
ON-BOARD
DIAGNOSTICS
1
PC
INTERFACE
SOFTWARE
Start offby collecting date from the time that the engine is
started.
If
you have a genset that has the idle mode, start the
PC
interface communicating and data logging before you
start the engine.
If
you have an engine that does not have an
idle mode, start the PC Interface as soon as possible after the
engine is running.
Let
the engine warm up for about 10 to
15
minutes before trying to apply an AC load. Monitor and
recordAC volts and amps
if
possible.
After the engine is warmed up, start applying an AC load by
turning
on
various devices.
Let
the unit run at each load
change for a couple
of
minutes so that the unit is stable.
Monitor and record
AC
volts and amps
if
possible at each
load site. Continue to as AC load until the unit is at or near
full power rating. Power is determined by multiplying the
AC voltage times the
AC
amperage. This will determine
if
the unit is overloaded
or
not.
After loading up the genset, begin to reduce the AC load. Let
the unit run at each load site for a couple
of
minutes to
stabilize. Continue to reduce the AC load and monitor
voltage and amperage until there is no AC load on genset.
This will give a technician a baseline
of
what is going on
when the engine is running under a controlled load condition.
Finally, after running the controlled baseline test, this might
sound strange,
but
sometimes the customer might know a
particular scenario that will cause a problem for the unit.
Sometimes
we
hear customers say that the unit runs fine for
awhile and when
my
air conditioner shuts off something
happens. Try repeating the scenario that the customer men-
tions. Always start
by
recording date from the start up for a
least a couple
of
minutes with no load on the generator to
get a starting point. Then continue to record data until the
problem shows up.
If
you have a unit with no idle mode, and the unit shut down
under some kind
of
fault, the date log will automatically stop
and save the file.
If
you have a unit with an idle mode, and
the unit was to shut downunder some kind
of
fault, you will
have to manually stop thedata log to save it.
Or
in the case
of
shutting
of
the
DC
circuit breaker, this will also cause the
data file to stop and save itself.
WHAT
TO
DO
WITH
THE
DATA
All
of
the data that is being recorded is also being displayed
on
the PC Interface in the various boxes. The following
information applies whether you are looking at the data file
after
it
has been recorded
or
watching it live in the PC
Interface. The data file can be opened in most spreadsheet
software such as Microsoft Excel.
Some
of
the data that is being collected is pretty much self
explanatory and simple to follow. For example, I think that
engine temp, air temp, oil pressure, and battery volts would
be easy to figure out. Some
of
the other items may be less
familiar.
6
Speed
Simple enough, this is the speed that the engine is running,
the genset is set up to operate at
60
Hz, then the engine needs
to run at 1800 rpm (belt driven units may be different).
If
the
unit is set up for 50
Hz
operation then the engine speed will
be 1500 rpm.
When a genset is governing properly, you should see read-
ings slightly above and below the desired speed. Even a well
tuned engine will vary a little. The point is you should see
readings above and below the desired speed.
If
you see speed
readings remain more than
20
rom above
or
below the
desired speed for a prolonged period
of
time, there could be a
problem, especially
if
this is noticed with no AC load
applied.
If
the speed is too high with no
AC
load applied, check the
data box labeled Stepper Pos. (steps). The throttle is con-
trolled by a stepper motor. Usually the step count for the
engine running with no
AC
load is typically in the 20-30
steps range. A couple
of
steps above or below this range
does not indicate a problem. However,
if
the step count is in
the single digit numbers
or
even showing a zero, the problem
maybe that the thrrottle body assembly may be out
of
calibration
or
not functioning properly. The stepper motor
can only go to a positioin that it thinks is zero.
If
the
calibratiortis off, the stepper cannot move the throttle closed
enough to slow the engine down. An engine that has this
problem will run at the proper speed once someAC load has
been added. However, when that load is dropped, the speed
will be too high, and in some cases may cause the engine to
over-speed and shut down.
If
the engine speed is too low with no
AC
load applied, there
is probably a totally different problem. Again, look at the
Stepper Position. Is the speed low but steps are high? This
would mean that the throttle is being opened to compensate
for loss
of
speed
but
the speed is not coming up. Check to
make sure that the fuel level is full in the fuel system and that
the fuel is good and the filters are clear. Bleed the fuel system
to remove any air. Check to make sure that the air intake
screens are clean. Check to make sure that thespark plugs
have not fouled.
If
t:pe
engine speed is okay when running with no AC load,
but once underway with someAC load being aplied the
speed drops and stays below the desired speed, first check the
AC power by multiplying the total
AC
amperage times the
AC volts to get the kilowatts.
If
this number is higher than
what the unit is rated for, then it is overloaded., Shut off
some
of
the devices until the speed returns to normal and
check the power again.
If
there is only a small AC load
applied and the speed cannot maintain, follow the same
suggestions from the previous paragraph.