Xylem CentriPro 9K585 User manual

Moisture Sensor Relay
• Connections to Aquavar SOLO and SOLO2• Connections to S-Drive and SPD
• Connections to Aquavar AB2 (AquaBoost II) • Connections to e-SM Smart Motor
• Connections to Aquavar IPC • Connections to Hydrovar
INSTALLATION AND OPERATION MANUAL FOR 9K583, 9K584, AND 9K585
INSTRUCTION MANUAL
IM234R03

2
SAFETY INSTRUCTIONS
TO AVOID SERIOUS OR FATAL PERSONAL INJURY
OR MAJOR PROPERTY DAMAGE, READ AND
FOLLOW ALL SAFETY INSTRUCTIONS IN MANUAL
AND ON EQUIPMENT.
THIS MANUAL IS INTENDED TO ASSIST IN THE
INSTALLATION AND OPERATION OF THIS UNIT
AND MUST BE KEPT WITH THE UNIT.
This is a SAFETY ALERT SYMBOL.
When you see this symbol on the
pump, the controller or in the manual,
look for one of the following signal
words and be alert to the potential for
personal injury or property damage.
Warns of hazards that WILL cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
serious personal injury, death or major
property damage.
Warns of hazards that CAN cause
personal injury or property damage.
NOTICE: INDICATES SPECIAL
INSTRUCTIONS WHICH ARE
VERY IMPORTANT AND MUST BE
FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS AND
WARNINGS PRIOR TO PERFORMING ANY WORK
ON THIS CONTROLLER.
MAINTAIN ALL SAFETY DECALS.
DANGER
WARNING
CAUTION
Disconnect and lockout electrical power
before installing or servicing any
electrical equipment.
ELECTROCUTION HAZARD.
CONTROLLER INPUT GROUND
TERMINAL (GND) AND ALL EXPOSED METAL
PIPING, INCLUDING PRESSURE TRANSDUCER
CASE, MUST BE CONNECTED TO THE SERVICE
ENTRANCE GROUND TERMINAL.
All electrical work must be performed
by a qualied technician. Always follow
the National Electrical Code (NEC), or the Canadian
Electrical Code, as well as all local, state and provincial
codes. Code questions should be directed to your
local electrical inspector. Failure to follow electrical
codes and OSHA safety standards may result in
personal injury or equipment damage. Failure to
follow manufacturer’s installation instructions may
result in electrical shock, re hazard, personal injury
or death, damaged equipment, unsatisfactory
performance, and may void manufacturer’s warranty.
WARNING
WARNING
WARNING
5VDC MOISTURE SENSOR RELAY
INSTALLATION INSTRUCTIONS
The Sensor can detect the presence of water and
provide a relay output for signal or control of an
external device. The switch operates on voltage DC
and functions as a Normally Closed Sensor, for a
Closed Loop system. The Red and Black wires power
the switch while the White and Green wires are the
relay output wires.
SPECIFICATIONS
Power Requirements: 9K585 9K584 9K583
Operating Voltage 5 Volts DC 12 Volts DC 24 Volts DC
Operating Current 10 mA 10 mA 10 mA
Contact Characteristics:
Contact Resistance 100 mΩ 100 mΩ 100 mΩ
Switching Voltage 30 Volts DC Max 30 Volts DC Max 30 Volts DC Max
Switching Current 500 mA Max 500 mA Max 500 mA Max
Power 250 mW Max 250 mW Max 250 mW Max
Wire Connections:
Red 5 Volts DC 12 Volts DC 24 Volts DC
Black - Ground - Ground - Ground
Green Relay Contact Relay Contact Relay Contact
White Relay Contact Relay Contact Relay Contact
For installation to an alarm panel, the Red wire is
connected to the positive side of a voltage supply
and the Black wire is connected to the negative.
The Green and White wires can then be connected
to any pre-selected Closed Loop zone. A resistor
can be connected in series with either the Green or
White wire for those panels that require end-of-line
resistance.
After installation these units should be tested with a
damp sponge or paper towel and inspected annually.
If there is any corrosion or damage the sensor should
be replaced.

3
AQUAVAR SOLO, SOLO2AND BALANCED FLOW
Connections for Moisture Sensor (Part Number 9K585) for Balanced Flow, Aquavar SOLO, SOLO2and
3AB2, 5AB2; AB2 Controllers
Connect White and
Green wires from
Moisture Sensor to
the RUN/STOP INPUT
marked "JUMPER TO
RUN" on controller.
Connect Black wire from Moisture Sensor to
transducer terminal marked "B" on controller.
Connect Red wire
from Moisture
Sensor to transducer
terminal marked "R"
on controller.
WIRING 2 OR MORE MOISTURE SENSOR
RELAY IN SERIES
Connect Black and Red wires to the transducer
terminal. Connect the white wire from sensor 1 and
green wire from sensor 2 to the Run/Stop input
terminal. Then wire the green wire from sensor 1
to the white wire of sensor 2. Now these sensors
are wired in series. After all connections are made,
perform a test to ensure the drive turns off when
moisture is present at the sensors.
Aquavar SOLO UIB Board
Transducer Block
Wire 2 Sensors in Series
Two Sensors
Run Stop / Input
BR
WW
GG
Black
Red
White
Green
Black
Red
White
Green
Sensor 1 Sensor 2

4
AQUAVAR AB2 OR AQUABOOST II
Connect Black wire
from Moisture Sensor
to terminal marked
"Com. (Blk)" on
controller.
Connect Red wire from
Moisture Sensor to
terminal marked "+5V
(Red)" on controller.
Connect Green wire
from Moisture Sensor
to terminal marked
"Input (Wht)" on
controller.
Connect White
wire from Moisture
Sensor to the White
wire of the pressure
transducer cable with
a wire nut
S-DRIVE AND AQUAVAR SPD
Connect White and Green wires
from Moisture Sensor to the
terminals 1 and 2 on controller.
Connect Red wire from
Moisture Sensor to the terminal
number 8 on controller.
Connect
Black wire
from Moisture
Sensor to
the terminal
number 9 on
controller.

5
e-SM WITH MOISTURE SENSOR
Connections for Moisture Sensor (Part Number 9K584) for eSM Smart Motors
Connect green wire
from Moisture Sensor
to terminal 11 (Start)
on eSM
Connect red wire from Moisture
Sensor to terminal 6 (15VDC) on
eSM
Connect white wire
from Moisture Sensor
to terminal 12 (Stop)
on eSM
Connect black wire
from Moisture Sensor
to terminal 17 (GND)
on eSM

6
IPC WITH MOISTURE SENSOR
Connections for Moisture Sensor (Part Number 9K583) to IPC and Hydrovar
Connect red and green wires from
Moisture Sensor to terminal 13 (24
V OUT) on IPC
Connect white wire
from Moisture Sensor
to terminal 18 (D IN)
on IPC
Connect black wire
from Moisture Sensor
to terminal 20 (COM)
on IPC

7
HYDROVAR WITH MOISTURE SENSOR
Connect green wire
from Moisture Sensor
to terminal 18 (ON/
OFF) on Hydrovar
Connect red wire
from Moisture
Sensor to terminal 4
(24V) on Hydrovar
Connect black wire
from Moisture Sensor
to terminal 6 (GND)
on Hydrovar
Connect white wire
from Moisture Sensor
to terminal 19 (GND)
on Hydrovar

Xylem Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Tel: (866) 673-0445
Fax: (888) 322-5877
www.xylem.com/centripro
CentriPro and Aquavar Solo are trademarks of Xylem Inc. or one of its subsidiaries.
© 2021 Xylem Inc. IM234 Rev 3 September 2021
This manual suits for next models
2
Table of contents
Other Xylem Relay manuals