Westlake Axiall Accu-Tab PowerBase 3140AT User manual

Accu-Tab®PowerBase®3140AT
by Axiall, a Westlake Company
Installation and Operating Instructions
Rev 03/29/19
The PowerBase®3140AT Chlorinator is
NSF® NSF/ANSI-Listed for pool applications.
ONLY Axiall Accu-Tab®Blue SI
Tablets for commercial pool applications
STD 50 are permitted for NSF installations.
Use of tablets will void NSF certification.
DANGER: DO NOT MIX CHEMICALS!
The PowerBase 3140AT chlorinator system is
designed for use with Axiall approved tablets only. Do
not use Cal-Hypo tablets with stabilized chlorine or
bromine products, or other sanitizing chemicals.
Fire or explosion could result.

2
Description
The Accu-Tab PowerBase 3140AT chlorination system incorporates a patented
Axiall chlorinator into a compact plug and play system. Included in the system is
an integrated, level controlled solution tank and a centrifugal pump. The flow
rate through the system is controlled by a manually adjusted valve located on
the discharge of the pump. The solution tank level is controlled by a float valve.
As solution is pulled from the tank, the float valve opens allowing water to flow to
the chlorinator, contacting the tablets, and then draining into the solution tank.
Overflow protection is standard. Two level switches in the top area of the
Solution Tank (4” apart) will flip a relay in the electrical box causing the pump to
turn on/off as needed.
The chlorination system is designed for use ONLY with Axiall Accu-TabBlue SI
tablets utilizing the Axiall erosion feeder technology that erodes only the bottom
layer of tablets on the sieve plate, while keeping tablets above the sieve plate dry
and ready for use. Tablets other than Axiall Accu-TabBlue SI tablets will have
different delivery rates, resulting in improper chlorine delivery.

3
Installation Instructions
1. Place the chlorination system in a location near the place of application.
2. Level the system. This is important for proper chlorine delivery.
3. Connect the inlet flow meter assembly to the solution tank. The parts were
shipped separately to prevent breakage in shipping.
4. Connect the inlet water supply with 2” PVC pipe or hose. Include an isolation
valve in the line.
5. Check pressure of inlet supply line. Float valve will leak through at pressure
exceeding 28 psi. If pressure exceeds 28 psi, a pressure regulator and/or
an inlet solenoid valve may be required.
6. Connect the discharge assembly to the pump using a section of 1-1/2” pipe.
(The parts were shipped loose to prevent breakage in shipment.)
7. Connect the discharge piping from the feeder to the chlorine application
point with 2” PVC pipe or hose. Include an isolation valve in the line.
8. Plug the power cord into a 120v receptacle.
9. If a chemical controller is utilized, plug the controller cord into the
controller’s 120v switched output.
NOTE: IF A HIGH PRESSURE WEBTROL PUMP IS ORDERED, A LARGER
CAPACITY PUMP CONTACTOR IS INSTALLED IN THE ELECTRICAL BOX
AND NO CORD/PLUG IS PROVIDED AS A 25 AMP CIRCUIT IS REQUIRED.

4
0
5
10
15
20
25
010 20 30 40 50 60
Chlorine Delivery (lbs/hr)
Flow Through Chlorinator (gpm)
NSF
®
Model 3140AT
Using Accu®-Tab Blue and Blue SI Tablets
For pool use only
Standard 50
PowrBase
3140
AT Syem
PowerBase
3140AT

5
Start Up
1. Close the discharge gate valve.
2. Open the feed and discharge isolation valves. Water will begin to fill the
solution tank.
3. When water stops flowing, switch the system “ON” using the chemical
controller. The pump will circulate water through the black tubing.
4. Check that the float valve is not leaking through on applications where the
inlet supply is greater than 25 psi.
5. Begin opening the discharge gate valve to start flow in and out of the system.
6. Determine the maximum inlet flow rate by continuing to open the discharge
gate valve in small increments. Remember to allow a few minutes each time
to allow the flow meter to stabilize. If pump loses prime, maximum inlet flow
has been exceeded. Shut down system for a few minutes (which will prime
the pump), close back on the discharge gate valve and restart the system.
Continue this process until the maximum inlet flow is determined.
7. Adjust flow through feeder using the discharge gate valve. The chlorine
delivery is determined by the flow rate through the chlorinator. Use the graph
above to determine proper flow rate. NOTE: After adjusting the discharge
valve, the flow meter will take a few moments to stabilize.
8. Check all piping for leaks.
Operation
1. Remove lid from chlorinator and fill with the appropriate amount of Accu-Tab
Blue SI tablets. Add no more than the amount of tablets that will be used
within one week.
2. Check pool water for desired chlorine level and adjust flow through chlorinator
as needed.
NOTE: When pool water circulation stops, flow to chlorinator will stop.
This will stop chlorine delivery.
WARNING: Overdosing of free chlorine can lead to bather irritation
(skin, eyes, nasal, etc.).
Adding Tablets
1. Tablets may be added while the system is running. Take care to protect eyes,
skin, clothing and other equipment from splashing. Do not inhale fumes.
2. Remove lid and add Accu-TabBlue SI tablets.
3. Replace lid.

6
Maintenance
Clean the Check Valve and Float Valve at least every 4-6 months, or as
needed, to remove scale or debris
Winterizing
1. Clean chlorination system following instructions below.
2. Close inlet isolation valve and operate pump until no more water can be
pumped out.
3. Shut system down and close the outlet isolation valve.
4. Siphon any remaining water from the solution tank.
5. Remove any debris from the chlorinator or solution tank.
6. Open the bottom drain on the pump.
7. Drain water from feed and discharge lines.
8. Make sure no water remains in the pump, chlorinator, pipe line, or solution
tank to prevent freezing over the winter.
System Cleaning
Over time the chlorination system may develop a build-up of scale. This
should be cleaned on a periodic basis, up to twice per year. If scale formation
is severe, more frequent cleanings may be necessary. Cleaning may be
accomplished by soaking the chlorinator with a dilute acid solution according
to the instructions below.
NOTE: Addition of muriatic acid may lower the pH of the pool water.
Preparation for cleaning
1. Prepare 2 gallons of muriatic acid.
2. Always use appropriate safety equipment while servicing the unit or handling
chemicals.
3. Clean the feeder in a well-ventilated area. Chlorine gas may be released
during the cleaning process!
Inlet/Outlet Bypass
To facilitate the cleaning process a Bypass may be installed between the inlet
and outlet lines to/from the chlorination system. Isolation valves at the re-
circulation line are required.
Bypass
Valve
PowerBase
System

7
Cleaning procedure
1. Turn system off.
2. Open lid and remove all tablets. Use proper protective equipment when
handling chemicals.
3. Switch system on to begin flushing the system.
4. Wash out the feeder with a hose to remove remnants of tablets and loosen
scale.
5. Operate system until normal solution tank level is achieved. Switch system
off.
6. Close inlet and outlet isolation valves and open inlet/outlet Bypass valve (if
installed).
7. Very carefully, pour the acid into the upper chlorinator to dissolve scale. It
may be necessary to pour directly on the inside walls to remove any scale
above the water level. Always add acid to water, never add water to acid.
8. Let soak for 30 minutes. As acid dissolves scale, carbon dioxide will be
released, and foaming will occur. If any tablets were left in the feeder,
chlorine gas may also be released.
9. Turn system on to start acid circulation through the black tubing. Circulate
for 10 minutes.
10. Open all valves to begin purging acid from system. Shut Bypass valve.
11. Wash the walls and sieve plate of the feeder with a hose to remove all acid
residue. Chlorine gas may be released if any acid remains in the system.
12. Allow feeder to flush water for 30 minutes.
13. Turn system off. System is ready for operation.
Troubleshooting
System overflows.
1. Debris in the float valve.
2. Debris in the check valve.
3. Float valve stuck in down position. Clean float valve. DO NOT use any
lubricant on the valve internals.
Pump will not run.
1. Check power supply and connections, and controller 110v signal.
2. Check for 110 voltage across terminals #2 and #5. If voltage present, wiring
or pump motor failure.
Pump loses prime (solution tank drains)
2. Maximum inlet flow exceeded. See Start-Up instructions—point #6.
Float Valve maintenance
If valve becomes clogged with debris on a continuing basis, add a second filter to
the inlet. Use the 60 mesh in the first filter then a 100 mesh in the second. The
100 mesh filter can be supplied by your specialist.

8
Chlorinator Top Orientation
Align the chlorinator top portion so that the pointer on the separation plate is
directly over the inlet –see photo below. This will prevent chlorine solution from
draining directly onto the float valve assembly.
I
nlet
2
”
O
utlet
1
½”
Outlet
2”
Inlet
2”
Pointer
Inlet (where flow
meter is attached)

9

10
PurAqua Part #: PAPP1500
Pump Frame: R48Y
Amp rating: 15 amps
Flow, gpm
Hayward Pump Performance

11
PowerBase Replacement Parts
PurAqua Part #
Axiall Part#
Hayward 1 ½ HP Pump
PAPP1500
9500080
Seal for Hayward Pump
SPX1250XZ2C
Webtrol 1 ½ HP Pump
PC150R
9500185 Option
Seal for Webtrol Pumps
70X130-M
Pump Contactor
WEG
9500145
1½” Inline Flow Meter
F-42050LN
9500002
Level Switch
M9710
9500084
1 ½” Discharge Swing Check Valve
S1720C-15
9500077
1 ½” Gate Valve
GVG-1500-S
9500006
2” Inlet Filter
2-60-F
9501015
Float Valve
Kerick 1-1/4”
9501071
Plunger and pin
Kerick 1-1/4”
9501072
6” Float Ball
9500038
R2-120
For other questions, contact Axiall Technical Service (855-934-3570) for assistance

12
CAL-HYPO COMMERCIAL SYSTEM LIMITED WARRANTY
Axiall, a Westlake Company ("Axiall") warrants (subject to the below conditions) only its title to
this water treatment system equipment (the "System") and that the System will be free of defects
in materials and workmanship for a period of eighteen (18) months from its original shipment
date.
THIS IS THE ONLY REPRESENTATION OR EXPRESS WARRANTY THAT AXIALL MAKES
AND ALL OTHER EXPRESS WARRANTIES UNDER STATUTE OR ARISING OTHERWISE IN
LAW FROM A COURSE OF DEALING OR USAGE OF TRADE WITH RESPECT TO THE
SYSTEM ARE DISCLAIMED. ANY IMPLIED WARRANTIES EXISTING AS A MATTER OF LAW
SHALL NOT EXCEED THE DURATION OF THIS LIMITED WARRANTY. IN THE EVENT THE
SYSTEM FAILS TO CONFORM TO THIS WARRANTY, AXIALL'S EXCLUSIVE OBLIGATION
AND YOUR EXCLUSIVE REMEDY SHALL BE LIMITED TO, AT AXIALL'S OPTION, THE
FURNISHING OF NEEDED REPLACEMENT PARTS OR THE FURNISHING OF A NEW
SYSTEM (BUT THIS DOES NOT INCLUDE INSTALLATION OR THE COSTS FOR
INSTALLATION). EXCEPT AS PROVIDED IN THE IMMEDIATELY PRECEDING SENTENCE,
IN NO EVENT WILL AXIALL BE LIABLE UNDER ANY THEORY OF RECOVERY (WHETHER
BASED ON NEGLIGENCE OF ANY KIND, STRICT LIABILITY OR TORT) FOR ANY DIRECT,
INDIRECT, SPECIAL, INCIDENTAL, PUNITIVE, OR CONSEQUENTIAL DAMAGES IN ANY
WAY RELATED TO ANY USE MADE OF THE SYSTEM.
Warranty Conditions. This Limited Warranty shall apply and be effective only if: (i) the System is
installed and operated and maintained in accordance with this manual and the instructions
accompanying the System; (ii) you, at your cost, promptly return the System or defective part to
such location as may be specified by Axiall; and, (iii) only Axiall’s Accu-Tab® Blue SI calcium
hypochlorite tablets are used in the System. If any of these conditions are not met, this Limited
Warranty will not apply and you acknowledge and agree that your purchase of the System will be
on an "AS-IS" basis without any warranty of any kind whatsoever having been provided by Axiall.
You assume all responsibility and risk and liability arising from: (i) the unloading, installation,
storage, handling and use of the System, including use thereof alone or in combination with other
materials; (ii) the improper functioning or failure of unloading, installation, transportation or
storage equipment you use, whether furnished or recommended by Axiall or not; and, (iii) the
failure to comply with laws, rules and regulations governing storage, unloading, installation,
handling, and use of the System. You will indemnify, hold harmless, and defend Axiall from and
against any claim, suit, damage, cost, expense, fine, liability, or cause of action whatsoever,
including reasonable attorney fees, on account of relating to, or arising out of the use,
possession, installation or resale of the System.
This Limited Warranty gives you specific rights, and you also may have other rights, which vary
from jurisdiction to jurisdiction. Some jurisdictions do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitations or exclusions may not apply to
you. Some jurisdictions do not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you.
Table of contents
Popular Water Dispenser manuals by other brands

JP Smart
JP Smart SM100 Operation manual

Elkay
Elkay EFA8 2J Series Installation, care & use manual

DS Services of America
DS Services of America Pure Water Dispenser 500 Series How to Clean

3M
3M Aqua-Pure CS Series Installation and operating instructions

Apec Water
Apec Water FUTURA Installation instructions & owner's manual

Whirlpool
Whirlpool Hot water dispenser Installation instructions and use and care guide