5
It is recommended that the control band be set as shown:
8°F for D SV300
7°F for D.SV360
L6°F for D. SV480
The controller hasabuilt in feature which providesa4min-
ute off cycle and a4minute on cycle to prevent compressor
rapid cycling.
Whenpower fails, the W7100 shuts off all stages of mechan-
ical cooling.Whenpower ~esumes,the economizer willfirst
be modulated open, prowdedenthalpy of the outside air is
suitable. Once the economizer is open, mechanical coofing
issequenced back on with aminimum of 4minutes between
succeedingstages, If outside air enthalpy is not suitable, econ-
omizer modulation is bypassed, allowingmechanical cooling
to beginsequencingafter 4minutes, with aminimum of 4
minutes between stages.
Whenthe D. SV does not haveeconomizer option, a510
ohm, ]/4 watt, 570 resistor is placed between termina]s9
and Yon the W7100 to eliminate the economizer delayand
energizemechanical coolingimmediately.
COOLING
Whenthe dischargetemperature has deviated 1‘F above(or
below) the control band, additional stagesof coolingwill be
turned on (or off) at four minute intervals until either the
dischargetemperature drops (or rises)to within one degree
of the control band, or the dischargetemperature falls(or
brises)at asufficient rate that will insure that dischargetemp-
erature will soon be within the control band (about 10mm-
utes). The rate feature prevents needlesscycling causedby
changesin load. The last stage to be turned on or off isre-
ferred to as cycfrngstage.
D-SV units have nominal cooling capacities of 25, 30 and
40 tons. The DSV300 has two stagesof capacity achieved
by unloadingasinglecompressor. The D. SV360 has three
sttigesof’capacity achieved by two unloading solenoidson
one compressor.The DSV480 has four stagesof capacity
achieved by two compressorseach with an unloader.
All systems are completely factory assembled, refrigerant
piped, refrigerant chargedand leak tested. Astrainer drier
and atno]stureindicator are installed in each liquid line. A
h]ghpressure cutout is located in each system(’s) on the
compressorbefore the dischargevalveand will de-energiie
the compressor control circuit should the system(’s)dis-
chargepressureexceed 395 psig.The pressurecutout wil[
remain de-energizeduntil the system(‘s)pressure returns to
310 ps]g.The opening of the high pressurecutout wdl en-
ergize thekwkout circuit. The control circuit must be open-
ed and closed to reset the lockout circuit, AntLcycletltning
is part of the compressorprotection module. This prevents
the compressor from lapid short cycling. Alow pressule
cutout 1slocated in each system(‘s)on the compressorbe-
fore the suctmn valveand will de-energl/e the c(~n]plcssor
Lcentrol circu]t should the system(’s) pressuredrop t~~7
psig.This control willautoma[ ically rese[ when the suetl<)n
pressurerises to 22 psig. The operungof the low p[essute
cutout willenergwethe Iociout CIIwit.
The control circuit must be opened and closed to reset the
lockout circuit.
Normalsequence of operation is as follows:
1. Poweris supplied to the unit through the disconnect
switch. The switch can be field-installedor factory-
installed as an option.
2. Assoon as power is supplied to the unit, the compres-
sor crankcase heaters ITH (and 2TH)will be energized,
CAUTIOIV:Do not attempt to start the compressorswirh-
out at least 8hoursof crankcaseheat or com-
pressordamagewill occur.
3. If the unit is not equipped with amorningwarmup ther-
mostat or aday-night switch the 7R relay coil will be
energized. The 7R contact closesenergizingthe 3M coil.
3Mcontacts close, starting the supply air fan motor. Af-
ter an adequate air flow is established, 5LP closesto en-
ergize6R coil, 6R contact closesin the compressor con-
trol circuit. If the unit has aday-nightswitch the switch
must be in the day position. If the unit has amorning
warmup thermostat it must be sat]sfiedor the above fan
and unit operation will not occur.
4. If the D. SVunit does not havean economizer cycle or
if the outdoor enthalpy is too high,on demand ,the dis-
chargeair sensor will signalthe logic panel to closethe
“Cool 1“ contacts and energize IR coil.
5. 1Rcontact closesand energizes IM coil, which starts the
(No. 1) compressor]n an unloaded condition. At the same
time. 4M isenergized to start the condenser fans.
6. If the dischargeair temperature is not within 1°F of the
control band the logic panel will energizethe following
stages.
a. “Cool 2“ contacts will energize.On the D-SV300 this
energizesthe 2R relay. The 2Rcontacts close de-ener-
gizingthe compressor urdoadlngsolenoid which loads
the compressor.On the D. SV360t}usenergizesthe
~R re]uy,The 2R contacts close de-energii.ingthe com-
pressorunloading solenoid which loads the compressor
to 2/3 or full capacity. On the D. SV480 this de-ener-
gi/es the compressorunloading solenoid which loads
t}leNo. 1compressor.
b. “COO13“ contacts will energize. On the D..SV36Othis
de-energizesthe compressor unloading solenoid which
Ioddsthe compressor to full cap~ctty. On the D.SV480
this enclgizes the 2R relay. The 2R conlacts close and
energize 2M COIIwhich starts the No. 2c~~mpressorin
an unk}.ided condition.
c, “COO!4“ contacts will energize. On the D. SV480 this
de-energues the ct~mpressorunloadlngsolenold winch
l(xidsthe No 2compressor.
7, The u(~mpressorshort cycle time and low vt)ltagep]otec-
tmn ISp~rt of [he solid stdte compressor protec~lonm[~d-
ule. It plevents Jcompress(~[fr(~mstarting unless It has
Central Environmental Systems 13