Table 2: Airflow data (CFM)
Models Blower
motor speed External static pressure (in. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
B18B
High (5) 975 925 875 825 800 750 700 650 600 550
Medium high (4) 900 850 800 775 725 675 625 575 525 500
Medium (3) 825 775 725 700 650 600 550 500 450 400
Medium low (2) 650 600 550 500 425 -----
Low (1) 450 - - - - -----
B24C
High (5) 1150 1125 1100 1050 1025 975 950 900 875 850
Medium high (4) 1000 950 925 875 825 775 750 700 650 600
Medium (3) 775 725 675 625 575 525 450 400 - -
Medium low (2) 675 600 550 500 425 -----
Low (1) 525 450 - - - -----
B30D
High (5) 1150 1125 1075 1050 1025 975 950 925 875 850
Medium high (4) 1000 950 900 875 825 800 750 700 675 625
Medium (3) 775 725 700 650 600 550 500 450 400 -
Medium low (2) 650 600 550 500 450 400 - - - -
Low (1) 575 525 475 400 - -----
B36D
High (5) 1500 1475 1450 1425 1425 1400 1375 1350 1325 -
Medium high (4) 1325 1300 1275 1250 1225 1200 1175 1150 1125 1100
Medium (3) 975 950 900 875 825 800 750 700 675 625
Medium low (2) 925 875 825 800 750 700 675 625 575 550
Low (1) 650 600 550 500 450 400 - - - -
C36D
High (5) 1600 1575 1525 1500 1450 1425 1400 1350 1325 1275
Medium high (4) 1400 1375 1325 1275 1225 1200 1150 1100 1075 1025
Medium (3) 1100 1050 1000 950 900 850 800 725 675 625
Medium low (2) 950 900 825 775 725 650 600 550 475 425
Low (1) 725 650 575 525 450 375 - - - -
C42F
High (5) 1525 1500 1450 1425 1375 1350 1300 1275 1225 1200
Medium high (4) 1375 1325 1300 1250 1200 1150 1125 1075 1025 975
Medium (3) 1050 1000 950 900 850 775 725 675 625 575
Medium low (2) 925 875 800 750 700 625 575 525 450 400
Low (1) 700 625 575 500 425 -----
C48G
High (5) 1925 1900 1875 1850 1800 1775 1750 1725 1700 1675
Medium high (4) 1750 1700 1675 1650 1600 1575 1550 1500 1475 1450
Medium (3) 1400 1350 1300 1275 1225 1175 1125 1075 1050 1000
Medium low (2) 1200 1150 1100 1050 1000 925 875 825 775 725
Low (1) 925 875 800 750 700 625 575 500 450 375
D48G
High (5) 2050 2000 1975 1950 1900 1875 1850 1800 1775 1750
Medium high (4) 1850 1800 1775 1725 1700 1650 1625 1575 1550 1500
Medium (3) 1625 1600 1550 1500 1450 1425 1375 1325 1275 1250
Medium low (2) 1275 1200 1150 1100 1050 975 925 875 825 750
Low (1) 1000 925 875 800 750 675 600 550 475 400
C60H
High (5) 1925 1900 1875 1850 1825 1775 1750 1725 1700 1675
Medium high (4) 1750 1725 1675 1650 1625 1575 1550 1525 1475 1450
Medium (3) 1375 1350 1300 1250 1225 1175 1125 1100 1050 1000
Medium low (2) 1200 1150 1100 1050 1000 950 900 850 800 750
Low (1) 950 900 825 775 725 650 600 550 475 425
D60H
High (5) 1925 1900 1875 1825 1800 1775 1750 1700 1675 1650
Medium high (4) 1775 1750 1725 1675 1650 1600 1575 1525 1500 1450
Medium (3) 1450 1400 1325 1275 1225 1175 1125 1075 1025 975
Medium low (2) 1225 1175 1125 1050 1000 950 875 825 775 700
Low (1) 975 900 850 775 700 625 550 475 425 -
Continued on next page
Table 2: Airflow data (CFM) (continued)
Notes:
1. No electric heat installed
2. Air handler units are tested to UL60335-2-40 standards up to 0.6 in. W.C. external static pressure.
3. Dry coil conditions only; tested without filters
4. For optimal performance, external static pressures of 0.2 in. W.C. to 0.5 in. W.C. are recommended. Heating applications are tested at 0.5 in. W.C. external static pressure.
5. Airflow data shown is from testing performed at 230 V. These units use a standard ECM constant torque motor and there is minimal variation of airflow at other distribution
voltage values. The above data can be used for airflow at other distribution voltages.
Clearances
It is essential to provide the following clearances:
1. Refrigerant piping and connections - minimum 12 in.
2. Maintenance and servicing access - minimum 36 in. from the front of
the unit for blower motor or coil replacement
3. Condensate drain lines routed to clear filter and panel access
4. Filter removal - minimum 36 in.
5. The supply air ductwork connected to this unit is designed for 1 in.
clearance for the first 18 in. of combustible materials if an electric heat
kit accessory is installed.
6. A combustible floor base accessory is available for downflow applica-
tions of this unit, if required by local code.
External duct static
Measure the supply air static pressure. Record this positive number.
Measure the return air static pressure. Record this negative number.
Treat the negative number as a positive and add the two numbers
together to determine the total external system static pressure. If a filter
rack is installed on the return air end of the air handler or indoor coil
section, make sure to measure the return air duct static between the filter
and the indoor coil.
Figure 2: Duct static measurements
Models Blower
motor speed External static pressure (in. W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
D60J
High (5) 2100 2075 2050 2025 2000 1975 1925 1900 1875 1850
Medium high (4) 1925 1900 1875 1825 1800 1775 1725 1700 1675 1650
Medium (3) 1750 1725 1675 1650 1600 1575 1525 1500 1450 1425
Medium low (2) 1350 1275 1225 1175 1125 1075 1025 975 925 875
Low (1) 1200 1150 1100 1025 975 925 850 800 750 675
Take measurements here if using
a filter rack.
Return air static must be taken
between the filter and indoor coil.
A1704-001
Table 3: Electrical heat - minimum fan speed
Heater kit
models1,2
Nominal
kW
at 240 V
Air handler models
B18B B24C B30D B36D C36D C42F C48G D48G C60H D60H D60J
8HK(0,1)6500206 2.4 Medium
Low (2) Medium
(3) Medium
High (4) Medium
(3) Medium
(3) Medium
(3) Medium
Low (2) Medium
Low (2) Medium
Low (2) Medium
Low (2) Medium
Low (2)
8HK(0,1)6500506 4.8 Medium
(3) Medium
(3) Medium
High (4) Medium
(3) Medium
(3) Medium
(3) Medium
Low (2) Medium
Low (2) Medium
Low (2) Medium
Low (2) Medium
Low (2)
8HK(0,1)6500806 7.7 Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
(3) Medium
(3) Medium
(3) Medium
(3) Medium
Low (2)
8HK(0,1)6501006
8HK06501025 9.6 Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
High (4) Medium
(3) Medium
(3) Medium
High (4) Medium
(3) Medium
Low (2)
8HK(1,2)6501506
8HK06501525 14.4 - Medium
High (4) High (5) Medium
High (4) Medium
High (4) Medium
High (4) Medium
(3) Medium
(3) Medium
High (4) Medium
High (4) Medium
(3)
8HK(1,2)6502006
8HK16502025 19.2 - - High (5) Medium
High (4) High (5) High (5) Medium
High (4) Medium
(3) Medium
High (4) Medium
High (4) Medium
(3)
8HK(1,2)6502506
8HK16502525 24---------Medium
High (4) Medium
(3)
1.(0,1) - 0 = no service disconnect or 1 = with service disconnect
2.(1,2) - 1 = with service disconnect, no breaker jumper bar or 2 = with service disconnect and breaker jumper bar