
YORKINTERNATIONAL
2
PRE START-UP
Improper installation, adjustment,
alterations, service or maintenance
can cause injury and property dam-
age,aswell as possible voidingoffac-
tory warranty. For assistance or ad-
ditional information, consult a quali-
fied contractor.
RECEIVINGANDINSPECTING
• Thoroughly examine the exterior and interior of all
units for transportation damage to the cabinet, pip-
ing, blower(s), motor(s), coil(s), electric heat and
electrical components. Interior damage may occur,
even with no visible exterior damage. If damage is
found,immediatelyfileaclaimwith the carrier.Note
the damage on the bill of lading before signing for
the shipment.
• Checkthe bill of lading forverification thatall items
shown (including loose items) have been received.
Notify the manufacturer’s representative of any
shortages or items shipped in error.
UNITRIGGING AND PLACEMENT
• Install ductwork to comply with ASHRAE Funda-
mentals Handbook, SMACNA, NFPA 90A and
local code.
• The installation must conform with local building
codes and the NATIONAL ELECTRIC CODE.
• Locateunitsupport in accordance with the mechani-
cal and structural plans. If so equipped, locate the
isolator placement and correct size as shown on
the submittal drawing.
• Ceiling suspension of horizontal units have factory
provisions for thru bolt hanger rods, except double
wallunits (which require externalrigging) (SeeFig-
ures 1, 2 and 3). If floor mount isolators are re-
quired for either horizontal or vertical units, then
factory or field provisions must be made for isola-
tor attachment. Vertical units can be mounted di-
rectly to the floor or on a base rail. If a base rail is
provided,isolatorscan be installed in mountingholes
provided on this base rail.
• Do not handle the unit using coil stubout connec-
tors, as damage may occur at brazed joint(s).
CLEARANCE
• Allunits,includingthosewithelectric heat, are listed
for zero clearance to combustibles.
• Sufficient clearance for normal servicing of this
equipment is recommended.
• All electrical panels must have 36" working space
in front of panel to meet NATIONAL ELECTRI-
CAL CODE; however, local inspectors may wave
this requirement if the hinged cover has a 90° free
swing.
PRE-STARTUPCHECK
• Prior to starting the unit, check torque of all set
screws on the fan(s), sheaves and bearings where
applicable.
Set screws may loosen during transportation. See
Table 3.
• Sheaves must be in line. Use a straight edge to
verify.