Electrical
requirements
Electrical ground is required on
this appliance.
Electric Shock Hazard
* Check with a qualified
electrician if you are in doubt as
to whether the appliance is
properly grounded. Improper
connection of the equipment-
grounding conductor line can
result in a risk of electrical shock.
. Do Not use an extension cord
with this appliance. Such use
may result in a fire, electrical
shock or other personal injury.
- Do Not have a fuse in the neutral
or ground circuit. A fuse in the
neutral or ground circuit could
result in an electrical shock
hazard.
I
Save Installation Instructions for the
local electrical insDector’s use. I
A
This appliance must be
. connected to the proper
electrical voltage and frequency as
specified on the serial/rating plate.
Models rated at 7.0 kw on 240 volts
(5.3 kw on 208 volts) or more require a
separate do-ampere circuit. Models
rated at 3.6 kw on 240 volts (2.7 kw on
208 volts) or less require a separate
30.ampere circuit. Fuse both sides of
the line. A time-delay fuse or circuit
breaker is recommended.
B
OVEN MUST BECONNECTED
. WITH COPPER WIRE ONLY.
C
Wire sizes must conform to
. the requirements of the
National Electrical Code, ANSI/NFPA
7Glatest edition*, and all local codes
and ordinances for the kilowatt rating
of the oven. This rating can be found
on the serial/rating plate behind the
oven door on the front frame.
D
This appliance should be
n
connected to the fused
disconnect (or circuit breaker) box
through flexible armored or
non-metallic. sheathed copper cable
(with grounding wire). The flexible
armored cable extending from the
appliance should be connected
directly to the junction box.
E
Locate the junction box to
allow as much slack in the
cabye as possible between the
junction box and the appliance so
that the oven can be moved if
servicing is ever needed.
F
A U.L.-listed conduit connector
must be provided at the
n
junction box.
G
It is the personal responsibility
n
and obligation of the
customer to contact a qualified
electrician to assure that the electrical
installation is adequate and is in
conformance with the National
Electrical Code ANSI/NFPA 70.latest
edition’, and all local codes and
ordinances,
Copier of lhe standard llsled may be oblained
from: ‘NatIonal Fire Protection Association
Ba+lery March Park.
Qulncy. Massachus&s 02269
H
A wiring diagram is included in
n
the Tech sheet. The Tech
sheet is located behind the control
panel.
PANELC
Electrical
connection
Electric,at ground is required on
this appliance.
Electrical Shock Hazard
- Do Not connect appliance to
electrical supply until appliance
is permanently grounded.
- Disconnect power to the
junction box before making the
electrical connection.
l
This appliance must to
connected to a grounded,
metallic, permanent wiring
system, or a grounding
conductor should be connected
to the grounding terminal of lead
on the appliance.
Failure to follow these instructions
could result in a fire, personal
injury, or electrical shock.
This appliance is manufactured with
white (neutral) power supply wire and
a frame-connected, green grounding
wire.
Connect the appliance cable to the
junction box through the U,L.-listed
conduit connector. Complete
electrical connection according to
your installation needs.
A. Where local codes
permit...
connecting the frame-grounding
conductor to the neutral (white)
junction box wire:
Cable from
power WPPlY
Cable
from OVB”
Figure 1
1. Turn power supply off
2. Connect three wires: green and
white appliance cable wires with the
neutral (white) wire in junction box.
3. Connect the two black wires; then
the two red wires. (See Figure 1.)
B. Where local codes
DO NOT permit...
connecting the frame-grounding
conductor to the neutral (white)
junction box wire:
Cable lrom
from awn
Figure 2
I. Turn power supply off.
2. Connect the white appliance
cable wire to the neutral (white) wire
in junction box.
3. Connect the two black wires; then
the two red wires. Gee Figure 2.)
4. Connect the grounding wire to a
grounded wire in the junction box or
to a grounded, copper cold water
pipe.”
Figure 3
5. A separate copper grounding wire
(No. 10 minimum) MUST be connected
to a grounded cold water pipe by
means of a clamp and then to the
external grounding connector screw.
Do Not ground to a gas supply pipe
or hot waler pipe. Do Not connect
to electrical supply until appliance is
permanently grounded. (See
Figure 3.)
” Grounded cold water pipe must hove metal
conilnuity to electrical ground and not be
interrupted by plastic. rubber or other
electrIcal insulating connectors such OS
hoses. fittings. washers or Qaskets (including
water meter or pump). Any electrical
insulating connector should be jumped OS
shown with calength of No.-4 copper wire
securely clamped +o bare metal at both
ends,
C. IF connecting to a
four-wire electrical
system...
DO NOT connect the frame-grounding
conductor to the neutral (white)
junctlon box wire.
ack
ires
Cable
rr0m 0~en
Figure 4
Conduit
connechx
1. Turn power supply off
2. Separate the green and white
appliance cable wires.
3. Connect the white appliance
cable wire to the neutral (white) wire
in junction box.
4. Connect the two black wires; then
the two red wires. (See Figure 4.)
5. Connect the green appliance
cable wire to green grounding wire in
the junction box.