Installation and Startup Guide
This document covers the installation of MT8071iER1 Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated (Indoor Use Only).
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This does
not guarantee noise immunity in severe cases. Proper wire routing and grounding
will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating limits
are followed. Avoid installing units in environments where severe mechanical
vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to flammable
gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in Pollution
Degree 2 Environment.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Unpacking the Unit
Unpack and check the delivery. If damage is found, notify the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
(1) Installation Instruction, 2-sided A4 *1
(2) Rear-Mount HMI *1
(3) Power Connector *1
(4) Fuse 1.25A/250V 5*20mm *1
(5) USB Stick Clamp & Tying Strap *1
Installation Instructions
1. Around the cutout on the control cabinet, draw the
reference lines for positioning the overlay. Panel
Cutout: 174.6mm x 113.6mm
2. Select the mounting holes according to the wall
thickness of control cabinet and secure the
mounting brackets onto both sides of the HMI unit.
3. Secure the HMI to the cabinet by four studs.
4. Affix the overlay (user-prepared) to the cabinet
front surface.
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
Power Connections
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC
ground to the ‘-’ terminal.
2. When downloading project using a USB cable, do not
connect HMI with PLC and PC simultaneously, for electric
potential difference may result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image,
click the system setting button.
(Default System Password: 111111)
It is necessary to connect the HMI to
your network through a RJ-45 cable.
Panel Thickness Range
1.5mm [0.06"]
3.5mm [0.13"]
~
2mm [0.08"]
2.4mm [0.09"]
2.5mm [0.1"]
2.9mm [0.11"]
1.9mm [0.07"]
1.5mm [0.06"]
3mm [0.12"]
3.5mm [0.13"]
~~~~
wall
11.95mm [0.47"]
8.1mm [0.32"] (9.85mm [0.39"])
(13mm [0.51"])
?.7mm [?.15"]
?.5mm [?.14"]
M3 x 0.5P x 8L
HEX NUTS M3 x 0.5 P
189.6mm [7.46"]
137.08mm [5.40"]
189.6mm [7.46"]
137.08mm [5.40"]
5.1mm [0.20"]
26.15mm [1.03"]
3mm [0.12"]
34.25mm [1.35"]
cdefg
174.6mm [6.87"]
113.6mm [4.47"]
MT8070iER:
174.6mm [6.87"] W x 113.6mm [4.47"] H
213.6mm [8.41"]
100mm [3.94"]
20.15mm [0.79"]
13.3mm [0.52"]
ba
Maximum Wall Thickness : 3.5 mm [ 0.13"]
MT8071iER1 series
Installation Instruction
Go to the Network tab, you may choose
to auto get DHCP IP, or designate your
own IP.
1
2
3
4
5
Panel Thickness Range
1.5mm [0.06"]
3.5mm [0.13"]
wall
11.95mm [0.47"]
8.1mm [0.32"] (9.85mm [0.39"])
(13mm [0.51"])
192.55mm [7.58"]
138.55mm [5.45"]
2mm [0.08"]
2.4mm [0.09"]
2.5mm [0.1"]
2.9mm [0.11"]
1.9mm [0.07"]
1.5mm [0.06"]
3mm [0.12"]
3.5mm [0.13"]
~~~~
Ø4mm [Ø0.16"] Ø3.7mm [Ø0.15"]
M3 x 0.5P x 8L
HEX NUTS M3 x 0.5 P
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
dialog box:
Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project file to HMI.
Using screensaver and backlight saver is recommended in order to avoid image persistence caused
by displaying the same image on HMI for a long time.
( Please refer to EasyBuilder Pro User Manual for software operation details )
Communication Connections
NOTE:
1. COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at a time.
COM1 RS232, 9 Pin, Male, D-sub COM2/3 RS485, 9 Pin, Female, D-sub
DIP SW Settings
Battery Replacement
Battery replacement shall be performed by qualified personnel only and care must be taken when
handling lithium batteries. For more information on battery replacement and disposal considerations,
please refer to the following link:
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touch Screen Calibration Mode
OFF
ON
OFF
OFF
Hide HMI System Setting Bar
OFF
OFF
ON
OFF
Boot Loader Mode
OFF
OFF
OFF
ON
Not supported
OFF
OFF
OFF
OFF
Normal
Another method to enter touch screen calibration mode: Press and hold
anywhere on the screen for more than 2 seconds when HMI starts.
CAUTION
NN
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.
PIN#
COM1 [RS232]
1
2
RxD
3
TxD
4
5
GND
6
7
RTS
8
CTS
9
PIN#
COM2 [RS485]
COM3
[RS485]
2W
4W
1
Data-
Rx-
2
Data+
Rx+
3
Tx-
4
Tx+
5
GND
6
Data-
7
8
9
Data+
Power
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power.An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
High
Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME8071ER_MT8071iER1_Installation_170620
DANGER
6
7
8
9

Other weintek Network Hardware manuals

weintek iR-ETN Series User manual

weintek

weintek iR-ETN Series User manual

weintek CMT G03 Series User manual

weintek

weintek CMT G03 Series User manual

weintek MT8070iER1 Series User manual

weintek

weintek MT8070iER1 Series User manual

weintek cMT-G05 User manual

weintek

weintek cMT-G05 User manual

weintek cMT-SVR-100 User manual

weintek

weintek cMT-SVR-100 User manual

weintek iR-ETN40P User manual

weintek

weintek iR-ETN40P User manual

Popular Network Hardware manuals by other brands

Alcatel-Lucent 5620 manual

Alcatel-Lucent

Alcatel-Lucent 5620 manual

D-Link DXS-3610-54S Quick installation guide

D-Link

D-Link DXS-3610-54S Quick installation guide

Huawei SUN2000 Series user manual

Huawei

Huawei SUN2000 Series user manual

Rockwell 57C404B instruction manual

Rockwell

Rockwell 57C404B instruction manual

VersaMax GFK-1551D quick start guide

VersaMax

VersaMax GFK-1551D quick start guide

DW VMAX IP G4 DW-VG494P user manual

DW

DW VMAX IP G4 DW-VG494P user manual

Dahua DHI-NVR5208-8P-4KS2 user manual

Dahua

Dahua DHI-NVR5208-8P-4KS2 user manual

EMC B Series Hardware reference manual

EMC

EMC B Series Hardware reference manual

Ovislink Air Live CoreNVR 9 Quick setup guide

Ovislink

Ovislink Air Live CoreNVR 9 Quick setup guide

Aethra AF3400 Technical specifications

Aethra

Aethra AF3400 Technical specifications

Klark Teknik DN9650 specification

Klark Teknik

Klark Teknik DN9650 specification

Bosch VIP X1600 M4S Installation and operating manual

Bosch

Bosch VIP X1600 M4S Installation and operating manual

Brocade Communications Systems Converged Enhanced Ethernet 8000 Administrator's guide

Brocade Communications Systems

Brocade Communications Systems Converged Enhanced Ethernet 8000 Administrator's guide

eks DL485-4W/2x manual

eks

eks DL485-4W/2x manual

Paradyne Hotwire 5620 installation instructions

Paradyne

Paradyne Hotwire 5620 installation instructions

Cisco ASR 5000 installation guide

Cisco

Cisco ASR 5000 installation guide

Cisco 3660 Series installation guide

Cisco

Cisco 3660 Series installation guide

Alvarion BreezeNET PRO.11 Series user guide

Alvarion

Alvarion BreezeNET PRO.11 Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.