
15 OPM-161/A
PROTECTIONS
When an alarm is present, the common alarm LED, if
configured, will illuminate. The LCD display will show an
icon to indicate the failure.
WARNINGS
Warnings are non-critical alarm conditions. They do not
affect the operation of the generator system, they
serve to draw the operator’s attention to an undesirable
condition. Warning alarms are self-resetting when the
fault condition is removed. The icon will appear steady in
the display.
SHUTDOWN
Shutdowns are critical alarm conditions that stop the
engine and draw the operator’s attention to an
undesirable condition. Shutdown alarms are latching.
The fault must be removed and the STOP/RESET button
pressed to reset the module. The icon will be flashing in
the display.
AUTO MODE
To activate the automatic start mode you will just need to
depress the AUTO button, the LED indicator beside the
button confirms that the unit is in automatic mode.
To test the Automatic Transfer Switch, follow the instruction
on the operator’s manual that came with the transfer
switch. If you get a fault during the initial start up or prior
to start up, it is most likely a false warning light. Simply reset
the ATS to start over.
Once you have completed testing of the ATS, be sure you
ALWAYS leave the system in the standby mode,unless
servicing the unit. For standby operation, press the AUTO
button on the front of the control. The green light should
light up next to the AUTO button.
NOTE: For setting the exerciser circuit, for all ATS, see the
operator’s manual shipped with the ATS.
MANUAL MODE
1. Press and release the MANUAL MODE button. The small
LED light next to it should come on.
Note: There is no start delay in this mode of operation.
2. Press and release the green START ENGINE button. The
DSE 7310 will send two signals to the engine. The first
signal wire #21 will engage the fuel solenoid, the second
wire, #22, will engage the starter on the engine. At this
point the DSE 7310 will start the cranking cycle (10
seconds on and 10 seconds off).
Note: Wire #93 is energized to turn on the glow plugs for
15 seconds first and then the starter and fuel solenoid are
engaged.
If the engine fails to start during this cranking period, the
starter motor is disengaged and goes into a rest mode
after which a second attempt is made to start the engine.
Should this sequence continue through 3 cranking cycles
the start sequence will be stopped and the display will
show ‘FAILED TO START’.
3. During manual operation, the load will not normally be
applied to the generator. But caution must be used, if the
line power should fail or be turned off the transfer switch
during manual operation the load may be applied to the
generator.
With the engine running smoothly check the no load
voltage and frequency on the digital display. The voltage
should match the nameplate and a frequency of 59.5 to
60.5 hertz (Hz).
If you have the proper voltage at the generator the next
step is to check the voltage at the generator terminals
in the Automatic Transfer Switch. The voltage between
the G1 and the G3 terminals should be the same as it
was on the generator front panel. The voltage should
also be checked between the hot terminals (G1 and G3)
and the G-N to be certain of a balanced voltage output
and a solid neutral connection. The voltage between G1
and G-N should be about 120 volts AC (277 on 480
units). The same approximate voltage should be found
between terminals G3 and G-N (120 volts AC).
On three phase panels the G2 voltage level should also
be checked. ON 240 VOLT (DELTA) SYSTEMS BE SURE
YOU KNOW WHERE THE HIGH VOLTAGE “WILD” LEG IS.
IT MUST BE IN THE SAME LOCATION ON THE LINE SIDE
AS IT IS ON THE GENERATOR SIDE. (i.e. if it’s on L-3 on
the line side it must be on G-3 on the generator side. Also
on three phase systems make sure that the rotation is the
same on the generator as it is on your line power. Failure
to insure proper rotation will cause three phase motors to
spin backwards possibly damaging them.
NOTICE: If for any reason during the check out procedure
the voltage and frequency are not correct, depress the
STOP/RESET button and correct the trouble before
proceeding.
4. Stopping - There are two ways to stop the unit when it is
in the manual mode. Pressing the STOP/RESET button will
stop the unit immediately. Pressing the AUTO mode
button will stop the unit but only after the cool down
timers have timed out and there is no remote start signal
being sent to the unit.
WARNING: EQUIPMENT DAMAGE
Always make sure the generator runs under no load for
five minutes before stopping to allow the engine and
components to cool down. Don’t use the E-Stop to shut
down the generator unless there is an emergency.
CONTROL POWER
The DSE7310 controller consumes small amounts of battery
power when it is in use. The controller comes with a power
switch that disconnects battery power when it is not in use.
The switch is designed with a safety relay that prevents it
from removing power to the controller while the generator
is operating. If the switch is turned off while the engine is
running it will continue operating until the engine shuts
down and then the controller will power down.
This switch should be used when the generator is not
going to be used over the course of several days and the
generator is not connected to a battery charger.