2
SAFETY INSTRUCTIONS
TO AVOID SERIOUS OR FATAL PERSONAL INJURY
OR MAJOR PROPERTY DAMAGE, READ AND
FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL
AND ON EQUIPMENT.
THIS MANUAL IS INTENDED TO ASSIST IN THE
INSTALLATION AND OPERATION OF THIS UNIT
AND MUST BE KEPT WITH THE UNIT.
This is a SAFETY ALERT SYMBOL.
When you see this symbol on the
pump, the controller or in the manual,
look for one of the following signal
words and be alert to the potential for
personal injury or property damage.
Warns of hazards that WILL cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
personal injury or property damage.
NOTICE: INDICATES SPECIAL
INSTRUCTIONS WHICH ARE
VERY IMPORTANT AND MUST BE
FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS AND
WARNINGS PRIOR TO PERFORMING ANY WORK
ON THIS CONTROLLER.
MAINTAIN ALL SAFETY DECALS.
Disconnect and lockout electrical power
before installing or servicing any
electrical equipment.
ELECTROCUTION HAZARD.
CONTROLLER INPUT GROUND
TERMINAL (GND) AND ALL EXPOSED METAL
PIPING, INCLUDING PRESSURE TRANSDUCER
CASE, MUST BE CONNECTED TO THE SERVICE
ENTRANCE GROUND TERMINAL.
All electrical work must be performed
by a qualied technician. Always follow
the National Electrical Code (NEC), or the Canadian
Electrical Code, as well as all local, state and provincial
codes. Code questions should be directed to your
local electrical inspector. Failure to follow electrical
codes and OSHA safety standards may result in
personal injury or equipment damage. Failure to
follow manufacturer’s installation instructions may
result in electrical shock, re hazard, personal injury
or death, damaged equipment, unsatisfactory
performance, and may void manufacturer’s warranty.
5VDC MOISTURE SENSOR RELAY
INSTALLATION INSTRUCTIONS
The Sensor can detect the presence of water and
provide a relay output for signal or control of an
external device. The switch operates on voltage DC
and functions as a Normally Closed Sensor, for a
Closed Loop system. The Red and Black wires power
the switch while the White and Green wires are the
relay output wires.
SPECIFICATIONS
Power Requirements: 9K585 9K584 9K583
Operating Voltage 5 Volts DC 12 Volts DC 24 Volts DC
Operating Current 10 mA 10 mA 10 mA
Contact Characteristics:
Contact Resistance 100 mΩ 100 mΩ 100 mΩ
Switching Voltage 30 Volts DC Max 30 Volts DC Max 30 Volts DC Max
Switching Current 500 mA Max 500 mA Max 500 mA Max
Power 250 mW Max 250 mW Max 250 mW Max
Wire Connections:
Red 5 Volts DC 12 Volts DC 24 Volts DC
Black - Ground - Ground - Ground
Green Relay Contact Relay Contact Relay Contact
White Relay Contact Relay Contact Relay Contact
For installation to an alarm panel, the Red wire is
connected to the positive side of a voltage supply
and the Black wire is connected to the negative.
The Green and White wires can then be connected
to any pre-selected Closed Loop zone. A resistor
can be connected in series with either the Green or
White wire for those panels that require end-of-line
resistance.
After installation these units should be tested with a
damp sponge or paper towel and inspected annually.
If there is any corrosion or damage the sensor should
be replaced.