control the modules change into the safe status.
X1
X2
DI
M
DI DO DIDODODO DO FS*
FS*AO DO
Safety control
Example set-up of safe I/O modules (FS*) in a u-remote station
1) Safety over EtherCAT®is a registered trademark and patented technology, licensed by
Beckhoff Automation GmbH, Germany
Safety function
The information on the inputs are transferred to the safety
control via a black channel according to EN61508-2). A safe
input will send the input information “false” to the safety con-
trol if a signal is within the inactive range or a fault has been
detected.
Vice versa the information from the safety control are trans-
ferred to the outputs. The safe outputs will be deactivated if
the output information “false” is sent from the safety control
or a fault has been detected (safe status see technical data).
3.1 Sample design
Safe I/O modules can be placed at any position in the
u-remote station. The only exceptions are safety segments
built up from safe power feed modules (s. section 4.1). No
safe I/O module with outputs (UR20-4DI-4DO-PN-FSOE or
UR20-4DI-4DO-PN-FSPS) may be placed within a safety
segment.
The following picture exemplies how to design a u-remote
station with safe I/O modules.
3 System description of safe I/O modules

3 System description of safe I/O modules | Transition diagramm
10 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
3.2 Transition diagramm
State 2
Running
Failure resolved
Failure occured
Acknowledgement
by safety control
Parameter received from safety control
Unrecoverable fault
State 1
Waiting for parameter
State 4
Requesting
acknowledgement
by safety control
State 3
Fault
Transition diagramm for safe I/O modules
3.3 Current-/voltage characteristics of the fail
safe digital inputs
0
0 2 20104 6 8 12 14 16 18
3
2
1
4
[V]
[mA]
Inputs "off" Inputs "on"
Current-/voltage characteristic for P-switching inputs
0
0 2 20104 6 8 12 14 16 18
3
2
1
4
[V]
[mA]
Inputs "off" Inputs "on"
Current-/voltage characteristic for PN-switching inputs

3 System description of safe I/O modules | Registration of safe I/O modules on the safety control
11u-remote IP20 modules for functional safety manual1484600000/04/06.2017
3.4 Registration of safe I/O modules on the
safety control
Safe I/O modules need to get registered on a safety control
using an engineering tool. Via the web server the safe I/O
modules can only be observed but not be parameterised or
forced.
PROFIsafe
For the commissioning of safe I/O modules running with the
PROFIsafe safety protocol you will need the Weidmüller CPD
tool which is available to download on the website. Accord-
ing to the parameter settings this software tool calculates a
check sum, wich will be transferred to the safety control in
Siemens STEP7 and on the TIA portal.
Fail-Safe-over-EtherCAT
For the commissioning of safe I/O modules running with
the Fail safe over EtherCAT safety protocol you will need
TwinCAT as well as a TwinSAFE safety control. The FSOE
modules have been tested using the TwinSAFE-Logic
EL6900 system (Beckhoff) and TwinCAT 2.11.2247
(Beckhoff).
3.5 Safety address
Before commissioning the safety address (F-address) has to
be set on each safe I/O module using the DIP switches on
the electronic unit. This address is indicated by the project
planning. The safety control transfers the safety address to
the module on each commissioning.
The safety address (decimal) has to be converted into a bi-
nary value and then set using the DIP switches .
Decimal/binary conversion table
decimal 2048 1024 512 256 128 64 32 16 8 4 2 1
binary
0 0 0 0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0 0 1 0
0 0 0 0 0 0 0 0 0 1 0 0
0 0 0 0 0 0 0 0 1 0 0 0
0 0 0 0 0 0 0 1 0 0 0 0
0 0 0 0 0 0 1 0 0 0 0 0
0 0 0 0 0 1 0 0 0 0 0 0
0 0 0 0 1 0 0 0 0 0 0 0
0 0 0 1 0 0 0 0 0 0 0 0
0 0 1 0 0 0 0 0 0 0 0 0
0 1 0 0 0 0 0 0 0 0 0 0
1 0 0 0 0 0 0 0 0 0 0 0
1234 0 1 0 0 1 1 0 1 0 0 1 0
Example: Address „1234“ is represented by setting
0000010011010010.
Please use e.g. a ball pen to set the DIP switches
and avoid sharp-edged tools.
With PROFIsafe modules: Make sure that switch-
es without identication marking always remain
in position “Zero”.
Setting the safety address
▶Before snapping the module onto the DIN rail please set
the safety address according to the project planning via
the DIP switches on the electronic unit.
▶Snap the module onto the DIN rail and continue the
installation of the u-remote station.
1 0
3
2
1
0
7
6
5
4
11
10
9
8
0000010011010010
1 0
3
2
1
0
7
6
5
4
11
10
9
8
DIP switches for setting the safety address on a PROFIsafe module (example setting: 1234)
Changing the safety address
To change the safety address after the module has been as-
signed to the control please act as follows (with V2 modules
start with step5):
1. Pull out the electronic unit.
2. Set all DIP switches to position „Zero“.
3. Slide the electronic unit back into the module and turn on
the module/station.
4. Please wait until the status LED of the module lights alter-
nating red and green (3 s green, 1 s red).
Only now the old safety address has been deleted and the
new one can be set.
5. Pull out the electronic unit again and set the new safety
address.
6. Slide the electronic unit back into the module and turn on
the module/station.
The status LED of the module lights green and the new safe-
ty address will be displayed on the web server.

3 System description of safe I/O modules | External circuitry of a PN/P output pair
12 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
3.6 External circuitry of a PN/P output pair
All information in this section refer to the ZVEI position paper
CB24I (Edition 2.0).
The outputs of the module can be circuited as follows.
Options for the external circuitry of the outputs
Circuit diagram Parameterisation
1
2 x single-channel, P-switching
or
dual-channel, P-switching
2 2 x single-channel, rst channel N-switching
3 dual-channel, rst channel N-switching
Examples 1 and 2
2 x single-channel, P-switching or dual-channel, P-switching
The outputs in circuit diagram1 correspond to the typeC
source.
1
2
3
4
1
2
3
4
1
2
3
4
DO (PN)
DO (P)
DO (PN) 24 V DC
DO (P)
DO (PN)
DO (P)
1
2
3
External circuitry of the outputs
Test pulse class Parameterisable per test pulse duration
Test pulse duration Depending on the parameterisation 0.5 ... 10ms
Test pulse intervall 200ms
Rated current 0.5A (as per EN61131-2)
Capacitive load
Depending on the parameterisation and the load
current. With test pulses enabled the output current
must be reduced to <10V within one millisecond.
With test pulses disabled (only possible with V2
modules) the connected capacity must not exceed
250µF.
Inductive load As per EN61131-2 for 0.5Aoutputs, maximum
leakage current in state OFF: 100µA
Lamp load When using a lamp load the test pulses must be
enabled (V2 modules only).
Example 3
Dual-channel, rst channel N-switching
The outputs correspond with the typeD source.
1
2
3
4
1
2
3
4
1
2
3
4
DO (PN)
DO (P)
DO (PN) 24 V DC
DO (P)
DO (PN)
DO (P)
1
2
3
External dual-channel circuitry of the outputs
Test pulse class Parameterisable per test pulse duration
Test pulse duration Depending on the parameterisation 0.5 ... 10ms
Test pulse intervall 200ms
Rated current 0.5A (as per EN61131-2)
Capacitive load
Depending on the parameterisation and the load
current. With test pulses enabled the output current
must be reduced to <10V within one millisecond.
With test pulses disabled (only possible with V2
modules) the connected capacity must not exceed
250µF.
Inductive load As per EN61131-2 for 0.5Aoutputs, maximum
leakage current in state OFF: 100µA
Lamp load When using a lamp load the test pulses must be
enabled (V2 modules only).
3.7 Operating with and without own test
pulses
All information in this section refer to the ZVEI position paper
CB24I (Edition 2.0).
The parameter settings allow to enable test pulses for the
inputs of the safe I/O modules. These test pulses are gener-
ated and analysed by the module. Thus the highest safety
levels can be achieved (see technical data). The test pulse
duration is determined by the input delay.
When operating without test pulses AUX-OX and AUX-OY
can be used as outputs for the supply voltage. The active
output signal includes test pulses, the length of which is pa-
rameterisable between 0.5ms and 10ms. With V2 modules
these test pulses can be disabled.
Please regard the notes for parameter settings
whenever you disable the test pulses (see module
descriptions in chapter5).

3 System description of safe I/O modules | Operating with and without own test pulses
13u-remote IP20 modules for functional safety manual1484600000/04/06.2017
Examples for operating with test pulses
1
2
3
4
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
Connecting example typeA sink
Input current 2.5mA typ. (acc. to Type3 as per EN61131-2)
Output voltage:
AUX-OX, P-switching 22V typ. (Supply voltage minus 2V)
AUX-OX, N-switching 0V
AUX-OY Supply voltage 24V typ.
Input capacity 10nF typ.
1
2
3
4
+24 V DC
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
Safety relay
Connecting example typeB sink
Test pulse delay Depending on the parameterisation
Test pulse duration 0.5 to 10ms; depending on the parameterised input
delay
Test pulse intervall 1200ms
Input capacity 10nF typ.
Antivalent circuits are possible with V2 modules only.
1
2
3
4
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
Connecting example with antivalent input circuit (V2 only)
For the operation with test pulses the V2modules can be
installed either with three or with four wires:
1
2
3
4
DI X
AUX-O X
AUX-O Y
DI Y
Operation with own test pulses, 4-wire installation
1
2
3
4
DI X
AUX-O X
AUX-O Y
DI Y
Operation with own test pulses, 3-wire installation
Examples for operating without test pulses
The following parameter settings are needed if an external
device is connected that generates test pulses by its own:
V1modules: test pulse “disabled“
V2modules: test pulse “external”.
1
2
3
4
+24 V DC
GND
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
OSSD
Safety
device
Connecting example for operation without own test pulses, typeCsink, class1
Test pulse duration Max. 1ms
Test pulse intervall Min. 0
Input resistance Min. 7.2kOhm (at 18V)
Input capacity Max. 10nF typ.
Input inductivity Max. 1mH

3 System description of safe I/O modules | Processing time
14 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
1
2
3
4
1
2
3
4
1
2
3
4
+24 V DC
GND
DI X
AUX-O X
AUX-O Y
DI Y
+24 V DC
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
+24 V DC
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
GND module
Example for the operation without own test pulses
In the event that the module shall be used as
typeA source with disabled test pulses the DIX
input must be parameterised N-switching.
1
2
3
4
DI X (N)
AUX-O X
AUX-O Y
DI Y (P)
Operation without own test pulses, typeA source with N-switching DIX
3.8 Processing time
The response time for each input or output of a safe I/O
module is <10ms. The processing time of a signal within the
safety chain can be calculated as follows:
Input delay (parameterised)
+ Response time input (<10 ms)
+ Response time output (<10 ms)
+ Data transfer from and to the PLC
+ PLC computing time
= Processing time

4 System description of safe power-feed modules
15u-remote IP20 modules for functional safety manual1484600000/04/06.2017
This chapter contains product-specic informa-
tion and notes about the use of safe power-feed
modules. Please also observe the system descrip-
tion in the u-remote manual document umber
1432790000)
The PF-O-xDI-SIL modules are controlled using con-
tact-based safety transducers and/or safety transducers with
OSSD outputs.
Each PF-O-xDI-SIL module safely switches off all fol-
lowing modules that are supplied by the output current path
and thus creates a safety segment. A survey of the switch-
able modules is shown at the end of this section. The safety
segment extends either to the next PF-O module or to the
end of the station. A safety-related input circuit together with
pulsed inputs is used for detecting broken wires and short
circuits.
Three types of safe power-feed modules are available in the
u-remote system:
–UR20-PF-O-1DI-SIL (one safe input)
–UR20-PF-O-2DI-SIL (two safe inputs)
–UR20-PF-O-2DI-DELAY-SIL (two safe inputs, delayed
switching off possible)
Thereby the following safety functions can be implemented:
–Up to two dual-channel safety circuits (AND linked), e.g.
for emergency stop switch, safety door contacts and
safety light curtains
–A range of output modules within a u-remote station is
safely supplied with power via the switched 24VSafe
output.
–PF-O-xDI-SIL modules can be cascaded.
Safety function
The safety function of the safe power-feed modules is
that the safe output “24VSafe” is being switched accord-
ing to the informations of the inputs (Type3 according to
EN61131-2, N-switching respectively). The safe status is
“24V switched off” (current path for outputs and the output
“24V Safe” is switched off).
Safe power-feed module UR20-PF-O-1DI-SIL
Safe power-feed module UR20-PF-O-2DI-SIL and UR20-PF-O-2DI-DELAY-SIL
4 System description of safe power-feed modules

4 System description of safe power-feed modules | Sample design
16 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
4.1 Sample design
The following picture exemplies how to design a safety seg-
ment using a safe power-feed module. All output modules
arranged within the safety segment will be switched safely.
Input modules can be arranged within the safety segment,
only they do not fulll any safety function and are not inu-
enced by the PF-O-xDI-SIL module.
Safe I/O modules with outputs may not be posi-
tioned within a safety segment.
For detailed planning please also observe the
notes in the section „Conguration“.
DI DI DO DIDODODO DO
PF-O
SIL PF-OAO DO
FB
UOUT 24 V Safe
UOUT 24 V
UIN 24 V
24 V
24 V
24 V
1
Example set-up of a safety segment (1) with PF-O-xDI-SIL
To switch the 24VSafe voltage back on, either an automatic
or a manual start can be selected.
–Automatic start: the safe output current path is switched
on immediately after resetting the safety circuit(s).
WARNING
Possible danger to life!
The option “Automatic start” might only be
used, after a risk analysis has shown that the
application is suitable.
–Manual start: the output current path is only switched on
again if the start button has been held down for 0.5 to
2seconds.

4 System description of safe power-feed modules | Transition diagramm
17u-remote IP20 modules for functional safety manual1484600000/04/06.2017
4.2 Transition diagramm
State 2
Wait for start
24 VSafe off
SS1 off
State 4
Running
24 VSafe on
SS1 on
Safety circuit active
1
Autostart mode, not after power on
Safety circuit active
2
Manual start mode
Safety circuit inactive
3
no delay
Manual start
key pressed
Delay time
expired
Safety circuit active1
Manual start mode or autostart mode after power on
Safety circuit inactive3
Safety circuit active1
Autostart mode
Safety circuit inactive3
delay
State 1
Idle
24 VSafe off
SS1 off
State 3
Wait for power off
24 VSafe on
SS1 off
1) Both channels of a safety circuit must get active within a discrepancy time of 0.5 s max.
2) The 24 V Safe output remains on until delay time is expired.
3) At least one channel of the safety circuit.
Transition diagramm of safe power-feed modules
With the delay SIL module (UR20-PF-O-2DI-DELAY-SIL)
switching off can be delayed by a dened time so that,
for example, a machine can be shut down in a controlled
manner. The delay time can be set in four steps between
0 and 60 seconds (corresponds to stop category 1 as per
EN60204).

4 System description of safe power-feed modules | Modules switchable by PF-O-xDI-SIL
18 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
4.3 Modules switchable by PF-O-xDI-SIL
Safely switchable output modules:
–UR20-4DO-P
–UR20-4DO-P-2A
–UR20-4DO-PN-2A
–UR20-8DO-P
–UR20-8DO-P-2W-HD
–UR20-16DO-P
–UR20-16DO-P-PLC-INT
–UR20-4DO-N
–UR20-4DO-N-2A
–UR20-8DO-N
–UR20-2PWM-PN-0.5A
–UR20-2PWM-PN-2A
–UR20-4AO-UI-16
–UR20-4AO-UI-16-HD
–UR20-4AO-UI-16-DIAG
–UR20-4AO-UI-16-DIAG-HD
In case a N-switching output module is positioned within a
safety segment the connected load needs to be switched
against +24V Safe.
The relay output modules UR20-4RO-CO-255 and UR20-
4RO-SSR-255 are not safely switchable, therefore they must
not switch any safety function.
The digital counter module UR20-1CNT-1DO-100 will not be
switched since it is supplied via the input current path.
4.4 Conguration
A PF-O-xDI-SIL module can be positioned anywhere in
the u-remote station. Multiple PF-O-xDI-SIL modules
and thus safety segments can be set up in a single station.
When planning a u-remote station with PF-O-xDI-SIL
modules, the following requirements must be met:
–The overall current consumption from the system current
path of all switchable modules within a safety segment
must be lower than 100mA (see table in section4.5).
–Each safety segment might include at most 12 switcha-
ble modules.
–The switch-off delay time for the safe input channels
within a safety circuit is 500ms ± 10ms.
–The load output is not designed for either inductive or
capacitive loads.
–The feed-in of the PF-O-xDI-SIL module must be
safeguarded with a 8-A super fast fuse.
–A SELV/PELV power supply must be used.
–The safely shut-off systems/applications must get their
power exclusively from the safe feed-in module
PF-O-xDI-SIL. Likewise, it must not be possible to
feed external energy into the safety segment elsewhere.
–Relay modules can be located within a safety segment,
however their outputs cannot be safely shut off in case of
a malfunction.
–At the SS1 output of the UR20-PF-O-2DI-DELAY-SIL, only
systems/equipment that do not feed any power back into
the system in the event of a malfunction can be con-
nected.
–Any external short circuits in the wiring of the safe output
must be avoided.
–Fault exclusion as per EN ISO13849-2 must be provided.
4.5 Switch-off delay time
The turn-off time of a PF-O-xDI-SIL module is 20ms,
caused by the hardware and rmware delay time. The time
required until the output voltage even of the last switchable
module of a safety segment is below 5V, can be calculated
as follows:
Turn-off time of a PF-O-xDI-SIL module
+ Sum of all modules’ hardware delay
= Switch off delay [ms]
Switch-off delay and current consumption
Hardware delay [ms] Current consumption
from ISYS [mA]
UR20-4DO-P 2 8
UR20-4DO-P-2A 2 8
UR20-4DO-PN-2A 3 15
UR20-8DO-P 1 15
UR20-8DO-P-2W-HD 1 15
UR20-16DO-P 1 10
UR20-16DO-P-PLC-INT 1 10
UR20-4DO-N 2 8
UR20-4DO-N-2A 2 8
UR20-2PWM-PN-0.5A 5 10
UR20-2PWM-PN-2A 5 10
UR20-4AO-UI-16 150* 10
UR20-4AO-UI-16-HD 150* 10
UR20-4AO-UI-16-DIAG 150* 10
UR20-4AO-UI-16-DIAG-HD 150* 10
*The delay time is always 150ms, irrespective of the amout of these modules.

4 System description of safe power-feed modules | Operation with and without test pulses
19u-remote IP20 modules for functional safety manual1484600000/04/06.2017
4.6 Operation with and without test pulses
The safe input circuits are designed to connect passive dual
channel switching devices. Each input channel is provided
with pulsed voltage the test pulses of which are analysed.
Therefore the highest safety levels can be achieved (see tech-
nical data).
1
2
3
4
1
2
3
4
S11 / S31
S12 / S32
S21 / S41
S22 / S42
S11 / S31
S12 / S32
S21 / S41
S22 / S42
+24 V DC
Safety relay
Sensor
Exemplary operation with test pulses
The safe power-feed module UR20-PF-O-2DI-DELAY-SIL
might also be operated without test pulses. This is mandato-
ry whenever an external device gernerating own test pulses
is connected.
When using switching devices generating own
test pulses please regard that low level with a
duration of more than 2ms will be detected as an
opening of the safety circuit.
1
1
2
3
4
1
4
2
3
4
+24 V DC
S11 / S31
S12 / S32
S21 / S41
S22 / S42
GND
...
1
2
3
4
+24 V DC
S11 / S31
S12 / S32
S21 / S41
S22 / S42
Safety relay
with
OSSD
outputs
Exemplary operation of the UR20-PF-O-2DI-DELAY-SIL without test pulses
Test pulses can be enabled or disabled using the DIP-switch-
es of the module.

20 1484600000/04/06.2017u-remote IP20 modules for functional safety manual
This manual suits for next models
10
Table of contents
Other Weidmuller I/O System manuals
Popular I/O System manuals by other brands

gefran
gefran SIEIDrive EXP-D14A4F instruction manual

Unitronics
Unitronics V200-18-E62B manual

Campbell
Campbell SDM-CVO4 product manual

National Instruments
National Instruments NI 9411 Operating instructions and specifications

Acard
Acard AEC-7732U Install Quick Guide

SolarMax
SolarMax 10 005 981 installation manual