Wind Crest SA1000 User manual

Windcrest
SA1000 Autodialler System
(Can be used to upgrade an AD1000EN-1R)
Windcrest
Tel: 0208 795 0333
Fax: 0208 795 0444
Page 1/5
Mains
Phone Line or GSM
Lift Car
Windcrest
PRESS BUTTON FOR
3 SECONDS, IF
UNOBTAINABLE,
PRESS BUTTON
AGAIN
Battery Backed
Power Supply

Windcrest
PRO RAM MER
YES
123
45 6
7 8 9 0
#
NO
CANCEL
ENTERTEST
CHECK
SET RESET
Volume
HL
Voice
Switching
Windcrest
Connections
Connect Mains via the 3 way connectors Use Cable Ties to secure the wires together and ensure no wire “whiskers”
Connect the wires to the Autodialler Main Unit and then connect the Battery
NB: The Power supply unit has been designed to supply power only for the Autodialler and no extra power is available for additional equipment
Over loading may damage the power supply
Remove
Screws
ELN
Battery Check +Ve Supply
0V Return
To Autodialler
Main Unit
Mains Supply
Fused 2A
LV
+
0V
12v Battery
Connection
2 off 12V
Batteries
MAINS
HIGH
VOLTAGE
Test
Programming
Keypad on the
back of the unit
SA100 Power Supply
Windcrest
Tel: 0208 795 0333
Fax: 0208 795 0444
Page 2/5
SA1000 System with built in Push button
280mm
40.0mm
MAX
110mm
Windcrest
PRESS BUTTON FOR
3 SECONDS, IF
UNOBTAINABLE,
PRESS BUTTON
AGAIN
Surface Mounted
Unit
290mm
40mm
3mm
110mm
Windcrest
270mm
PRESS BUTTON FOR 3
SECONDS, IF
UNOBTAINABLE,
PRESS BUTTON
AGAIN
lush Mounted
Unit

Windcrest
Tel: 0208 795 0333
Fax: 0208 795 0444
SA1000 connections
Drawing: SA1K Connections
Date: 03/09/17
Connect all the wires of the RJ45 Cable as er the above and then lug into the SA1000 Unit.
Note:- The RJ45 Cable is supplied with the unit. However, if any other RJ45 cable to be used for the SA1000 unit, the plug must
be made as per the above drawing. Incorrectly made plug will result in damaging of the unit and will violate warranty terms.
31 52 4 6 7 8
WRON
Orientation of the RJ45 Plug
Single Wire Colours Connections
1. Orange/White……….Not Used
2. Orange……………….Low Battery Signal from
Windcrest PSU (LV) or see below
3. reen/White ………..”+” on Windcrest PSU
4. Blue…………………..BT/Telephone Line
5. Blue/White…………...BT/Telephone Line
6. reen…………………”0V” on Windcrest PSU
7. Brown/White………… ”+” on Windcrest PSU
8. Brown…………………”0V” on Windcrest PSU
Analogue Telephone
Network
Low Battery Signal:-
If the Windcrest PSU is not used, a set of voltage free contacts will be required to indicate battery status
to the SA1000 unit. If the battery is good (adequate ca acity in accordance to EN 81-28 ), these contacts
will need to be “CLOSED” and if the battery is low, these contacts will need to be “OPEN”. If the
contacts are not rovided the unit will assume as the battery is low. The battery indicator voltage free
contacts to be connected across 2. Orange & 7. Brown/White.
Page 3/5
Not used wires must be isolated from other wires. If it
shorts out with any of other wire, this may result in
damage of the unit.

Programming Via Keypad
Press *1234# on the keypad (on back of the unit) and the unit will give two bleeps to
confirm it is in the programming mode.
Following are the programming parameters strings. At the end of each string, the unit will
announce the complete string to confirm the programmed parameter.
Programming strings:-
1st Telephone Number *11#Number##
2nd Telephone Number *12#Number##
3rd Telephone Number *13#Number##
4th Telephone Number *14#Number##
5th Telephone Number *15#Number##
Contract Number *16#Number##
Windcrest ID Code *17# Unit will announce the ID Code
Test Calls (Help Point) *20#N## N = 0 to Turn OFF
N = 1 to Turn ON.
Auto Jump *21#N## N = 0 to Turn OFF
N = 1 to Turn ON.
SP Bit 1 *22#N## N = 0 to Turn OFF
N = 1 to Turn ON.
HOT LINE *23#N## N = 0 to Turn OFF
(Automatic dialling by telephone line) N = 1 to Turn ON.
Voice ID (Help Point) *24#N## N = 0 to Turn OFF
N = 1 to Turn ON.
Instant Trigger *25#N## N = 0 for 3 Secs Trigger Delay
N = 1 for Instant Trigger
Identification Message *26#N## N = 0 for Contract Number
N = 1 for User Recorded Msg.
SP Bit 3 *27#N## N = 0 to Turn OFF
N = 1 to Turn ON.
SP Bit 4 *28#N## N = 0 for Computer Based
Test calls
N = 1 for Manned Test Calls
Call Duration *30#N## N = 1 to 9
Test Call Frequency (Hrs) *40#NN## NN = 01 to 99 Hours
Unit Number *41#NN## NN = 00 , 01 , 02 , 03 ,04 ,05 ,
06, 07, 08, 09,
For Alphabets
A=10, B = 11, ….Z=35
RPA Number *98#NNNN# NNNN = 4 digit Remote Programming Access Code
(Remote Programming Access Code – This can only be programmed by Keypad)
To Record *51# Start Recording after the Beep
Tone by speaking into the Main Autodialler unit.
A Beep will be heard at the end of the Recording duration (10 Secs) and the recorded message will be played.
To Play Recorded Message *50#
To end the Programming *00#. Unit will give two beeps.
Page 4/5

Remote Programming of the SA1000 unit
The autodialler has the facility to auto-answer an incoming call, after 6-15 seconds.
Once the call has been answered, the programming mode can be instigated by a series of simple
commands via a simple Touch-Tone Telephone or a Mobile Phone.
The programming is by means of using the (DTMF) Touch-Tones from the calling telephone or a
management computer based system into the Lift car.
To enter into the Remote Programming Mode, a Remote Programming Access (RPA) Number,“v..vv#”
within a time period of 30 seconds. (v is any digit 0 to 9). The Default is 1234.
If the RPA is incorrect the system will go in the normal auto-answer.
If the RPA number is correct, the system will output two short Beep tones and wait for additional
command tones for a period of 30 seconds before exiting and going in the normal auto-answer mode, i.e.
line being connected to the speaker box, after the emission of a short tone.
Exiting from the programming mode is by either a command code sequence, or no activity for 30seconds
whilst in the programming mode. (Note, when entering the remote programming mode, the call duration
time period is suspended; and re-established when existing from the programming mode).
The following can be implemented once in the programming mode.
00# Terminate Programming Mode
vv Announce the Programmed number e.g. if 15 is entered; the system will produce “Beep 15
Beep 5627899 Beep” if the Phone number of the 5th number was 5627899.
Sequence of Events
1. Call the Unit using a simple phone. The call will be Auto-answered and you will be connected to the
Speaker.
2. Inform the person if in the area of the Unit that you are about to update the Emergency Telephone.
3. Key in the Remote Programming Access Number.
So key on your telephone 1234# The unit will respond by two beeps.
4. Program the parameters by keying in the strings as mentioned in the programming by Keypad section.
Note that RPA code cannot be programmed remotely.
5. Enter 00# to end remote programming.
Page 5/5