Weidmuller UR67 Series User manual

UR67-PN-V14-CU-16DI-12 2599680000
UR67-PN-V14-CU-8DIDO-12 2599670000
UR67-PN-V14-POF-16DI-12 2599700000
UR67-PN-V14-POF-8DIDO-12 2599690000
Remote-I/O-System u-remote UR67
I/O-Modules IP67 PROFINET-V14
Manual
Letʼs connect.

Content
22599890000/01/03.2020 Manual UR67-PROFINET-V14
1 About this documentation 3
1.1 Symbols and notes 3
1.2 Complete documentation 3
1.3 Standard data structure 4
1.4 Software releases described 4
2 Safety 5
2.1 General safety notice 5
2.2 Intended use 5
2.3 Legal notice 5
3 System overview 6
3.1 Fieldbus features 7
3.2 Web server 7
3.3 Accessories 7
3.4 Explanation of serial numbers 8
4 Module descriptions 9
4.1 UR67-PN-V14-CU-16DI-12 9
4.2 UR67-PN-V14-CU-8DIDO-12 10
4.3 UR67-PN-V14-POF-16DI-12 11
4.4 UR67-PN-V14-POF-8DIDO-12 12
4.5 Connection assignments 13
4.6 Connection-channel allocation 13
4.7 Technical Data 14
4.8 Output behaviour in the event of under-voltage 16
4.9 Derating 16
5 Installation and wiring 17
5.1 Preparing for installation 17
5.2 Installing a module 17
5.3 Earthing the module 17
5.4 Attaching markers 20
5.5 Wiring 20
5.6 Insulation testing 20
6 Commissioning 21
6.1 Requirements 21
6.2 Device description les 21
6.3 Commissioning with the TIA portal 21
6.4 Adjustable parameters 25
6.5 Simple Network Management Protocol (SNMP) 27
7 Bit assignment 28
7.1 Process input data 28
7.2 Process output data 29
7.3 Diagnostic data 30
8 Diagnostics 32
8.1 Descriptions of errors 32
8.2 Diagnostics at the control unit 32
8.3 LED displays and troubleshooting 33
9 Web server 35
9.1 Connecting and starting up the web server 35
9.2 Getting to know and setting up the web server 35
9.3 Accessing and editing parameters 37
9.4 Accessing process data and diagnostics 37
9.5 Accessing and editing I&M data 38
9.6 Restarting the web server 38
9.7 Resetting the module to factory settings 39
9.8 Web server in Force mode 39
9.9 Updating rmware 40
9.10 Saving a service le 41
10 Disassembly and disposal 42
10.1 Disassembling the u-remote module 42
10.2 Disposing of the u-remote module 42
Manufacturer
Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 26
D-32758 Detmold
T +49 5231 14-0
F +49 5231 14-292083
www.weidmueller.com Document No. 2599890000
Revision 01/March 2020

1 About this documentation | Symbols and notes
32599890000/01/03.2020 Manual UR67-PROFINET-V14
1 About this documentation
1.1 Symbols and notes
The safety notices in this documentation are designed ac-
cording to the severity of the danger.
DANGER
Imminent danger to life!
Notes with the signal word “Danger” warn you
of situations that will result in serious injury or
death if you do not follow the instructions giv-
en in this manual.
WARNING
Possible danger to life!
Notes with the signal word “Warning” warn
you of situations that may result in serious inju-
ry or death if you do not follow the instructions
given in this manual.
CAUTION
Risk of injury!
Notes with the signal word “Caution” warn you
of situations that may result in injury if you do
not follow the instructions given in this man-
ual.
ATTENTION
Material damage!
Notes with the signal word “Attention” warn you of hazards
that may result in material damage.
Text next to this arrow are notes that are not rele-
vant to safety, but provide important information
about proper and effective work procedures.
The situation-dependent safety notices may contain the fol-
lowing warning symbols:
Symbol Meaning
Warning against dangerous electrical voltage
Warning against electrostatically charged
components
Warning against hot surfaces
Warning against laser rays
Warning against automatic startup
Observe the documentation
▶All instructions can be identified by the black triangles
next to the text.
–Lists are marked with a tick.
4
21
3
Female connections with sockets are illustrated
using empty circles.
1
34
2
Male connections with pins are illustrated using
lled circles.
1.2 Complete documentation
The documentation is intended for trained elec-
tricians who are familiar with national and inter-
national laws, provisions and standards.
All documents can also be downloaded from
the Weidmüller website.

1 About this documentation | Standard data structure
42599890000/01/03.2020 Manual UR67-PROFINET-V14
1.3 Standard data structure
All information about the structure of data
(e.g.process data and parameters) refers to the
standard data format settings in the module
parameters. These are shown in the Motorola
format.
1.4 Software releases described
The present manual describes the following rmware releas-
es:
Firmware releases
Order No. Module Release
2599680000 UR67-PN-V14-CU-16DI-12 01.00.00
2599670000 UR67-PN-V14-CU-8DIDO-12 01.00.00
2599700000 UR67-PN-V14-POF-16DI-12 01.00.00
2599690000 UR67-PN-V14-POF-8DIDO-12 01.00.00
Device description files
Fieldbus protocol Release
PROFINET 20190118
Web server language files
Language Release Availability
German 01.00.00 On delivery
English 01.00.00 On delivery
Chinese 01.00.00 On delivery

2 Safety | General safety notice
52599890000/01/03.2020 Manual UR67-PROFINET-V14
2 Safety
This chapter includes general safety instructions on handling
the u-remote IP67 modules. Specic safety instructions for
specic tasks and situations are given at the appropriate
places in the documentation.
All work must only be carried out by
trained electricians who are familiar with
the safety standards that apply to automa-
tion technology.
The documentation must be stored in such a
way that it is accessible to operating staff at
all times.
2.1 General safety notice
When working during continued operations, the emergency
stop mechanisms must not be made ineffective.
If faults relating to a u-remote product cannot be rectied,
the product in question must be sent to Weidmüller. Weid-
müller assumes no liability if the module is tampered with!
All connected devices must comply with the requirements
set out in EN 61558-2-4 and EN 61558-2-6. Cables and ac-
cessories may only be installed if they meet the requirements
and provisions regarding safety, electromagnetic compati-
bility and, if applicable, telecommunications terminal equip-
ment, as well as the relevant specications. Information on
the specic cables and accessories that are permissible for
installation is provided in this manual or can be requested
from Weidmüller.
Electrostatic discharge
u-remote products can be damaged or destroyed by electro-
static discharge. During handling of the products, the neces-
sary safety measures against electrostatic discharge (ESD)
must be observed in accordance with IEC61340-5-1 and
IEC61340-5-2. The packing and unpacking as well as the
assembly and disassembly of a device must only be carried
out by qualied personnel.
Fusing
The operator must set up the equipment so that it is pro-
tected against overloading. The 24VDC power supply units
used for supplying the system must fulll the SELV category.
The upstream fuse must be designed such that it does not
exceed the maximum load current. The maximum permissi-
ble load current for the u-remote components can be found
in the technical data.
The operator must decide whether additional surge protec-
tion is required in accordance with IEC 62305. Voltages that
exceed +/-30V may lead to the destruction of the modules.
A power supply with secure isolation must be used.
Earthing (functional earth FE)
Each UR67-PN-V14 module has two earthing connections;
the connection points are labelled with "XE". More informa-
tion can be found in chapter 5.
Shielding
Shielded lines are to be connected with shielded plugs in
compliance with the relevant standard.
2.2 Intended use
The UR67-PN-V14 modules are decentralised input and out-
put devices within a PROFINET network (RT/IRT).
The products are designed for use in an industrial environ-
ment and must only be used within the scope of the stated
technical specications. The devices to be connected must
comply with the requirements set out in EN61558-2-4 and
EN61558-2-6. The industrial environment is labelled as
such to ensure that consumers are not directly connected to
the public low-voltage network. Additional measures must
be taken for use in the home, and in the business and com-
mercial sectors.
Any intervention in the products’ hardware or software other
than described in this manual may only be performed by
Weidmüller.
Malfunction-free operation is only guaranteed if the housing
is fully assembled. Observance of the documentation is also
part of the intended use.
2.3 Legal notice
The UR67-series products comply with the EU Directive
2014/30/EU (EMC Directive).
Components of free software products are integrated into
the modules: The licence terms are available from the web
server.

3 System overview
62599890000/01/03.2020 Manual UR67-PROFINET-V14
3 System overview
UR67-PN-V14 modules for PROFINET
The UR67-PN-V14 modules are digital I/O modules that com-
municate via PROFINET.
The fully encapsulated metal housing means that the mod-
ules comply with degree of protection IP67.
The digital inputs comply with type2 in accordance with
IEC61131-2. For connections with digital inputs, a self-reset-
ting fuse limits the sensor supply current to 0.5A per pin.
The output current is up to 2 A per channel. The output cir-
cuits are galvanically isolated from the rest of the network
and from the sensor electronics. The outputs are designed
with short circuit protection.
The modules with output functionality support a substitute
value function. This function can be used to set how an
output is to respond to an impaired or interrupted eldbus
communication.
The UR67-PN-V14 modules differ with regard to their I/O
functionality and their Ethernet connections.
Module designation Order number Ethernet connection Number of digital inputs Number of digital outputs
UR67-PN-V14-CU-16DI-12 2599680000 V14 PushPull RJ45 16 0
UR67-PN-V14-CU-8DIDO-12 2599670000 V14 PushPull RJ45 8 8
UR67-PN-V14-POF-16DI-12 2599700000 V14 PushPull SC-RJ POF 16 0
UR67-PN-V14-POF-8DIDO-12 2599690000 V14 PushPull SC-RJ POF 8 8
Status LEDs are assigned to the module and to each I/O con-
nection, and the colour and ashing behaviour of these LEDs
indicate the status of the connection (see chapter 8).
UR67-PN-V14-CU-X (2599670000, 2599680000) UR67-PN-V14-
POF-X (
2599690000
,
2599700000
)

3 System overview | Fieldbus features
72599890000/01/03.2020 Manual UR67-PROFINET-V14
3.1 Fieldbus features
MAC addresses
Each module has three unique MAC addresses assigned by
the manufacturer that cannot be changed by the user (one
for the module and two for the Ethernet ports). The MAC ad-
dress of the module is imprinted on the module itself.
Integrated Ethernet switch
The integrated Ethernet cut-through switch with two con-
nections makes it possible to set up ring topologies and line
topologies.
PROFINET product features
The UR67-PN-V14 modules support the PROFINET IO device
IRT (Isochronous Real-Time). This means that process data
can be transferred in real-time.
The UR67-PN-V14 modules support the following PROFINET
functions:
–DCP for the automatic assignment of IP addresses
–Fast start-up for prioritised start-up
–Device replacement without interchangeable medium /
PG for the replacement of devices without re-configura-
tion
–LLDP for the detection of devices in the vicinity (neigh-
bouring device detection)
–MRP for the implementation of redundant PROFINET net-
works without additional switches
–Shared Device for the flexible assignment of channels
and modules to different control units
–SNMP for the monitoring of network components
Alarm and diagnostic messages
The modules offer extended alarm and diagnostic messages.
–Module diagnostics
–Individual channel diagnostics
–Fibre-optic cable diagnostics (only with UR67-PN-V14-
POF)
Device description les
A device description le is needed for the conguration and
parameterisation of the module in the engineering tool.
–PROFINET: modular GSDML file
You can download the current device description
les from the Weidmüller website.
3.2 Web server
The web server can be used to display the UR67-PN-V14
module on a connected PC. This allows you to execute the
following functions for test purposes or during commission-
ing or service work:
–Access the module status
–Display and change the module parameters
–Access diagnostic information
–Operate the module in Force mode for testing purposes
A description of the web server can be found in chapter 9.
3.3 Accessories
Protective caps
Degree of protection IP67 is only achieved when the module
is fully installed. Therefore, all connections not being used
must be tted with protective caps. The dust caps included
with the module for the supply connections and the Ethernet
connections are not suitable for achieving degree of protec-
tion IP67.
Connection Protective cap Order No.
M12 SAI-SK-M12-UNI 2029 2330260000
V14 PushPull RJ45 IE-BP-V14P 1058310000
V14 PushPull SC-RJ POF IE-BP-V14P 1058310000
PushPull Power IE-BP-VAPP (IP 54) 1068930000
Markers
Markers are required for the labelling of operating materials.
The markers can be printed using the Weidmüller PrintJet
ADVANCED (order no. 1324380000).
Markers Order No.
ESG 8/13.5/43.3 SAI AU
large markers 8/43.3 and small markers 8/13.5 1912130000
Cable lugs
In order to select the correct cable lugs for attaching the FE
conductors, we recommend using the Weidmüller catalogue
6 or the product catalogue on Weidmüller website.
Cables and connections
In order to select the correct cables, we recommend using
the Weidmüller catalogue 8 and 9 or the product congura-
tor on the Weidmüller website.

3 System overview | Explanation of serial numbers
82599890000/01/03.2020 Manual UR67-PROFINET-V14
3.4 Explanation of serial numbers
Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Year Code Month Code Day Code Manufacturer Code Product family code Consecutive number
2018 A S January 1 1 1 0 1 P C 7 4 0 0 1 0 1
2019 A T February 2 2 2 0 2
2020 A C March 3 3 3 0 3
2021 A V April 4 4 4 04
2022 A W May 5 5 5 0 5
2023 AXJune 6 6 6 06
2024 A YJuly 7 7 7 07
2025 AZAugust 8 8 8 0 8
2026 B A September 9 9 9 0 9
2027 B B October O 10 A1 0
2028 B C November N 11 B1 1
2029 B D December D 12 C1 2
2030 B E 13 D1 3
2031 B F 14 E 14
2032 B G 15 F1 5
2033 BH16 G 16
2034 B I 17 H 17
2035 B J 18 I1 8
2036 B S 19 J1 9
2037 B L 20 S20
2038 BM 21 L 2 1
2039 B N 22 M 2 2
2040 B O 23 N2 3
2041 B P 24 O 24
2042 B Q 25 P2 5
2043 B R 26 Q 2 6
2044 B S 27 R 27
... 28 S2 8
2052 C A 29 T2 9
2053 C B 30 C3 0
... 31 V3 1
Example
Serial number: AS7H21PC7400101
Date: 17.07.2018
Manufacturer: Weidmüller
Product family: u-remote

4 Module descriptions | UR67-PN-V14-CU-16DI-12
92599890000/01/03.2020 Manual UR67-PROFINET-V14
4.1 UR67-PN-V14-CU-16DI-12
Input module UR67-PN-V14-CU-16DI-12 (Order No. 2599680000)
The module has eight 5-pin A-coded M12 connections for
signal lines. The Ethernet cable is connected via two V14
PushPull RJ45 connectors. The power supply is connected
via two PushPull Power connections.
The UR67-PN-V14-CU-16DI-12 module has 16digital inputs
(P-switching).
LED Display Meaning
X0...X7, 0 yellow/red Channel 0 status
X0...X7, 1 yellow/red Channel 1 status
US1 green/orange/red Supply voltage US1 status
US2 green/orange/red Supply voltage US2 status
BF red Bus error
SF red System error
LNK1/ACT1 green/orange Connection/XF1 connection activity
LNK2/ACT2 green/orange Connection/XF2 connection activity
TEST white Locating PROFINET devices
For information on LED displays and error messages, see chapter 8
1
2
3
4
5
6
7
8
9
10
Device description UR67-PN-V14-CU-16DI-12
1 Module markers
2 I/O connectionX0
3 Status LED forX0 connection, channel0/channel1
4 Supply connection XD1
5 Ethernet connection XF1
6 Connection markers
7 Module status LEDs
8 Supply connection XD2
9 Ethernet connection XF2
10 Earthing connections XE
4 Module descriptions

4 Module descriptions | UR67-PN-V14-CU-8DIDO-12
102599890000/01/03.2020 Manual UR67-PROFINET-V14
4.2 UR67-PN-V14-CU-8DIDO-12
Input and output module UR67-PN-V14-CU-8DIDO-12 (Order No. 2599670000)
The module has eight 5-pin A-coded M12 connections for
signal lines. The Ethernet cable is connected via two V14
PushPull RJ45 connectors. The power supply is connected
via two PushPull Power connections.
The UR67-PN-V14-CU-8DIDO-12 module has 8digital inputs
and 8digital outputs (P-switching).
LED Display Meaning
X0...X7, 0 yellow/red Channel 0 status
X0...X7, 1 yellow/red Channel 1 status
US1 green/orange/red Supply voltage US1 status
US2 green/orange/red Supply voltage US2 status
BF red Bus error
SF red System error
LNK1/ACT1 green/orange Connection/XF1 connection activity
LNK2/ACT2 green/orange Connection/XF2 connection activity
TEST white Locating PROFINET devices
For information on LED displays and error messages, see chapter 8
1
2
3
4
5
6
7
8
9
10
Device description UR67-PN-V14-CU-8DIDO-12
1 Module markers
2 I/O connectionX0
3 Status LED forX0 connection, channel0/channel1
4 Supply connection XD1
5 Ethernet connection XF1
6 Connection markers
7 Module status LEDs
8 Supply connection XD2
9 Ethernet connection XF2
10 Earthing connections XE

4 Module descriptions | UR67-PN-V14-POF-16DI-12
112599890000/01/03.2020 Manual UR67-PROFINET-V14
4.3 UR67-PN-V14-POF-16DI-12
Input module UR67-PN-V14-POF-16DI-12 (Order No. 2599700000)
The module has eight 5-pin A-coded M12 connections for
signal lines. The Ethernet cable is connected via two V14
PushPull SC-RJ-POF connectors. The power supply is con-
nected via two PushPull Power connections.
The UR67-PN-V14-POF-16DI-12 module has 16digital in-
puts (P-switching).
LED Display Meaning
X0...X7, 0 yellow/red Channel 0 status
X0...X7, 1 yellow/red Channel 1 status
US1 green/orange/red Supply voltage US1 status
US2 green/orange/red Supply voltage US2 status
BF red Bus error
SF red System error
LNK1/ACT1 green/orange Connection/XF1 connection activity
LNK2/ACT2 green/orange Connection/XF2 connection activity
DIA POF green/orange/red POF diagnostics
TEST white Locating PROFINET devices
For information on LED displays and error messages, see chapter 8
1
2
3
4
5
6
7
8
9
10
Device description UR67-PN-V14-POF-16DI-12
1 Module markers
2 I/O connectionX0
3 Status LED forX0 connection, channel0/channel1
4 Supply connection XD1
5 Ethernet connection XF1
6 Connection markers
7 Module status LEDs
8 Supply connection XD2
9 Ethernet connection XF2
10 Earthing connections XE

4 Module descriptions | UR67-PN-V14-POF-8DIDO-12
122599890000/01/03.2020 Manual UR67-PROFINET-V14
4.4 UR67-PN-V14-POF-8DIDO-12
Input and output module UR67-PN-V14-POF-8DIDO-12 (Order No. 2599690000)
The module has eight 5-pin A-coded M12 connections for
signal lines. The Ethernet cable is connected via two V14
PushPull SC-RJ-POF connectors. The power supply is con-
nected via two PushPull Power connections.
The UR67-PN-V14-POF-8DIDO-12 module has 8digital in-
puts and 8digital outputs (P-switching).
LED Display Meaning
X0...X7, 0 yellow/red Channel 0 status
X0...X7, 1 yellow/red Channel 1 status
US1 green/orange/red Supply voltage US1 status
US2 green/orange/red Supply voltage US2 status
BF red Bus error
SF red System error
LNK1/ACT1 green/orange Connection/XF1 connection activity
LNK2/ACT2 green/orange Connection/XF2 connection activity
DIA POF green/orange/red POF diagnostics
TEST white Locating PROFINET devices
For information on LED displays and error messages, see chapter 8
1
2
3
4
5
6
7
8
9
10
Device description UR67-PN-V14-POF-8DIDO-12
1 Module markers
2 I/O connectionX0
3 Status LED forX0 connection, channel0/channel1
4 Supply connection XD1
5 Ethernet connection XF1
6 Connection markers
7 Module status LEDs
8 Supply connection XD2
9 Ethernet connection XF2
10 Earthing connections XE

4 Module descriptions | Connection assignments
132599890000/01/03.2020 Manual UR67-PROFINET-V14
4.5 Connection assignments
I/O connections (X0...X7)
M12, A-coded 16DI 8DIDO
1
3
5
4
2
1+24V US1
n.c. (X0...X3)
+24V US1 (X4...X7)
2DI1 DO1 (X0...X3)1)
DI1 (X4...X7)2)
3GND US1
GND US2 (X0...X3)
GND US1 (X4...X7)
4 DI0 DO0 (X0...X3)1)
DI0 (X4...X7)2)
5FE FE
1) supplied via US2
2) references US1
Supply connection (XD1, XD2)
PushPull Power Signal Role
5
4
3
2
1
5FE Functional earthing
4 GND US2 Earth/reference potential US2
3+24V US2/ 16A Supply voltage US2
2GND US1 Earth/reference potential US1
1+24V US1/ 16A Supply voltage US1
PROFINET (XF1, XF2)
V14 PushPull RJ45 Signal Role
8 1...
1TX+ Transmission data +
2TX- Transmission data -
3RX+ Received data +
4 n.c. –
5n.c. –
6 RX-- Received data -
7 n.c. –
8n.c. –
V14 PushPull SC-RJ POF
1 2
1RX Received data
2TX Transmission data
4.6 Connection-channel allocation
UR67-PN-V14-CU-16DI-12, UR67-PN-V14-POF-16DI-12
Connection Pin Channel Connection Pin Channel
X0
4 DI 0
X4
4 DI 8
2DI 1 2DI 9
X1
4 DI 2
X5
4 DI 10
2DI 3 2DI 11
X2
4 DI 4
X6
4 DI 12
2DI 5 2DI 13
X3
4 DI 6
X7
4 DI 14
2DI 7 2DI 15
UR67-PN-V14-CU-8DIDO-12, UR67-PN-V14-POF-8DIDO-12
Connection Pin Channel Connection Pin Channel
X0
4 DO 0
X4
4 DI 0
2DO 1 2DI 1
X1
4 DO 2
X5
4 DI 2
2DO 3 2DI 3
X2
4 DO 4
X6
4 DI 4
2DO 5 2DI 5
X3
4 DO 6
X7
4 DI 6
2DO 7 2DI 7

4 Module descriptions | Technical Data
142599890000/01/03.2020 Manual UR67-PROFINET-V14
4.7 Technical Data
Technical data UR67-PN-V14-CU-16DI-12
(2599680000)
UR67-PN-V14-CU-8DIDO-12
(2599670000)
UR67-PN-V14-POF-16DI-12
(2599700000)
UR67-PN-V14-POF-8DIDO-12
(2599690000)
Bus system
Ethernet connection 2x V14 PushPull RJ45 data connectors (AIDA) 2x V14 PushPull SC-RJ POF data connectors (AIDA)
Fieldbus protocol PROFINET IO (RT/IRT), V2.3, Conformance Class C
Redundancy protocol MRP
Input data width max. 10 byte
Output data width max. 4 byte
Parameter data max. 16 byte
Transfer rate Max. 100 Mbps
Fast startup < 500 ms
Shared device/input yes, for 2 control units
Addressing DCP
GSDML GSDML-V2.33-WI-UR67PN-20190118.xml
Net load Class III as per Security Level 1 Test (PNO)
I&M data I&M 0-4
Inputs
Number 16 816 8
Input type Sourcing, type 2 as per IEC 61131-2
Low input voltage < +5V with regard to 0V of input voltage US1
High input voltage > +11V with regard to 0 V of input voltage US1
Input filter Input delay, adjustable from 0 to 20 ms
Sensor supply 500mA
Sensor connection 2-wire+FE, 3-wire+FE via M12, 5-pin A-coded
Reverse polarity protection yes
Short circuit protection Sensor supply: multifuse, automatic restart after tripping
Surge protection Yes
Outputs
Number 0 8 0 8
Output type Sourcing
Load type Ohmic, inductive, lamp load
Max. output current
per channel 2A
per module 16 A
Breaking energy (inductive) 150mJ per channel
Switching frequency
Ohmic load (min. 12 Ω) 500Hz
Inductive load (DC13) 0.2Hz without free-wheeling diode, 500Hz with suitable free-wheeling diode
Lamp load (48W) 10Hz
Actuator connection 2-wire+FE via M12, 5-pin A-coded
Short-circuit-proof yes
Protective circuit Constant current with thermal cutout; congurable parameters: automatic restart / malfunction acknowledgement

4 Module descriptions | Technical Data
152599890000/01/03.2020 Manual UR67-PROFINET-V14
Technical data UR67-PN-V14-CU-16DI-12
(2599680000)
UR67-PN-V14-CU-8DIDO-12
(2599670000)
UR67-PN-V14-POF-16DI-12
(2599700000)
UR67-PN-V14-POF-8DIDO-12
(2599690000)
Current limitation response time < 100µs
Surge protection yes
Supply
Sensor/module supply US1 24VDC +20%/-15%
Actuator supply US2 24VDC +20%/-15%
Module electronics current con-
sumption
<150mA at 24VDC
Test voltage 500V DC between current paths and to FE
Functional safety Actuator supply US2, reliable cutout in accordance with PL d
Voltage bypass 10ms
General data
Type of protection IP 67 (not UL-tested)
Enclosure material Die-cast zinc, matt nickel surface
Temperature
Operation -20...+55°C
Storage, transport -40...+70°C
Weight 965g 970g 995g 1000g
Dimensions (H × W × D) 43 × 60 × 225mm 51 × 60 × 225mm
Flammability rating UL 94
Air pressure
Operation 1013 hPa (height: 0 m) up to 700 hPa (height: 3000 m) in accordance with IEC 61131-2
Storage, transport 1013 hPa (height: 0 m) up to 700 hPa (height: 3000 m) in accordance with IEC 61131-2
Humidity 10% to 95%, non-condensing in accordance with DIN EN 61131-2
Vibration resistance 0.35mm / 10 ...60,1 Hz and 5g / 60,1 ...500 Hz in accordance with DIN EN 60068-2-6
Shock resistance 50g / 11ms in accordance with DIN EN 60068-2-27
Pollution degree 3 (in accordance with EN 60664-1, VDE 0110-1)
Overvoltage category II
Tightening torques
Mounting screw M6 3Nm
Earthing screw M4 1.2Nm
Plug connector M12 0.5Nm
M12 protective cap 0.5Nm
Approvals and standards
EMC EN 61000-6-2:2005/AC:2005,
EN 61000-6-4:2007/A1:2001

4 Module descriptions | Output behaviour in the event of under-voltage
162599890000/01/03.2020 Manual UR67-PROFINET-V14
4.8 Output behaviour in the event of under-volt-
age
19,2 V 20,4 V
DO
US2
1
0
Output signal versus supply voltage US2 (output set in process data)
4.9 Derating
35 36 37 554544434241403938 46 5453525150494847
I
US2_max
[A]
T
A
[°C] / 2000 m
1
2
3
4
5
0
11
6
8
9
10
14
15
16
17
12
7
13 IUS1_max 8 A
IUS1_max 16 A
Derating of the UR67-PN-V14-POF modules
Above 2000m, the permissible ambient temperature for
UR67-PN-V14-POF modules decreases by 1 °C per 200 m.
The UR67-PN-V14-CU modules can be operated up to
3000m within the entire temperature range.

WARNING
Dangerous contact voltage!
▶All installation and wiring work must be
carried out with the power supply discon-
nected.
▶Make sure that the place of installation
has been disconnected from the power
supply!
CAUTION
Hot surface!
The module can become very hot when in
operation.
▶Allow the module to cool down before
touching it.
CAUTION
Risk of glare!
The Ethernet connections of the UR67-PN-
V14-POF modules contain a Class-1 laser.
▶Never look either directly or indirectly into
the laser beam!
▶Never aim the laser beam at other
persons!
5.1 Preparing for installation
Make sure that the permitted environmental conditions for
installation and operation are observed (see Technical data).
Installation dimensions
The installation dimensions are provided in the installation
drawings on the following pages.
Unpacking the delivery
▶Please check the delivery for completeness and transport
damage.
▶Please report any transport damage immediately to the
respective transport company.
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
u-remote products can be destroyed by elec-
trostatic discharge.
▶Please make sure that persons and work
equipment are sufficiently earthed!
▶Unpack all of the parts.
▶Dispose of all packaging in accordance with the local dis-
posal guidelines. The cardboard packaging can be sent
for paper recycling.
5.2 Installing a module
The installation surface must be level.
▶Drill the holes for the fixings (for the drilling dimensions,
see the installation drawings on the following pages).
▶Attach each module with two screws and a washer (in
accordance with DIN EN ISO 7089).
▶Observe the indicated screw dimension and tightening
torques (see installation drawing).
5.3 Earthing the module
The module must be earthed in order to discharge interfer-
ence currents and for EMC stability.
▶Connect one of the earth connections XE to the reference
earth (see installation drawing) using a low-impedance
connection.
If the installation surface is earthed, the connection can be
made directly via the mounting screws.
If the installation surface is not earthed, use an earthing strap
or a suitable cable with cable lug!
5 Installation and wiring
5 Installation and wiring | Preparing for installation
172599890000/01/03.2020 Manual UR67-PROFINET-V14

E141197
25
29.4
43.6
37.2
60
209.4
225
M6x25
3 Nm
M6x25
3 Nm
M4x6
1.2 Nm
1.8
7.6
Installation dimensions UR67-PN-V14-CU-16DI-12 (2599680000), UR67-PN-V14-CU-8DIDO-12 (2599670000)
5 Installation and wiring | Earthing the module
182599890000/01/03.2020 Manual UR67-PROFINET-V14

25
29.4
50.8
43.6
60
225
209.4
1.8
7.6
M6x25
3 Nm
M6x25
3 Nm
M4x6
1.2 Nm
Installation dimensions UR67-PN-V14-POF-16DI-12(2599700000), UR67-PN-V14-POF-8DIDO-12 (2599690000)
5 Installation and wiring | Earthing the module
192599890000/01/03.2020 Manual UR67-PROFINET-V14

5.4 Attaching markers
The module and all ports can be labelled using markers.
▶Press the labelled marker into the corresponding fixture
opening.
▶To remove a marker, lever it out carefully using a screw-
driver (2.5 or 3mm).
5.5 Wiring
WARNING
Dangerous contact voltage!
▶All installation and wiring work must be
carried out with the power supply discon-
nected.
▶Make sure that the place of installation
has been disconnected from the power
supply!
Once the module has been mechanically installed, the wiring
can then be carried out.
▶Connect all cables according to the wiring diagram.
All unused ports must be sealed with protective
caps in order to achieve protection class IP67.
The dust caps included with the module for the
supply connections and the Ethernet connections
are not suitable for achieving degree of protection
IP67.
Ensure compliance with the minimum permissi-
ble cable bending radius.
5.6 Insulation testing
Insulation tests must always be carried out before each com-
missioning and in accordance with the respective national
provisions.
ATTENTION
The product can be destroyed as a re-
sult of excessive test voltage!
Please observe the following during insula-
tion tests:
–The test voltage within a channel must
not exceed 30V between 24V and GND!*
–A max. test voltage of 500 V can be
applied to all other connection points.
* We recommend connecting 24V and GND at the power
supply plug.
5 Installation and wiring | Attaching markers