4
Heating System
1. Move SYSTEM switch to HEAT position
2. Press toadjustthermostatsettingto90°andholdforfive
seconds. Both stages of the heating system should begin to
operate. However, if the word HEAT is flashing, the com-
pressor lockout feature is operating (see Lockout Bypass
Option to temporarily override the compressor lockout fea-
ture during testing).
3. Press toadjusttemperaturesettingbelowroomtempera-
ture. The auxiliary heating system will stop immediately and
the first stage will stop within three to four minutes.
Cooling System
Topreventcompressorand/orpropertydamage,ifthe
outdoor temperature is below 50°F, DO NOT operate
the cooling system.
1. Move SYSTEM switch to COOL position.
2. Press to adjust thermostat setting below room tempera-
ture.Theblowershouldcomeonimmediatelyonhighspeed,
followedbycoldaircirculation.However,ifthefanisrunning
but the compressor is not running and the word COOL is
flashing, the compressor lockout feature is operating (see
Lockout Bypass Option to temporarily override the com-
pressor lockout feature during testing).
3. Press to adjust temperature setting above room tem-
perature. The cooling system should stop operating
O/B TERMINAL SWITCH SELECTION
The O/B switch on this thermostat is factory set to the “O”
position. This will accommodate the majority of heat pump
applications, which require the changeover relay to be ener-
gized in COOL. If the thermostat you are replacing or the heat
pump being installed with this thermostat requires a “B” termi-
nal,to energizethe changeoverrelay inHEAT,the O/Bswitch
must be moved to the “B” position.
ARMCHAIR PROGRAMMING
Armchair Programming is a unique feature that allows your
thermostattobeprogrammedbeforebeingmountedonthewall.
If you do not want to Armchair Program, the thermostat can be
programmedafterbeingmountedonthewallandsystempower
turned on.
If you wish to Armchair Program your thermostat, temporarily
holdanew9-voltbattery againstthe wiresinthe batterycutout
on the back of the thermostat base for approximately 45
seconds.Thiswill provide achargethat will lastapproximately
30 to 45 minutes to allow the thermostat to be programmed.
After programming, the thermostat must be mounted on the
wall, wires connected and system power turned on.
To have sufficient time to complete the installation without
losingtheprogramming,holdthe9-voltbatterytotheterminals
on the back of the base for 30 to 45 seconds again after
programming the thermostat. The battery must be removed
before mounting the thermostat on the wall.
ADJUSTABLE ANTICIPATION
Thefirst stage hasanticipationthatcanbe setto2.5or4 cycles
per hour for heating or cooling. The second stage heat has a
fixed anticipation. To change the first stage anticipation in the
HEAT or COOL mode, press SET TIME and VIEW PRGM
buttons at the same time until the desired setting is displayed
(Sfor slow (factory setting) or Ffor fast).
CHECK THERMOSTAT OPERATION
If at any time during testing, your system does not operate
properly, contact a qualified serviceperson.
Fan Operation
1. Turn on power to the system.
2. Move SYSTEM switch to OFF position.
3. MoveFANswitchtoON.Theblowershouldbegintooperate.
4. MoveFANswitchto AUTOposition. Theblowershould stop
within a short period of time.
NOTE
CAUTION
!
LOCKOUT BYPASS OPTION
FOR QUALIFIED SERVICE TECHNICIANS’ USE
ONLY.OPERATORSSHOULDNOTUSETHISFEA-
TURE DUE TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL INJURY.
COMPRESSOR SHORT TERM
CYCLE PROTECTION
This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature
while testing thermostat operation, simply press
and buttons at the same time.
DO NOT USE THE LOCKOUT BYPASS OPTION
UNLESSTHECOMPRESSOROILHEATERSHAVE
BEEN OPERATIONAL FOR 6 HOURS AND THE
SYSTEMHASNOT BEENOPERATIONALFORAT
LEAST 5 MINUTES.