2. Technical Parameters
Input voltage: 90V-265VAC, 47-63Hz
Output voltage: DC12V-DC15V adjustable
Output current: 5A
Unlock delay time: 0-45s
Battery supported: 12V7Ah Lead-acid battery
Working humidity: <95%
Working temperature: -20~50 ℃
3. Connection Diagram
1 +12V & GND: Output + & -, connect Main controller
2A PUSH(+) & GND: Active High, Connect Door Exit Button
2B PUSH(-): Active Low, connect Door Exit Button
3A NO(+) & GND: Normally Open, connect Electric lock
3B NC(-) & GND:Normally Close, connect Magnetic lock
4 :Connect Intercom system or Alarm system
5 Battery + & Battery -: Connect
Lead-acid battery
PS: Terminal 6, 7, 8 are interchangeable.
4.
Installation Attention:
1) DO NOT operate when AC in, all connecting operation must before connecting AC input. Wet hand operation
NOT allowed.
2) The product should be installed indoor where is dry and well ventilated, without direct sunlight.
3) Please make sure all connection wire are correctly linked before using, especially the Positive(+) and negative(-)
of battery connection.
4) Before connecting Electronic Lock, please turn the Time delay button to 0s to avoid burn lock coil.
5) Lock over 500mA is not suggested to be connected directly to the power supply to ensure stable function.
6) After AC connected, RED and GREEN LED indicator should be light. If not, please check if AC socket under
poor contact or input fuse was burned.
7) When AC input cut off, YELLOW and GREEN LED indicator should be light. If not, please check if fuse was
burned or battery connecting wire fell off, or battery capacity lower than 10V.