WindowMaster WLA 330 User manual

DK +45 4567 0300 [email protected]
UK +44 (0) 1536 614 070 [email protected]
DE +49 (0) 40 87 409 -560 Vertrieb / -484 Technik info.d[email protected]
CH +41 (0) 62 289 22 22 [email protected]om
NO +47 33 99 71 00 [email protected]om
US +1 650 360 5414 [email protected]
WLA 330 install 2011-UK ©WindowMaster 2005, 2020 ®WindowMaster is a registered trademark used under licence by WindowMaster International A/S
WindowMaster International A/S, Skelstedet 13, DK-2950 Vedbæk
Mitgliedim
Fachkreis
elektrom otoris ch
betriebene
Rauch- und Wärme-
abzugsanlagen
WLA 330
Wind/Rain sensor

2
Important information
▪Read instructions carefully before installation. Keep the instructions for future reference.
▪Sensor WLA 330 should be installed in accordance with current national legislation.
▪Disconnect from mains supply before installation or removal of the sensor and before carrying out any maintenance or service work
and ensure that it cannot be reconnected unintentionally during this time.
▪If the sensor gets activated, the window operator automatically closes the window. For personal safety, never have your hand or body
out of the window without disconnecting from mains supply.
▪Do not paint or lacquer the rain sensor.
▪Dirt on the sensor may cause operating problems. Therefore, it is recommended to clean the rain sensor with a soft wet cloth once or
twice a year or when required.
▪Electrical products must be disposed of in conformity with national regulations for electronic waste and not with usual household
waste.
▪The packaging can be disposed of with usual household waste.
▪WLA 330 is a low-voltage product that complies with the requirements of the EMC directive concerning use in household, trade and
light industry.
▪This product has been designed for use with genuine WindowMaster products. Connection to other products may cause damage or
malfunction.
Description
The wind/rain sensor comprises a wind wheel and a rain sensor surface.
This sensor is used for the automatic control of Smoke Control Units and ventilation central units.
The wind/rain sensor is equipped with a potential free change-over contact
having a contact rating of 60V/2A.
In the event of wind and/or rain, the change-over contact switches over from the N/C contact
to the N/O contact.
The settings for the wind trigger threshold, the actuation delay, the drop out delay
and the trip in the event of a mains failure are made by a 6 pole DIP switch in the sensor.
Operation / Function
Triggering by wind
The potential free contact switches when the (settable) wind sensor trips.
The red LED in the sensor is lit.
Remark:
The trip is reset 10 or 20 min. (settable) after the last sensor actuation.
Beaufort table:
Wind force in
Beaufort
Speed in m/s
Speed
in km/h
Wind intensity
Effects
0
0 –0,2
< 1
calm
smoke rises straight
1
0,3 –1,5
1 –5
light air
only noticeable from the smoke
2
1,6 –3,3
6 –11
light breeze
noticeable on the face
3
3,4 –5,4
12 –19
gentle breeze
thin twigs are moved
4
5,5 –7,9
20 –28
moderate breeze
thin branches are moved
5
8 –10,7
29 –38
fresh breeze
small trees sway
6
10,8 –13,8
39 –49
strong breeze
thick branches are moved
7
13,9 –17,1
50 –61
moderate gale
entire trees are in motion
8
17,2 –20,7
62 –74
fresh gale
Branches break off trees
9
20,8 –24,4
75 –88
strong gale
minor damage to houses
10
24,5 –28,4
89 –102
whole gale
trees blown over
11
28,5 –32,6
103 –117
storm
severe storm damage
12
> 32,6
> 117
hurricane
Triggering by rain
The potential free contact switches when the rain sensor trips.
The red LED in the sensor is lit.
Remark:
The trip is reset 10 or 20 min. (settable) after the last sensor actuation.

Operating/control and display elements

Connection to control units
WCC 103 / 103 BT
WCC 106 BT
WCC 3x0 Standard

WCC 3x0 Plus
DIP switches
Various wind/rain parameters and operating modes can be set by means of the installed DIP switches.
DIP switch settings for the wind speed
Test
Approx
.3 m/s
Approx
4 m/s
Approx
6 m/s
Approx
8 m/s
Approx
10 m/s
Approx
12 m/s
Approx
14 m/s
Switch 1
off
on
off
on
off
on
off
on
Switch 2
off
off
on
on
off
off
on
on
Switch 3
off
off
off
off
on
on
on
on
Note
Factory setting = operation, meaning switch 1, 2, 3 and 6 = on and switch 4 and 5 = off.
Should there during installation be the need to disconnect the wind/rain drop out delay, set switch 1+2+3 = off (= Test).
Important! Once installation and star-up are completed, proceed with the wind speed setting required on site, meaning one or more of
the switches 1,2 or 3 MUST be on!
Remark: In the test setting, the activation and drop out delay is deactivated!
DIP switch settings
Switch setting OFF
Switch setting ON
Switch 4 = Wind activation delay
2 seconds
5 seconds
Switch 5 = Wind/rain drop out delay
10 minutes
20 minutes
Switch 6 = Monitoring
off
on
Information regarding switch 6:
Only the supply voltage (terminals 1+2) for the sensor is monitored.
The system will trip automatically in the event of a supply voltage failure.
Display: Red steady light in the sensor LED = Sensor tripped by wind or rain.
Connection
Terminal 1 = Operating voltage AC/DC
Terminal 2 = Operating voltage AC/DC
Terminal 3 = Relay (arm)
Terminal 4 = Relay (N/C contact)
Terminal 5 = Relay (N/O contact)

Technical data
Supply voltage: 18V to 26V AC or 20V to 32V DC
Circuit output: 1 x potential free change-over contact
Switching capacity: 60V / 2A
Sensor dimensions: 80 x 160 x 55mm (WxHxD / without wind wheel)
Sensor weight: approx. 0.7kg
Sensor protection type: IP65
Setting of the wind mode: approx. 3 to 14 m/s (±20%)
Setting of the wind/rain drop out delay: 10 min. / 20 min.
Setting of the wind actuation delay: 2 s / 5 s
Setting of the monitoring: Off / On
CE sign in accordance with the EMC directive and the low voltage directive
Cleaning clean the sensor regularly depending on the degree of soiling.
This manual suits for next models
1